Yodify Product Library
Instantly add the Water Treatment Airflow Sensor Monitoring and 50,000+ more product series to your store or catalog  
Book Your Demo and See How
or create your store

Water Treatment Airflow Sensor Monitoring

Brand: Moore Industries

In municipal and industrial wastewater treatment, aeration is part of the secondary treatment process. 

The activated sludge process is the most common option in secondary treatment. In industrial use, a common method of aeration is air diffusion method, in which air is diffused into a receiving vessel containing counter-current flowing water, to remove dissolved gases, such as carbon dioxide, Hydrogen Sulfide or methane, and to oxidize dissolved metals such as iron. 

If air header flow rates being supplied by compressors are not sufficient, the secondary treatment process will be incomplete and may yield contaminated water to rivers and other environmental water sources.
Features
  • Powers and Receives 4-20mA Signal from Airflow Sensor
  • Dual field configurable alarms capable of alarming on
    NAMUR failure output range from Airflow Sensor
  • Relays rated 5A, 250VAC
  • 50msec response time
  • Adjustable deadband for each alarm

Specifications

Repeatability

  • Trip point repeats within ± 0.1 % of Full Scale

Stability

  • Trip point within ± 0.2 % of Span per year

Burden

  • 4-20 mA is 1 V, max
  • 0-5 A is 0.01 V, max

Power Consumption

  • 1.5 W, typical
  • 2.5 W, typical with -TX option
  • 3.5 W max, with -TX option

Deadband

  • 1-20 % of Span standard

Alarm Response

  • 50 msec for a step change of 10-90 % beyond trip point(s)

Line Voltage Effect

  • 0.005 % per 10 % line change

Isolation

  • 1500 Vrms between input, output and power

Maximum Input Overrange

  • 200 % of Full Scale for DC Current input, 150 % of Full Scale for DC Voltage and AC Current inputs

Operating Range

  • -20° C to +70° C (-4° F to +158° F)

Relative Humidity

  • 0-95 %, Non-Condensing

Ambient Effect

  • ± 0.007 % of Span/°C, typical, ± 0.015 % of Span/°C, max

RFI/EMI Protection

  • Trip point not to be affected by more than 0.1 % of Span at 10 V/m, 20-1000 MHz

Trip Points

  • Multiturn front panel potentiometers adjust trip point from 0-110 % of input span

Indicators

  • Front panel LED(s) is ON when relay is energized

Weight

  • 454 grams (1 lb)

Documentation

Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team