Yodify Product Library
Instantly add the Nelson™ Heat Trace Tee Connection Kits and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
Nelson™ Heat Trace Tee Connection Kits
Brand: NelsonNelson™ Heat Trace tee splice connection kits are used to connect up to three heater cables.
It may be used to connect multiple heater segments, connect different wattage cables together or to provide access to service removable equipment.
AXTC125 is designed per NEC/CEC requirements including standard terminal blocks sized for maximum 8 AWG wiring.
EXTC125 is designed per IEC requirements including standard terminal blocks sized for maximum 6mm² wiring.
HTC125 is a tee kit that is offered without an enclosure for the customers who provide the connection enclosure separately.
Kits are used to connect and terminate Nelson™ Heat Trace LT-J, LT-JT, HLT-J, XLT-J and CLT-JT Series self-regulating heater cables.
Features- Ordering information: One kit should be ordered for each type of connection needed. A pipe clamp of the appropriate size for the pipe must be selected (-3 for PC03, -12 for PC12, -20 for PC20) for each connection kit. A small pipe adapter kit must be ordered for each kit for installation on 25mm (1 inch) or smaller pipe.
- The enclosure must be rated to meet the specifics of the installed environment.
- Global-reach industrial-grade universal connection kits for hazardous locations.
- Certified for NEC/CEC (AX Series) and IEC (EX Series) installations.
- Incorporate rugged, non-metallic construction rated for IP66 / NEMA 4X.
- Designed with corrosion resistant, antistatic enclosures and components.
- Easy entry and connectivity with terminal blocks and DIN rails.
- Fits all wattages of Nelson™ LT-J, LT-JT, HLT-J, XLT-J and CLT-JT Series self-regulating heater cables.
Specifications
Brand
Accessories
- Pipe Clamp to Secure Standoff to Pipe & a Small Pipe Adapter are available. See Catalog Pages for Details
Amperage, Maximum
- 14 A CLT Series, 18 A LT, HLT Series, 25 A XLT Series
Approvals & Certifications
- UL Listed, CSA & ATEX Certified, FM Approved: Hazardous (Classified) Locations
- Ex II 2 G, Ex E IIC T5 Gb, Ex II 2 D, Ex Tb IIIC T95° C
Conductor Size
- 1 mm² (18 AWG) to 6 mm² (8 AWG)
CSA
- Class I, Div. 2, Groups B, C, D, Class II, Groups E, F, G (Canada Only), Class III (Canada Only), Enclosure Typical 4X, Class I, Zone 1, Ex E II
Enclosure Material
- Glass Reinforced, Carbon-loaded, Polyester, UV Resistant, Polymer
FM
- Class I, Div. 2, Groups B, C, D, Class II, Groups E, F, G, Class III, Enclosure Typical 4X, IP66, Class I Zone 1, AEx E IIC
Ingress Protection
- NEMA 4X, IP66
Minimum Installation Temperature
- -40° C (-40° F)
Temperature Use Range
- -50° to +55° C (-58° to +131° F) Ambient
UL
- Class I, Div. 2, Groups A, B, C, D, Class II, Div. 2, Groups F, G, Class III, Div. 1, & 2
Voltage Range
- 300 Vac, Max.