340 BN/MB BTU Energy Transmitter

Brand: Badger Meter

The 340 BN/MB BTU Energy Transmitter is an economical, compact device for sub-metering applications using the BACnet or Modbus® communications protocol.

An economical, compact device for sub-metering applications.

Calculates thermal energy using the signal from a flow sensor installed in a hydronic heating or chilled water system, and the signals from two 10 kΩ temperature thermistors, 100 Ω RTDs or 1000 Ω RTDs installed in the system’s inlet and outlet points.
Features
  • On-board microcontroller and circuitry make precise measurements and produce accurate, drift-free outputs
  • Calibration information for the flow sensor type and pipe size may be preselected or entered by the user in the field
  • Calculates thermal energy using the signal from a flow sensor installed in a hydronic heating or chilled water system
  • Compact cast epoxy body

Specifications

Brand

Power Supply Options

  • Power Supply: 12…24 VAC | 12…35 VDC
  • Current Draw: 115 mA max. at 12 VDC

Pulse Type Sensors - Signal Amplitude

  • 2.5 VDC Threshold

Pulse Type Sensors - Signal Limits

  • Vin < 12 V (DC or AC peak)

Pulse Type Sensors - Frequency Range

  • 4…1000 Hz

Pulse Type Sensors - Pull-up

  • 15 VDC @ 2 kΩ Source Impedance

Sine Wave Sensors - Signal Amplitude

  • 30 mV p-p Threshold

Sine Wave Sensors - Signal Limits

  • Vin < 12 V (DC or AC peak)

Sine Wave Sensors - Frequency

  • 4…1000 Hz

Power Out Terminal

  • 15 VDC ± 1 VDC @ 500 Ω Source Impedance

Temperature Sensor (2 of same type Required) Input

  • 10 kΩ Thermistor, 2 Wire, Type II, 10 kΩ @ 25°C (77°F)
  • 100 Ω Platinum RTD, DIN Calibration Curve, conforms to IEC-751 Standard
  • 1000 Ω Platinum RTD, DIN Calibration Curve, conforms to IEC-751 Standard
  • Calibration range of Measurement 0…150°C (32…302°F)

Communication Port

  • RS-485 with Termination, Pull-up and Pull-down Jumpers

Pulse Output

  • Isolated Solid-State Switch in any Standard or Custom Total Units
  • Adjustable 50 ms to 1.0 second pulse output width in 50 ms increments
  • Maximum Sinking Current: 100 mA @ 36 VDC

Temperature

  • Operating: 32...158 °F (0...70 °C)
  • Storage: –40…185 °F (-40...85 °C)

Weight

  • 4.8 oz with Connector Headers Installed

Sensor Calibration

  • Badger Meter: Use K and offset values provided in sensor manual
  • Other Sensors: Check with respected manufacturer of flow sensor and with factory

Unit of Measure - Flow Measurement Rate

  • Rate: gpm, gph, l/sec, l/min, l/hr, ft³/sec, ft³/min, ft³/hr, m³/sec, m³/min, m³/hr
  • Total: Gallons, Gallons X 100, Gallons X 1000, Liters, Cubic Feet, Cubic Meters

Units of Measure - Energy Measurement

  • Rate: kBtu/min, kBtu/hr, kW, MW, hp, tons
  • Total: Btu, kBtu, MBtu, kWh, MWh, kJ, MJ

Temperature Measurement

  • Fahrenheit, Centigrade

Programming

  • Requires PC or laptop running Windows 2000, XP, Vista or Windows 7
  • Data Industrial 340BN/MB Programming Kit A-301-20 containing software and Data Industrial Series programming cable is required for programming and setup