Binary Output Series 9175
Brand: R. STAHL AG9175 series binary outputs issue binary signals via one or two channels for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices feature three-way galvanic separation.
A wire-breakage and short-circuit monitoring system, which can be disconnected, directly monitors the state of the field circuit.
Features- Comprehensive portfolio to cater for all characteristics
- Two-channel variants reduce the amount of space required
- Can be used up to SIL 3 (IEC/EN 61508)
1 - 12 of 12 Part Numbers

160398
Comprehensive portfolio to cater for all characteristics
two-channel variants reduce the amount of space required
can be used up to SIL 3 (IEC/EN 61508)
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
- Ambient temperature max. - +70 °C
- Ambient temperature max. note - Single device
- Ambient temperature max. note 2 - Group assembly
- Ambient temperature max.2 - +60 °C
- Ambient temperature min. - -20 °C
- Ambient temperature min. 2 - -20 °C
- Ambient temperature min. note - Single device
- Ambient temperature min. note 2 - Group assembly
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
- Relative humidity max. - 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power voltage range - 18 ... 31,2 V
- Nominal current - 80.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 1.90 W
- Power dissipation max. - 1.40 W
- Undervoltage monitoring - Yes
- Voltage range residual ripple - ≤ 3,6 VSS
Electrical Data
- Number of channels - 1
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - DMT 03 ATEX E 043 X
- ATEX gas certificate - DMT 03 ATEX E 043 X
- Certificate EAC - TS RU S-DE.GB04.B.00353
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM), USA (UL)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA nC [ia Ga] IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA nC [ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx BVS 10.0050 X
- IECEX gas certificate - IECEx BVS 10.0050 X
- Installation in Division NEC 500 - (Class I, II, III) 2
- Ship approval - CCS, DNVGL
Galvanic isolation
- Galvanic isolation Ex i output to auxiliary power - 1,5 kV AC
- Galvanic isolation Ex i output to fault message contact - 1,5 kV AC
- Galvanic isolation Ex i output to input - 1,5 kV AC
- Galvanic isolation fault message contact to auxiliary power - 350 V AC
- Galvanic isolation fault message contact to input - 350 V AC
- Galvanic isolation input to auxiliary power - 350 V AC
- Galvanic isolation input to input - 350 V AC
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 50178
General
- Functional Description - 9175 series binary outputs issue binary signals via one or two channels for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices feature three-way galvanic separation. A wire-breakage and short-circuit monitoring system, which can be disconnected, directly monitors the state of the field circuit.
- Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
- Product Description - Binary output Ex i field circuit
- Product Type - 9175/10-12-11s
- WebCode - 9175A
Input
- Control current - < 5 mA
- Input - In accordance with EN 61131-2
- Input voltage for OFF - 0 - 5 V
- Input voltage for ON - 15.0 - 31.2 V
Mechanical Data
- Connection cross-section - 0.2-2.5 mm² flexible 0.25-2.5 mm² flexible core end sleeve 0.2-2.5 mm² rigid
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 17.60 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.175 kg
Mounting / Installation
- Conduct cross-section flexible max. - 2.5 mm²
- Conduct cross-section flexible max. - 0.2 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Screw terminal
- Mounting position - vertical horizontal
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Error detection wire breakage - > 7 kΩ
- Indication of line fault - "LF" LED, red
- Internal Resistance R i - 150.00 Ω
- LFD relay - Yes
- Max. output current I a max - 60.00 mA
- Message of line fault and Auxilliary power failure - - Contact (30 V / 100 mA) closed to ground in case of fault - pac-Bus, floating contact (30 V / 100 mA)
- Note - You can find a list of connectible Ex i solenoid valves on our homepage www.r-stahl.com (WebCode 9175A)
- Output internal resistiance R i - 150.00 Ω
- Output open circuit voltage U a - 10,00 V
- Output residual ripple - < 50 mV
- Output switching frequency - <= 200 Hz
- Short circuit error detection - 40 ... 60 Ω ± 3 Ω /10 K
- Switch user adjustment line fault - activated / deactivated
- Switching capacity fault message contact - 30 V / 100 mA
- Switching delay ON/OFF - ≤ 1 ms
- Switching state indication - Yellow LED "OUT"
- test current - 2.7 mA (at 100-ohm load)
- test current 2 - 0.68 mA (at 7-kΩ load)
Safety Data
- Internal capacitance C i - 1.1 nF
- Internal inductance L i - negligible
- Max. current I o (Ex ia) - 75.00 mA
- Max. permissible external capacitance C o for IIB - 12.100 μF
- Max. permissible external capacitance C o for IIC - 1.790 μF
- Max. permissible external inductance L o for IIB - 25.000 mH
- Max. permissible external inductance L o for IIC - 6.300 mH
- Max. Power P o - 210.000 mW
- Max. Voltage U o - 11.30 V
- Safety-related maximum voltage - 253 V

160400
Comprehensive portfolio to cater for all characteristics
two-channel variants reduce the amount of space required
can be used up to SIL 3 (IEC/EN 61508)
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
- Ambient temperature max. - +70 °C
- Ambient temperature max. note - Single device
- Ambient temperature max. note 2 - Group assembly
- Ambient temperature max.2 - +60 °C
- Ambient temperature min. - -20 °C
- Ambient temperature min. 2 - -20 °C
- Ambient temperature min. note - Single device
- Ambient temperature min. note 2 - Group assembly
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
- Relative humidity max. - 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power voltage range - 18 ... 31,2 V
- Nominal current - 80.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 1.90 W
- Power dissipation max. - 1.40 W
- Undervoltage monitoring - Yes
- Voltage range residual ripple - ≤ 3,6 VSS
Electrical Data
- Number of channels - 1
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - DMT 03 ATEX E 043 X
- ATEX gas certificate - DMT 03 ATEX E 043 X
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM), USA (UL)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA nC [ia Ga] IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA nC [ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx BVS 10.0050 X
- IECEX gas certificate - IECEx BVS 10.0050 X
- Installation in Division NEC 500 - (Class I, II, III) 2
- Ship approval - CCS, DNVGL
Galvanic isolation
- Galvanic isolation Ex i output to auxiliary power - 1,5 kV AC
- Galvanic isolation Ex i output to fault message contact - 1,5 kV AC
- Galvanic isolation Ex i output to input - 1,5 kV AC
- Galvanic isolation fault message contact to auxiliary power - 350 V AC
- Galvanic isolation fault message contact to input - 350 V AC
- Galvanic isolation input to auxiliary power - 350 V AC
- Galvanic isolation input to input - 350 V AC
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 50178
General
- Functional Description - 9175 series binary outputs issue binary signals via one or two channels for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices feature three-way galvanic separation. A wire-breakage and short-circuit monitoring system, which can be disconnected, directly monitors the state of the field circuit.
- Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
- Product Description - Binary output Ex i field circuit
- Product Type - 9175/10-12-11k
- Title Product Variant Technical Data - 9175/10-12-11k binary output
- WebCode - 9175A
Input
- Control current - < 5 mA
- Input - In accordance with EN 61131-2
- Input voltage for OFF - 0 - 5 V
- Input voltage for ON - 15.0 - 31.2 V
Mechanical Data
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 17.60 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.111 kg
Mounting / Installation
- Conduct cross-section flexible max. - 2.5 mm²
- Conduct cross-section flexible max. - 0.2 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Spring clamp terminal
- Mounting position - horizontal vertical
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Error detection wire breakage - > 7 kΩ
- Indication of line fault - "LF" LED, red
- Internal Resistance R i - 150.00 Ω
- LFD relay - Yes
- Max. output current I a max - 60.00 mA
- Message of line fault and Auxilliary power failure - - Contact (30 V / 100 mA) closed to ground in case of fault - pac-Bus, floating contact (30 V / 100 mA)
- Output internal resistiance R i - 150.00 Ω
- Output open circuit voltage U a - 10,00 V
- Output residual ripple - < 50 mV
- Output switching frequency - <= 200 Hz
- Short circuit error detection - 40 ... 60 Ω ± 3 Ω /10 K
- Switch user adjustment line fault - activated / deactivated
- Switching capacity fault message contact - 30 V / 100 mA
- Switching delay ON/OFF - ≤ 1 ms
- Switching state indication - Yellow LED "OUT"
- test current - 2.7 mA (at 100-ohm load)
- test current 2 - 0.68 mA (at 7-kΩ load)
Safety Data
- Internal capacitance C i - 1.1 nF
- Internal inductance L i - negligible
- Max. current I o (Ex ia) - 75.00 mA
- Max. permissible external capacitance C o for IIB - 12.100 μF
- Max. permissible external capacitance C o for IIC - 1.790 μF
- Max. permissible external inductance L o for IIB - 25.000 mH
- Max. permissible external inductance L o for IIC - 6.300 mH
- Max. Power P o - 210.000 mW
- Max. Voltage U o - 11.30 V
- Safety-related maximum voltage - 253 V

160404
Comprehensive portfolio to cater for all characteristics
two-channel variants reduce the amount of space required
can be used up to SIL 3 (IEC/EN 61508)
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
- Ambient temperature max. - +70 °C
- Ambient temperature max. note - Single device
- Ambient temperature max. note 2 - Group assembly
- Ambient temperature max.2 - +60 °C
- Ambient temperature min. - -20 °C
- Ambient temperature min. 2 - -20 °C
- Ambient temperature min. note - Single device
- Ambient temperature min. note 2 - Group assembly
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
- Relative humidity max. - 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power voltage range - 18 ... 31,2 V
- Nominal current - 140.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 3.40 W
- Power dissipation max. - 2.40 W
- Undervoltage monitoring - Yes
- Voltage range residual ripple - ≤ 3,6 VSS
Electrical Data
- Number of channels - 2
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - DMT 03 ATEX E 043 X
- ATEX gas certificate - DMT 03 ATEX E 043 X
- Certificate EAC - TS RU S-DE.GB04.B.00353
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM), USA (UL)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA nC [ia Ga] IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA nC [ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx BVS 10.0050 X
- IECEX gas certificate - IECEx BVS 10.0050 X
- Installation in Division NEC 500 - (Class I, II, III) 2
- Ship approval - CCS, DNVGL
Galvanic isolation
- Galvanic isolation Ex i output to auxiliary power - 1,5 kV AC
- Galvanic isolation Ex i output to fault message contact - 1,5 kV AC
- Galvanic isolation Ex i output to input - 1,5 kV AC
- Galvanic isolation Ex i to Ex i - N/A
- Galvanic isolation fault message contact to auxiliary power - 350 V AC
- Galvanic isolation fault message contact to input - 350 V AC
- Galvanic isolation input to auxiliary power - 350 V AC
- Galvanic isolation input to input - 350 V AC
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 50178
General
- Functional Description - 9175 series binary outputs issue binary signals via one or two channels for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices feature three-way galvanic separation. A wire-breakage and short-circuit monitoring system, which can be disconnected, directly monitors the state of the field circuit.
- Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
- Product Description - Binary output Ex i field circuit
- Product Type - 9175/20-12-11s
- Title Product Variant Technical Data - Type 9175/20-12-11.
- WebCode - 9175A
Input
- Control current - < 5 mA
- Input - In accordance with EN 61131-2
- Input voltage for OFF - 0 - 5 V
- Input voltage for ON - 15.0 - 31.2 V
Mechanical Data
- Connection cross-section - 0.2-2.5 mm² flexible 0.25-2.5 mm² flexible core end sleeve 0.2-2.5 mm² rigid
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 17.60 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.190 kg
Mounting / Installation
- Conduct cross-section flexible max. - 2.5 mm²
- Conduct cross-section flexible max. - 0.2 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Screw terminal
- Mounting position - horizontal vertical
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Error detection wire breakage - > 7 kΩ / > 3,5 kΩ
- Indication of line fault - "LF" LED, red
- Internal Resistance R i - 150 Ω / 75 Ω*
- Internal resistance R i note - 150 Ω / 75 Ω
- LFD relay - Yes
- Max. output current I a max - 60 mA / 120 mA*
- Max. output current I a note - 60 mA / 120 mA
- Message of line fault and Auxilliary power failure - - Contact (30 V / 100 mA) closed to ground in case of fault - pac-Bus, floating contact (30 V / 100 mA)
- Note - You can find a list of connectible Ex i solenoid valves on our homepage www.r-stahl.com (WebCode 9175A)
- Output open circuit voltage U a - 10,00 V
- Output residual ripple - < 50 mV
- Output switching frequency - <= 200 Hz
- Parallel error detection short ciruit - 20 ... 30 Ω ± 3 Ω /10 K
- Short circuit error detection - 40 ... 60 Ω ± 3 Ω /10 K
- Switch user adjustment line fault - activated / deactivated
- Switching capacity fault message contact - 30 V / 100 mA
- Switching delay ON/OFF - ≤ 1 ms
- Switching state indication - Yellow LED "OUT"
- test current - 2.7 mA (at 100-ohm load)
- test current 2 - 0.68 mA (at 7-kΩ load)
Safety Data
- Internal capacitance C i - 1.1 nF
- Internal inductance L i - negligible
- Max. current I o (Ex ia) - 75.00 mA
- Max. permissible external capacitance C o for IIB - 12.100 μF
- Max. permissible external capacitance C o for IIC - 1.790 μF
- Max. permissible external inductance L o for IIB - 25.000 mH
- Max. permissible external inductance L o for IIC - 6.300 mH
- Max. Power P o - 210.000 mW
- Max. Voltage U o - 11.30 V
- Safety-related maximum voltage - 253 V

160406
Comprehensive portfolio to cater for all characteristics
