Yodify Product Library
Instantly add the IPAQ C520 Universal HART Transmitter and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
IPAQ C520 Universal HART Transmitter
Brand: InorThe IPAQ C520 Transmitters are universal, isolated, dual-input temperature transmitters with additional voltage and resistance input.
The IPAQ C520N is approved for Non-Incendive use in Ex-Zone 2.
C520X/C520XS are Intrinsically Safe versions for use in Ex-Zone 0, 1 and 2.
The transmitters are compatible with the HART 6 protocol.
Typical characteristics are the high accuracy, stability and reliability combined with a robust housing.
Features- Universal, Dual-input for RTD and T/C
- SIL 2 Compatible According to IEC 61508-2
- Withstands 10 g Vibrations
- Complies with NAMUR NE 21, NE 43, NE 53, NE 89 and NE 107
- EMC Immunity According to Criteria A
- Sensor Backup
- Sensor Drift Monitoring
- Sensor Isolation Monitoring
- Sensor Matching
- 50 Pint Customized Linearization
- Integrated in Emerson AMS and Siemens PDM Systems
1 - 8 of 8 Part Numbers
70ADA00027
- Model - Head Mounting Kit
70C5200010
- Model - C520
70C5200S10
- Model - C520S, SIL 2 Compatible
70C520N010
- Model - C520N
70C520X010
- Model - C520X
70C520XS10
- Model - C520XS, SIL 2 Compatible
70CAL00001
- Model - Configuration
70CFGUS001
- Model - ICON PC Configuration Kit (USB-Connection)
1 - 8 of 8 Part Numbers
Specifications
Brand
Accuracy
- ± 0.05 % of Span
- ± 0.1°C (± 0.2°F)
Ambient Temperature Range
- -40°C to 85°C (-40°F to 185°F)
Approvals & Certifications
- ATEX II 1 G Ex ia IIC T4-T6
- ATEX II 3 G Ex NL IIC T4-T6
- CE
- EMC
- IEC 60751
- NAMUR
- SIL 2
Communication
- HART
Electrical Connectors
- DIN 43760 - RTD Sensor
Input
- -10 to 1,000 mV
- Thermocouple B, C, D, E, J, K, N, R, S, T
Input Signal
- RTD
Isolation
- 1,500 VAC, 1 Minute - Galvanic
Output
- 20-4 mA
- 4-20 mA
Power Requirement
- 10-30 VDC - I.S. Power Supply
- 10-36 VDC - Standard
Resistance
- 100 to 4,000 ohms - Input Resistance
RTD Type
- Cu10
- Ni100
- Ni1000
- Ni120
- Pt100
Sensor, Probe Connection
- 2-Wire
- 3-Wire
- 4-Wire
Stability
- Maximum
Temperature Range
- -200°C to 850°C (-328°F to 1,562°F)