Yodify Product Library
Instantly add the RF Capacitance Level Control and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
RF Capacitance Level Control
Brand: SOR IncSelecting the right probe for your application is very important. The objective is to maximize the amount of capacitance change for every inch (cm) of level change.
Following are general guidelines for selecting a probe for a particular application:
- If process media is non-conductive - less than 10 µ Siemens/low dielectric (less than 10), select a bare probe
- If process media is conductive - greater than 10µ Siemens/high dielectric (greater than 10), select an insulated probe
- If process is non-conductive and in a horizontal (bullet) tank, or if the probe must be mounted more than 12" from the vessel wall, select a stilling well, dual-rod or dual-cable probe
- If vessel is non-metallic, select a stilling well, dual-rod or dual-cable probe
- Use rigid probes for measurement lengths of 10 feet or less. Use cable probes for longer ranges
Specifications
Brand
Approvals & Certifications
- Hydrostatic Pressure Test
- Typical Material of Wetted Parts
Approvals & Certifications
- CSA
- FM
- IECEX
- INMETRO
Flange Size - 1-1/2” (DN 40)
- 1-1/2” (DN 40) - 150# ANSI
- 1-1/2” (DN 40) - 300# ANSI
Flange Size - 1” (DN 25)
- 1” (DN 25) - 150# ANSI
- 1” (DN 25) - 300# ANSI
Flange Size - 2” (DN 50)
- 2” (DN 50) - 150# ANSI
- 2” (DN 50) - 300#
Flange Size - 3” (DN 80)
- 3” (DN 80) - 150#
- 3” (DN 80) - 300# ANSI
Flange Size - 4” (DN 100)
- 4” (DN 100) - 150# ANSI
- 4” (DN 100) - 300# ANSI
Flange Type
- Raised Face (RF)
Maximum System Pressure
- psi: 725.2 (kPa: 5,000, bar: 50)
Name Plate, Tag Material
- Stainless Steel
- Fiber
NPT Connection
- 1” NPT
- 1-1/2” NPT
- 2” NPT
- 3/4” NPT
Process Temperature
- -73° to 204° C (-100° to 400° F)
Sensor, Probe Diameter
- 5/16” to 1.05” (7.9 to 26.7 mm)
Sensor, Probe Length
- 1 to 1,440” (2.54 to 3,658 cm)
Sensor, Probe Material
- Probe: Flexible Kynar
- Probe: Rigid 316 Stainless Steel
- Probe: Rigid Teflon
- Sensor: 316 Stainless Steel
- Sensor: Polished 316L Stainless Steel
Tri-Clamp Connection
- 1” Sanitary Clamp
- 1-1/2” Sanitary Clamp
- 2” Sanitary Clamp