two-channel variants reduce the amount of space required
can be used up to SIL 3 (IEC/EN 61508)
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
- Ambient temperature max. - +70 °C
- Ambient temperature max. note - Single device
- Ambient temperature max. note 2 - Group assembly
- Ambient temperature max.2 - +60 °C
- Ambient temperature min. - -20 °C
- Ambient temperature min. 2 - -20 °C
- Ambient temperature min. note - Single device
- Ambient temperature min. note 2 - Group assembly
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
- Relative humidity max. - 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power voltage range - 18 ... 31,2 V
- Nominal current - 140.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 3.40 W
- Power dissipation max. - 2.40 W
- Undervoltage monitoring - Yes
- Voltage range residual ripple - ≤ 3,6 VSS
Electrical Data
- Number of channels - 2
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - DMT 03 ATEX E 043 X
- ATEX gas certificate - DMT 03 ATEX E 043 X
- Certificate EAC - TS RU S-DE.GB04.B.00353
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM), USA (UL)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA nC [ia Ga] IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA nC [ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx BVS 10.0050 X
- IECEX gas certificate - IECEx BVS 10.0050 X
- Installation in Division NEC 500 - (Class I, II, III) 2
- Ship approval - CCS, DNVGL
Galvanic isolation
- Galvanic isolation Ex i output to auxiliary power - 1,5 kV AC
- Galvanic isolation Ex i output to fault message contact - 1,5 kV AC
- Galvanic isolation Ex i output to input - 1,5 kV AC
- Galvanic isolation Ex i to Ex i - N/A
- Galvanic isolation fault message contact to auxiliary power - 350 V AC
- Galvanic isolation fault message contact to input - 350 V AC
- Galvanic isolation input to auxiliary power - 350 V AC
- Galvanic isolation input to input - 350 V AC
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 50178
General
- Functional Description - 9175 series binary outputs issue binary signals via one or two channels for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices feature three-way galvanic separation. A wire-breakage and short-circuit monitoring system, which can be disconnected, directly monitors the state of the field circuit.
- Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
- Product Description - Binary output Ex i field circuit
- Product Type - 9175/20-12-11k
- Title Product Variant Technical Data - 9175/20-12-11k digital output
- WebCode - 9175A
Input
- Control current - < 5 mA
- Input - In accordance with EN 61131-2
- Input voltage for OFF - 0 - 5 V
- Input voltage for ON - 15.0 - 31.2 V
Mechanical Data
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 17.60 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.111 kg
Mounting / Installation
- Conduct cross-section flexible max. - 0.2 mm²
- Conduct cross-section flexible max. - 2.5 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Spring clamp terminal
- Mounting position - vertical horizontal
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Error detection wire breakage - > 7 kΩ / > 3,5 kΩ
- Indication of line fault - "LF" LED, red
- Internal Resistance R i - 150 Ω / 75 Ω*
- Internal resistance R i note - 150 Ω / 75 Ω
- LFD relay - Yes
- Max. output current I a max - 60 mA / 120 mA*
- Max. output current I a note - 60 mA / 120 mA
- Message of line fault and Auxilliary power failure - - Contact (30 V / 100 mA) closed to ground in case of fault - pac-Bus, floating contact (30 V / 100 mA)
- Note - You can find a list of connectible Ex i solenoid valves on our homepage www.r-stahl.com (WebCode 9175A)
- Output open circuit voltage U a - 10,00 V
- Output residual ripple - < 50 mV
- Output switching frequency - <= 200 Hz
- Parallel error detection short ciruit - 20 ... 30 Ω ± 3 Ω /10 K
- Short circuit error detection - 40 ... 60 Ω ± 3 Ω /10 K
- Switch user adjustment line fault - activated / deactivated
- Switching capacity fault message contact - 30 V / 100 mA
- Switching delay ON/OFF - ≤ 1 ms
- Switching state indication - Yellow LED "OUT"
- test current - 2.7 mA (at 100-ohm load)
- test current 2 - 0.68 mA (at 7-kΩ load)
Safety Data
- Internal capacitance C i - 1.1 nF
- Internal inductance L i - negligible
- Max. current I o (Ex ia) - 75.00 mA
- Max. permissible external capacitance C o for IIB - 12.100 μF
- Max. permissible external capacitance C o for IIC - 1.790 μF
- Max. permissible external inductance L o for IIB - 25.000 mH
- Max. permissible external inductance L o for IIC - 6.300 mH
- Max. Power P o - 210.000 mW
- Max. Voltage U o - 11.30 V
- Safety-related maximum voltage - 253 V

160410
Comprehensive portfolio to cater for all characteristics
two-channel variants reduce the amount of space required
can be used up to SIL 3 (IEC/EN 61508)
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
- Ambient temperature max. - +70 °C
- Ambient temperature max. note - Single device
- Ambient temperature max. note 2 - Group assembly
- Ambient temperature max.2 - +60 °C
- Ambient temperature min. - -20 °C
- Ambient temperature min. 2 - -20 °C
- Ambient temperature min. note - Single device
- Ambient temperature min. note 2 - Group assembly
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
- Relative humidity max. - 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power voltage range - 18 ... 31,2 V
- Nominal current - 80.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 1.90 W
- Power dissipation max. - 1.40 W
- Undervoltage monitoring - Yes
- Voltage range residual ripple - ≤ 3,6 VSS
Electrical Data
- Number of channels - 1
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - DMT 03 ATEX E 043 X
- ATEX gas certificate - DMT 03 ATEX E 043 X
- Certificate EAC - TS RU S-DE.GB04.B.00353
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM), USA (UL)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA nC [ia Ga] IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA nC [ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx BVS 10.0050 X
- IECEX gas certificate - IECEx BVS 10.0050 X
- Installation in Division NEC 500 - (Class I, II, III) 2
- Ship approval - CCS, DNVGL
Galvanic isolation
- Galvanic isolation Ex i output to auxiliary power - 1,5 kV AC
- Galvanic isolation Ex i output to fault message contact - 1,5 kV AC
- Galvanic isolation Ex i output to input - 1,5 kV AC
- Galvanic isolation fault message contact to auxiliary power - 350 V AC
- Galvanic isolation fault message contact to input - 350 V AC
- Galvanic isolation input to auxiliary power - 350 V AC
- Galvanic isolation input to input - 350 V AC
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 50178
General
- Functional Description - 9175 series binary outputs issue binary signals via one or two channels for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices feature three-way galvanic separation. A wire-breakage and short-circuit monitoring system, which can be disconnected, directly monitors the state of the field circuit.
- Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
- Product Description - Binary output Ex i field circuit
- Product Type - 9175/10-14-11s
- Title Product Variant Technical Data - Type 9175/.0-14-11.
- WebCode - 9175A
Input
- Control current - < 5 mA
- Input - In accordance with EN 61131-2
- Input voltage for OFF - 0 - 5 V
- Input voltage for ON - 15.0 - 31.2 V
Mechanical Data
- Connection cross-section - 0.2-2.5 mm² flexible 0.25-2.5 mm² flexible core end sleeve 0.2-2.5 mm² rigid
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 17.60 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.175 kg
Mounting / Installation
- Conduct cross-section flexible max. - 2.5 mm²
- Conduct cross-section flexible max. - 0.2 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Screw terminal
- Mounting position - vertical horizontal
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Error detection wire breakage - > 10 kΩ
- Indication of line fault - "LF" LED, red
- Internal Resistance R i - 130.00 Ω
- LFD relay - Yes
- Max. output current I a max - 45.00 mA
- Message of line fault and Auxilliary power failure - - Contact (30 V / 100 mA) closed to ground in case of fault - pac-Bus, floating contact (30 V / 100 mA)
- Output internal resistiance R i - 130.00 Ω
- Output open circuit voltage U a - 17,50 V
- Output residual ripple - < 50 mV
- Output switching frequency - <= 200 Hz
- Short circuit error detection - 40 ... 80 Ω ± 6 Ω /10 K
- Switch user adjustment line fault - activated / deactivated
- Switching capacity fault message contact - 30 V / 100 mA
- Switching delay ON/OFF - ≤ 1 ms
- Switching state indication - Yellow LED "OUT"
- test current - 2.1 mA (at 100-ohm load)
- test current 2 - 0.76 mA (at 10-kΩ load)
Safety Data
- Internal capacitance C i - 1.1 nF
- Internal inductance L i - negligible
- Max. current I o (Ex ia) - 150.00 mA
- Max. current I o (Ex ib) - 60.0 mA
- Max. permissible external capacitance C o for IIB - 1.470 μF
- Max. permissible external capacitance C o for IIC - 0.235 μF
- Max. permissible external inductance L o for IIB - 6.000 mH
- Max. permissible external inductance L o for IIC - 1.500 mH
- Max. Power P o - 732.000 mW
- Max. Voltage U o - 19.60 V
- Safety-related maximum voltage - 253 V

160411
Comprehensive portfolio to cater for all characteristics
two-channel variants reduce the amount of space required
can be used up to SIL 3 (IEC/EN 61508)
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
- Ambient temperature max. - +70 °C
- Ambient temperature max. note - Single device
- Ambient temperature max. note 2 - Group assembly
- Ambient temperature max.2 - +60 °C
- Ambient temperature min. - -20 °C
- Ambient temperature min. 2 - -20 °C
- Ambient temperature min. note - Single device
- Ambient temperature min. note 2 - Group assembly
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
- Relative humidity max. - 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power voltage range - 18 ... 31,2 V
- Nominal current - 80.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 1.90 W
- Power dissipation max. - 1.40 W
- Undervoltage monitoring - Yes
- Voltage range residual ripple - ≤ 3,6 VSS
Electrical Data
- Number of channels - 1
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - DMT 03 ATEX E 043 X
- ATEX gas certificate - DMT 03 ATEX E 043 X
- Certificate EAC - TS RU S-DE.GB04.B.00353
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM), USA (UL)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA nC [ia Ga] IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA nC [ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx BVS 10.0050 X
- IECEX gas certificate - IECEx BVS 10.0050 X
- Installation in Division NEC 500 - (Class I, II, III) 2
- Ship approval - CCS, DNVGL
Galvanic isolation
- Galvanic isolation Ex i output to auxiliary power - 1,5 kV AC
- Galvanic isolation Ex i output to fault message contact - 1,5 kV AC
- Galvanic isolation Ex i output to input - 1,5 kV AC
- Galvanic isolation fault message contact to auxiliary power - 350 V AC
- Galvanic isolation fault message contact to input - 350 V AC
- Galvanic isolation input to auxiliary power - 350 V AC
- Galvanic isolation input to input - 350 V AC
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 50178
General
- Functional Description - 9175 series binary outputs issue binary signals via one or two channels for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices feature three-way galvanic separation. A wire-breakage and short-circuit monitoring system, which can be disconnected, directly monitors the state of the field circuit.
- Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
- Product Description - Binary output Ex i field circuit
- Product Type - 9175/10-14-11k
- Title Product Variant Technical Data - 9175/10-14-11k digital output
- WebCode - 9175A
Input
- Control current - < 5 mA
- Input - In accordance with EN 61131-2
- Input voltage for OFF - 0 - 5 V
- Input voltage for ON - 15.0 - 31.2 V
Mechanical Data
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 17.60 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.180 kg
Mounting / Installation
- Conduct cross-section flexible max. - 2.5 mm²
- Conduct cross-section flexible max. - 0.2 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Spring clamp terminal
- Mounting position - vertical horizontal
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Error detection wire breakage - > 10 kΩ
- Indication of line fault - "LF" LED, red
- Internal Resistance R i - 130.00 Ω
- LFD relay - Yes
- Max. output current I a max - 45.00 mA
- Message of line fault and Auxilliary power failure - - Contact (30 V / 100 mA) closed to ground in case of fault - pac-Bus, floating contact (30 V / 100 mA)
- Note - You can find a list of connectible Ex i solenoid valves on our homepage www.r-stahl.com (WebCode 9175A)
- Output internal resistiance R i - 130.00 Ω
- Output open circuit voltage U a - 17,50 V
- Output residual ripple - < 50 mV
- Output switching frequency - <= 200 Hz
- Short circuit error detection - 40 ... 80 Ω ± 6 Ω /10 K
- Switch user adjustment line fault - activated / deactivated
- Switching capacity fault message contact - 30 V / 100 mA
- Switching delay ON/OFF - ≤ 1 ms
- Switching state indication - Yellow LED "OUT"
- test current - 2.1 mA (at 100-ohm load)
- test current 2 - 0.76 mA (at 10-kΩ load)
Safety Data
- Internal capacitance C i - 1.1 nF
- Internal inductance L i - negligible
- Max. current I o (Ex ia) - 150.00 mA
- Max. current I o (Ex ib) - 60.0 mA
- Max. permissible external capacitance C o for IIB - 1.470 μF
- Max. permissible external capacitance C o for IIC - 0.235 μF
- Max. permissible external inductance L o for IIB - 6.000 mH
- Max. permissible external inductance L o for IIC - 1.500 mH
- Max. Power P o - 732.000 mW
- Max. Voltage U o - 19.60 V
- Safety-related maximum voltage - 253 V

160413
Comprehensive portfolio to cater for all characteristics
two-channel variants reduce the amount of space required
can be used up to SIL 3 (IEC/EN 61508)
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
- Ambient temperature max. - +70 °C
- Ambient temperature max. note - Single device
- Ambient temperature max. note 2 - Group assembly
- Ambient temperature max.2 - +60 °C
- Ambient temperature min. - -20 °C
- Ambient temperature min. 2 - -20 °C
- Ambient temperature min. note - Single device
- Ambient temperature min. note 2 - Group assembly
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
- Relative humidity max. - 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power voltage range - 18 ... 31,2 V
- Nominal current - 140.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 3.40 W
- Power dissipation max. - 2.40 W
- Undervoltage monitoring - Yes
- Voltage range residual ripple - ≤ 3,6 VSS
Electrical Data
- Number of channels - 2
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - DMT 03 ATEX E 043 X
- ATEX gas certificate - DMT 03 ATEX E 043 X
- Certificate EAC - TS RU S-DE.GB04.B.00353
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM), USA (UL)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA nC [ia Ga] IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA nC [ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx BVS 10.0050 X
- IECEX gas certificate - IECEx BVS 10.0050 X
- Installation in Division NEC 500 - (Class I, II, III) 2
- Ship approval - CCS, DNVGL
Galvanic isolation
- Galvanic isolation Ex i output to auxiliary power - 1,5 kV AC
- Galvanic isolation Ex i output to fault message contact - 1,5 kV AC
- Galvanic isolation Ex i output to input - 1,5 kV AC
- Galvanic isolation Ex i to Ex i - N/A
- Galvanic isolation fault message contact to auxiliary power - 350 V AC
- Galvanic isolation fault message contact to input - 350 V AC
- Galvanic isolation input to auxiliary power - 350 V AC
- Galvanic isolation input to input - 350 V AC
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 50178
General
- Functional Description - 9175 series binary outputs issue binary signals via one or two channels for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices feature three-way galvanic separation. A wire-breakage and short-circuit monitoring system, which can be disconnected, directly monitors the state of the field circuit.
- Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
- Product Description - Binary output Ex i field circuit
- Product Type - 9175/20-14-11s
- Title Product Variant Technical Data - 9175/20-14-11s digital output
- WebCode - 9175A
Input
- Control current - < 5 mA
- Input - In accordance with EN 61131-2
- Input voltage for OFF - 0 - 5 V
- Input voltage for ON - 15.0 - 31.2 V
Mechanical Data
- Connection cross-section - 0.2-2.5 mm² flexible 0.25-2.5 mm² flexible core end sleeve 0.2-2.5 mm² rigid
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 17.60 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.190 kg
Mounting / Installation
- Conduct cross-section flexible max. - 2.5 mm²
- Conduct cross-section flexible max. - 0.2 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Screw terminal
- Mounting position - vertical horizontal
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Error detection wire breakage - > 10 kΩ / > 5 kΩ
- Indication of line fault - "LF" LED, red
- Internal Resistance R i - 130 Ω / 65 Ω*
- Internal resistance R i note - 130 Ω / 65 Ω
- LFD relay - Yes
- Max. output current I a max - 45 mA / 90 mA*
- Max. output current I a note - 45 mA / 90 mA
- Message of line fault and Auxilliary power failure - - Contact (30 V / 100 mA) closed to ground in case of fault - pac-Bus, floating contact (30 V / 100 mA)
- Output open circuit voltage U a - 17,50 V
- Output residual ripple - < 50 mV
- Output switching frequency - <= 200 Hz
- Parallel error detection short ciruit - 20 ... 40 Ω ± 6 Ω /10 K
- Short circuit error detection - 40 ... 80 Ω ± 6 Ω /10 K
- Switch user adjustment line fault - activated / deactivated
- Switching capacity fault message contact - 30 V / 100 mA
- Switching delay ON/OFF - ≤ 1 ms
- Switching state indication - Yellow LED "OUT"
- test current - 2.1 mA (at 100-ohm load)
- test current 2 - 0.76 mA (at 10-kΩ load)
Safety Data
- Internal capacitance C i - 1.1 nF
- Internal inductance L i - negligible
- Max. current I o (Ex ia) - 150.00 mA
- Max. current I o (Ex ib) - 60.0 mA
- Max. permissible external capacitance C o for IIB - 1.470 μF
- Max. permissible external capacitance C o for IIC - 0.235 μF
- Max. permissible external inductance L o for IIB - 6.000 mH
- Max. permissible external inductance L o for IIC - 1.500 mH
- Max. Power P o - 732.000 mW
- Max. Voltage U o - 19.60 V
- Safety-related maximum voltage - 253 V

160414
Comprehensive portfolio to cater for all characteristics
two-channel variants reduce the amount of space required
can be used up to SIL 3 (IEC/EN 61508)
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
- Ambient temperature max. - +70 °C
- Ambient temperature max. note - Single device
- Ambient temperature max. note 2 - Group assembly
- Ambient temperature max.2 - +60 °C
- Ambient temperature min. - -20 °C
- Ambient temperature min. 2 - -20 °C
- Ambient temperature min. note - Single device
- Ambient temperature min. note 2 - Group assembly
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
- Relative humidity max. - 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power voltage range - 18 ... 31,2 V
- Nominal current - 140.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 3.40 W
- Power dissipation max. - 2.40 W
- Undervoltage monitoring - Yes
- Voltage range residual ripple - ≤ 3,6 VSS
Electrical Data
- Number of channels - 2
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - DMT 03 ATEX E 043 X
- ATEX gas certificate - DMT 03 ATEX E 043 X
- Certificate EAC - TS RU S-DE.GB04.B.00353
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM), USA (UL)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA nC [ia Ga] IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA nC [ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx BVS 10.0050 X
- IECEX gas certificate - IECEx BVS 10.0050 X
- Installation in Division NEC 500 - (Class I, II, III) 2
- Ship approval - CCS, DNVGL
Galvanic isolation
- Galvanic isolation Ex i output to auxiliary power - 1,5 kV AC
- Galvanic isolation Ex i output to fault message contact - 1,5 kV AC
- Galvanic isolation Ex i output to input - 1,5 kV AC
- Galvanic isolation Ex i to Ex i - N/A
- Galvanic isolation fault message contact to auxiliary power - 350 V AC
- Galvanic isolation fault message contact to input - 350 V AC
- Galvanic isolation input to auxiliary power - 350 V AC
- Galvanic isolation input to input - 350 V AC
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 50178
General
- Functional Description - 9175 series binary outputs issue binary signals via one or two channels for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices feature three-way galvanic separation. A wire-breakage and short-circuit monitoring system, which can be disconnected, directly monitors the state of the field circuit.
- Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
- Product Description - Binary output Ex i field circuit
- Product Type - 9175/20-14-11k
- Title Product Variant Technical Data - 9175/20-14-11k digital output
- WebCode - 9175A
Input
- Control current - < 5 mA
- Input - In accordance with EN 61131-2
- Input voltage for OFF - 0 - 5 V
- Input voltage for ON - 15.0 - 31.2 V
Mechanical Data
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 17.60 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.111 kg
Mounting / Installation
- Conduct cross-section flexible max. - 0.2 mm²
- Conduct cross-section flexible max. - 2.5 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Spring clamp terminal
- Mounting position - vertical horizontal
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Error detection wire breakage - > 10 kΩ / > 5 kΩ
- Indication of line fault - "LF" LED, red
- Internal Resistance R i - 130 Ω / 65 Ω*
- Internal resistance R i note - 130 Ω / 65 Ω
- LFD relay - Yes
- Max. output current I a max - 45 mA / 90 mA*
- Max. output current I a note - 45 mA / 90 mA
- Message of line fault and Auxilliary power failure - - Contact (30 V / 100 mA) closed to ground in case of fault - pac-Bus, floating contact (30 V / 100 mA)
- Output open circuit voltage U a - 17,50 V
- Output residual ripple - < 50 mV
- Output switching frequency - <= 200 Hz
- Parallel error detection short ciruit - 20 ... 40 Ω ± 6 Ω /10 K
- Short circuit error detection - 40 ... 80 Ω ± 6 Ω /10 K
- Switch user adjustment line fault - activated / deactivated
- Switching capacity fault message contact - 30 V / 100 mA
- Switching delay ON/OFF - ≤ 1 ms
- Switching state indication - Yellow LED "OUT"
- test current - 2.1 mA (at 100-ohm load)
- test current 2 - 0.76 mA (at 10-kΩ load)
Safety Data
- Internal capacitance C i - 1.1 nF
- Internal inductance L i - negligible
- Max. current I o (Ex ia) - 150.00 mA
- Max. current I o (Ex ib) - 60.0 mA
- Max. permissible external capacitance C o for IIB - 1.470 μF
- Max. permissible external capacitance C o for IIC - 0.235 μF
- Max. permissible external inductance L o for IIB - 6.000 mH
- Max. permissible external inductance L o for IIC - 1.500 mH
- Max. Power P o - 732.000 mW
- Max. Voltage U o - 19.60 V
- Safety-related maximum voltage - 253 V

160416
Comprehensive portfolio to cater for all characteristics
two-channel variants reduce the amount of space required
can be used up to SIL 3 (IEC/EN 61508)
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
- Ambient temperature max. - +70 °C
- Ambient temperature max. note - Single device
- Ambient temperature max. note 2 - Group assembly
- Ambient temperature max.2 - +60 °C
- Ambient temperature min. - -20 °C
- Ambient temperature min. 2 - -20 °C
- Ambient temperature min. note - Single device
- Ambient temperature min. note 2 - Group assembly
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
- Relative humidity max. - 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power voltage range - 18 ... 31,2 V
- Nominal current - 80.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 1.90 W
- Power dissipation max. - 1.40 W
- Undervoltage monitoring - Yes
- Voltage range residual ripple - ≤ 3,6 VSS
Electrical Data
- Number of channels - 1
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - DMT 03 ATEX E 043 X
- ATEX gas certificate - DMT 03 ATEX E 043 X
- Certificate EAC - TS RU S-DE.GB04.B.00353
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM), USA (UL)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA nC [ia Ga] IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA nC [ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx BVS 10.0050 X
- IECEX gas certificate - IECEx BVS 10.0050 X
- Installation in Division NEC 500 - (Class I, II, III) 2
- Ship approval - CCS, DNVGL
Galvanic isolation
- Galvanic isolation Ex i output to auxiliary power - 1,5 kV AC
- Galvanic isolation Ex i output to fault message contact - 1,5 kV AC
- Galvanic isolation Ex i output to input - 1,5 kV AC
- Galvanic isolation fault message contact to auxiliary power - 350 V AC
- Galvanic isolation fault message contact to input - 350 V AC
- Galvanic isolation input to auxiliary power - 350 V AC
- Galvanic isolation input to input - 350 V AC
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 50178
General
- Functional Description - 9175 series binary outputs issue binary signals via one or two channels for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices feature three-way galvanic separation. A wire-breakage and short-circuit monitoring system, which can be disconnected, directly monitors the state of the field circuit.
- Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
- Product Description - Binary output Ex i field circuit
- Product Type - 9175/10-16-11s
- Title Product Variant Technical Data - Type 9175/.0-16-11.
- WebCode - 9175A
Input
- Control current - < 5 mA
- Input - In accordance with EN 61131-2
- Input voltage for OFF - 0 - 5 V
- Input voltage for ON - 15.0 - 31.2 V
Mechanical Data
- Connection cross-section - 0.2-2.5 mm² flexible 0.25-2.5 mm² flexible core end sleeve 0.2-2.5 mm² rigid
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 17.60 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.175 kg
Mounting / Installation
- Conduct cross-section flexible max. - 0.2 mm²
- Conduct cross-section flexible max. - 2.5 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Screw terminal
- Mounting position - vertical horizontal
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Error detection wire breakage - > 15 kΩ
- Indication of line fault - "LF" LED, red
- Internal Resistance R i - 250.00 Ω
- LFD relay - Yes
- Max. output current I a max - 35.00 mA
- Message of line fault and Auxilliary power failure - - Contact (30 V / 100 mA) closed to ground in case of fault - pac-Bus, floating contact (30 V / 100 mA)
- Note - You can find a list of connectible Ex i solenoid valves on our homepage www.r-stahl.com (WebCode 9175A)
- Output internal resistiance R i - 250.00 Ω
- Output open circuit voltage U a - 25,00 V
- Output residual ripple - < 50 mV
- Output switching frequency - <= 200 Hz
- Short circuit error detection - 50 ... 90 Ω ± 8 Ω /10 K
- Switch user adjustment line fault - activated / deactivated
- Switching capacity fault message contact - 30 V / 100 mA
- Switching delay ON/OFF - ≤ 1 ms
- Switching state indication - Yellow LED "OUT"
- test current - 2.3 mA (at 100-ohm load)
- test current 2 - 0.72 mA (at 15-kΩ load)
Safety Data
- Internal capacitance C i - 1.1 nF
- Internal inductance L i - negligible
- Max. current I o (Ex ia) - 110.00 mA
- Max. current I o (Ex ib) - 50.0 mA
- Max. permissible external capacitance C o for IIB - 0.667 μF
- Max. permissible external capacitance C o for IIC - 0.085 μF
- Max. permissible external inductance L o for IIB - 9.000 mH
- Max. permissible external inductance L o for IIC - 1.200 mH
- Max. Power P o - 760.000 mW
- Max. Voltage U o - 27.60 V
- Safety-related maximum voltage - 253 V

160417
Comprehensive portfolio to cater for all characteristics
two-channel variants reduce the amount of space required
can be used up to SIL 3 (IEC/EN 61508)
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
- Ambient temperature max. - +70 °C
- Ambient temperature max. note - Single device
- Ambient temperature max. note 2 - Group assembly
- Ambient temperature max.2 - +60 °C
- Ambient temperature min. - -20 °C
- Ambient temperature min. 2 - -20 °C
- Ambient temperature min. note - Single device
- Ambient temperature min. note 2 - Group assembly
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
- Relative humidity max. - 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power voltage range - 18 ... 31,2 V
- Nominal current - 80.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 1.90 W
- Power dissipation max. - 1.40 W
- Undervoltage monitoring - Yes
- Voltage range residual ripple - ≤ 3,6 VSS
Electrical Data
- Number of channels - 1
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - DMT 03 ATEX E 043 X
- ATEX gas certificate - DMT 03 ATEX E 043 X
- Certificate EAC - TS RU S-DE.GB04.B.00353
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM), USA (UL)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA nC [ia Ga] IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA nC [ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx BVS 10.0050 X
- IECEX gas certificate - IECEx BVS 10.0050 X
- Installation in Division NEC 500 - (Class I, II, III) 2
- Ship approval - CCS, DNVGL
Galvanic isolation
- Galvanic isolation Ex i output to auxiliary power - 1,5 kV AC
- Galvanic isolation Ex i output to fault message contact - 1,5 kV AC
- Galvanic isolation Ex i output to input - 1,5 kV AC
- Galvanic isolation fault message contact to auxiliary power - 350 V AC
- Galvanic isolation fault message contact to input - 350 V AC
- Galvanic isolation input to auxiliary power - 350 V AC
- Galvanic isolation input to input - 350 V AC
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 50178
General
- Functional Description - 9175 series binary outputs issue binary signals via one or two channels for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices feature three-way galvanic separation. A wire-breakage and short-circuit monitoring system, which can be disconnected, directly monitors the state of the field circuit.
- Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
- Product Description - Binary output Ex i field circuit
- Product Type - 9175/10-16-11k
- Title Product Variant Technical Data - 9175/10-16-11k digital output
- WebCode - 9175A
Input
- Control current - < 5 mA
- Input - In accordance with EN 61131-2
- Input voltage for OFF - 0 - 5 V
- Input voltage for ON - 15.0 - 31.2 V
Mechanical Data
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 17.60 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.180 kg
Mounting / Installation
- Conduct cross-section flexible max. - 0.2 mm²
- Conduct cross-section flexible max. - 2.5 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Spring clamp terminal
- Mounting position - vertical horizontal
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Error detection wire breakage - > 15 kΩ
- Indication of line fault - "LF" LED, red
- Internal Resistance R i - 250.00 Ω
- LFD relay - Yes
- Max. output current I a max - 35.00 mA
- Message of line fault and Auxilliary power failure - - Contact (30 V / 100 mA) closed to ground in case of fault - pac-Bus, floating contact (30 V / 100 mA)
- Note - You can find a list of connectible Ex i solenoid valves on our homepage www.r-stahl.com (WebCode 9175A)
- Output internal resistiance R i - 250.00 Ω
- Output open circuit voltage U a - 25,00 V
- Output residual ripple - < 50 mV
- Output switching frequency - <= 200 Hz
- Short circuit error detection - 50 ... 90 Ω ± 8 Ω /10 K
- Switch user adjustment line fault - activated / deactivated
- Switching capacity fault message contact - 30 V / 100 mA
- Switching delay ON/OFF - ≤ 1 ms
- Switching state indication - Yellow LED "OUT"
- test current - 2.3 mA (at 100-ohm load)
- test current 2 - 0.72 mA (at 15-kΩ load)
Safety Data
- Internal capacitance C i - 1.1 nF
- Internal inductance L i - negligible
- Max. current I o (Ex ia) - 110.00 mA
- Max. current I o (Ex ib) - 50.0 mA
- Max. permissible external capacitance C o for IIB - 0.667 μF
- Max. permissible external capacitance C o for IIC - 0.085 μF
- Max. permissible external inductance L o for IIB - 9.000 mH
- Max. permissible external inductance L o for IIC - 1.200 mH
- Max. Power P o - 760.000 mW
- Max. Voltage U o - 27.60 V
- Safety-related maximum voltage - 253 V

160419
Comprehensive portfolio to cater for all characteristics
two-channel variants reduce the amount of space required
can be used up to SIL 3 (IEC/EN 61508)
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
- Ambient temperature max. - +70 °C
- Ambient temperature max. note - Single device
- Ambient temperature max. note 2 - Group assembly
- Ambient temperature max.2 - +60 °C
- Ambient temperature min. - -20 °C
- Ambient temperature min. 2 - -20 °C
- Ambient temperature min. note - Single device
- Ambient temperature min. note 2 - Group assembly
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
- Relative humidity max. - 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power voltage range - 18 ... 31,2 V
- Nominal current - 140.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 3.40 W
- Power dissipation max. - 2.40 W
- Undervoltage monitoring - Yes
- Voltage range residual ripple - ≤ 3,6 VSS
Electrical Data
- Number of channels - 2
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - DMT 03 ATEX E 043 X
- ATEX gas certificate - DMT 03 ATEX E 043 X
- Certificate EAC - TS RU S-DE.GB04.B.00353
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM), USA (UL)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA nC [ia Ga] IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA nC [ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx BVS 10.0050 X
- IECEX gas certificate - IECEx BVS 10.0050 X
- Installation in Division NEC 500 - (Class I, II, III) 2
- Ship approval - CCS, DNVGL
Galvanic isolation
- Galvanic isolation Ex i output to auxiliary power - 1,5 kV AC
- Galvanic isolation Ex i output to fault message contact - 1,5 kV AC
- Galvanic isolation Ex i output to input - 1,5 kV AC
- Galvanic isolation Ex i to Ex i - N/A
- Galvanic isolation fault message contact to auxiliary power - 350 V AC
- Galvanic isolation fault message contact to input - 350 V AC
- Galvanic isolation input to auxiliary power - 350 V AC
- Galvanic isolation input to input - 350 V AC
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 50178
General
- Functional Description - 9175 series binary outputs issue binary signals via one or two channels for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices feature three-way galvanic separation. A wire-breakage and short-circuit monitoring system, which can be disconnected, directly monitors the state of the field circuit.
- Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
- Product Description - Binary output Ex i field circuit
- Product Type - 9175/20-16-11s
- Title Product Variant Technical Data - 9175/20-16-11s digital output
- WebCode - 9175A
Input
- Control current - < 5 mA
- Input - In accordance with EN 61131-2
- Input voltage for OFF - 0 - 5 V
- Input voltage for ON - 15.0 - 31.2 V
Mechanical Data
- Connection cross-section - 0.2-2.5 mm² flexible 0.25-2.5 mm² flexible core end sleeve 0.2-2.5 mm² rigid
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 17.60 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.190 kg
Mounting / Installation
- Conduct cross-section flexible max. - 0.2 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Screw terminal
- Mounting position - vertical horizontal
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Error detection wire breakage - > 15 kΩ / > 7,5 kΩ
- Indication of line fault - "LF" LED, red
- Internal Resistance R i - 250 Ω / 125 Ω*
- Internal resistance R i note - 250 Ω / 125 Ω
- LFD relay - Yes
- Max. output current I a max - 35 mA / 70 mA*
- Max. output current I a note - 35 mA / 70 mA
- Message of line fault and Auxilliary power failure - - Contact (30 V / 100 mA) closed to ground in case of fault - pac-Bus, floating contact (30 V / 100 mA)
- Note - You can find a list of connectible Ex i solenoid valves on our homepage www.r-stahl.com (WebCode 9175A)
- Output open circuit voltage U a - 25,00 V
- Output residual ripple - < 50 mV
- Output switching frequency - <= 200 Hz
- Parallel error detection short ciruit - 25 ... 45 Ω ± 8 Ω /10 K
- Short circuit error detection - 50 ... 90 Ω ± 8 Ω /10 K
- Switch user adjustment line fault - activated / deactivated
- Switching capacity fault message contact - 30 V / 100 mA
- Switching delay ON/OFF - ≤ 1 ms
- Switching state indication - Yellow LED "OUT"
- test current - 2.3 mA (at 100-ohm load)
- test current 2 - 0.72 mA (at 15-kΩ load)
Safety Data
- Internal capacitance C i - 1.1 nF
- Internal inductance L i - negligible
- Max. current I o (Ex ia) - 110.00 mA
- Max. current I o (Ex ib) - 50.0 mA
- Max. permissible external capacitance C o for IIB - 0.667 μF
- Max. permissible external capacitance C o for IIC - 0.085 μF
- Max. permissible external inductance L o for IIB - 9.000 mH
- Max. permissible external inductance L o for IIC - 1.200 mH
- Max. Power P o - 760.000 mW
- Max. Voltage U o - 27.60 V
- Safety-related maximum voltage - 253 V

160420
Comprehensive portfolio to cater for all characteristics
two-channel variants reduce the amount of space required
can be used up to SIL 3 (IEC/EN 61508)
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
- Ambient temperature max. - +70 °C
- Ambient temperature max. note - Single device
- Ambient temperature max. note 2 - Group assembly
- Ambient temperature max.2 - +60 °C
- Ambient temperature min. - -20 °C
- Ambient temperature min. 2 - -20 °C
- Ambient temperature min. note - Single device
- Ambient temperature min. note 2 - Group assembly
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
- Relative humidity max. - 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power voltage range - 18 ... 31,2 V
- Nominal current - 140.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 3.40 W
- Power dissipation max. - 2.40 W
- Undervoltage monitoring - Yes
- Voltage range residual ripple - ≤ 3,6 VSS
Electrical Data
- Number of channels - 2
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - DMT 03 ATEX E 043 X
- ATEX gas certificate - DMT 03 ATEX E 043 X
- Certificate EAC - TS RU S-DE.GB04.B.00353
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM), USA (UL)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA nC [ia Ga] IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA nC [ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx BVS 10.0050 X
- IECEX gas certificate - IECEx BVS 10.0050 X
- Installation in Division NEC 500 - (Class I, II, III) 2
- Ship approval - CCS, DNVGL
Galvanic isolation
- Galvanic isolation Ex i output to auxiliary power - 1,5 kV AC
- Galvanic isolation Ex i output to fault message contact - 1,5 kV AC
- Galvanic isolation Ex i output to input - 1,5 kV AC
- Galvanic isolation Ex i to Ex i - N/A
- Galvanic isolation fault message contact to auxiliary power - 350 V AC
- Galvanic isolation fault message contact to input - 350 V AC
- Galvanic isolation input to auxiliary power - 350 V AC
- Galvanic isolation input to input - 350 V AC
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 50178
General
- Functional Description - 9175 series binary outputs issue binary signals via one or two channels for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices feature three-way galvanic separation. A wire-breakage and short-circuit monitoring system, which can be disconnected, directly monitors the state of the field circuit.
- Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
- Product Description - Binary output Ex i field circuit
- Product Type - 9175/20-16-11k
- Title Product Variant Technical Data - 9175/20-16-11k digital output
- WebCode - 9175A
Input
- Control current - < 5 mA
- Input - In accordance with EN 61131-2
- Input voltage for OFF - 0 - 5 V
- Input voltage for ON - 15.0 - 31.2 V
Mechanical Data
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 17.60 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.111 kg
Mounting / Installation
- Conduct cross-section flexible max. - 0.2 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Spring clamp terminal
- Mounting position - vertical horizontal
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Error detection wire breakage - > 15 kΩ / > 7,5 kΩ
- Indication of line fault - "LF" LED, red
- Internal Resistance R i - 250 Ω / 125 Ω*
- Internal resistance R i note - 250 Ω / 125 Ω
- LFD relay - Yes
- Max. output current I a max - 35 mA / 70 mA*
- Max. output current I a note - 35 mA / 70 mA
- Message of line fault and Auxilliary power failure - - Contact (30 V / 100 mA) closed to ground in case of fault - pac-Bus, floating contact (30 V / 100 mA)
- Output open circuit voltage U a - 25,00 V
- Output residual ripple - < 50 mV
- Output switching frequency - <= 200 Hz
- Parallel error detection short ciruit - 25 ... 45 Ω ± 8 Ω /10 K
- Short circuit error detection - 50 ... 90 Ω ± 8 Ω /10 K
- Switch user adjustment line fault - activated / deactivated
- Switching capacity fault message contact - 30 V / 100 mA
- Switching delay ON/OFF - ≤ 1 ms
- Switching state indication - Yellow LED "OUT"
- test current - 2.3 mA (at 100-ohm load)
- test current 2 - 0.72 mA (at 15-kΩ load)
Safety Data
- Internal capacitance C i - 1.1 nF
- Internal inductance L i - negligible
- Max. current I o (Ex ia) - 110.00 mA
- Max. current I o (Ex ib) - 50.0 mA
- Max. permissible external capacitance C o for IIB - 0.667 μF
- Max. permissible external capacitance C o for IIC - 0.085 μF
- Max. permissible external inductance L o for IIB - 9.000 mH
- Max. permissible external inductance L o for IIC - 1.200 mH
- Max. Power P o - 760.000 mW
- Max. Voltage U o - 27.60 V
- Safety-related maximum voltage - 253 V