Yodify Product Library
Instantly add the GTx108-F(/SI & /DI) SWSI & DWDI Airflow Measurement with Temperature and Alarm Capacity and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
GTx108-F(/SI & /DI) SWSI & DWDI Airflow Measurement with Temperature and Alarm Capacity
Brand: EBTRON, IncThe GTx108-F/SI and GTx108-F/DI are EBTRON’s solution for accurate and repeatable airflow measurement in SWSI and DWDI fans.
Airflow, temperature and/or airflow alarming are available on all models. Does not affect SWSI or DWDI fan performance.
Features- Thermal Dispersion Technology
- Designed for SWSI and DWDI Fans
- NIST-traceable Calibration
- %-of-reading Accuracy
- Airflow and Status Alarm
- Temperature Output Capability
- Combination Analog/Network Models
- Throat, Face, and Forward Mounting
- Remote Transmitter with LCD Display
- 3-year Warranty
1 - 1 of 1 Part Numbers
GTx108-F(/SI & /DI)
The GTx108-F/SI and GTx108-F/DI are EBTRON’s solution for accurate and repeatable airflow measurement in SWSI and DWDI fans. Airflow, temperature and/or airflow alarming are available on all models. Does not affect SWSI or DWDI fan performance.
1 - 1 of 1 Part Numbers
Specifications
Brand
Certifications & Approvals
- BTL
- cULus
Probe and Sensor Node Configurations
- SWSI and DWDI Fans: 2 Probes x 1 Sensor Node/per Probe in Each Fan Inlet
NIST
- NIST-traceable Calibration
Temperature Range
- Transmitter: -20° to 120° F (-28.9° to 48.9° C)
- Probe: -20° to 160° F (-28.9° to 71.1° C)
Humidity
- Probes: 0 to 100 %
- Transmitter: 5 to 95 %
Material of Construction
- Sensing Node Housing: Glass-filled Polypropylene
- Sensor Potting: Waterproof Marine Epoxy
- Mounting Rods: Zinc-Plated Steel
- Mounting Brackets: 304 Stainless Steel
- Probe to Transmitter Cables: FEP Jacket, Plenum Rated CMP/CL2P, UL/cUL Listed, -67° to 392° F (-55° to 200° C), UV Tolerant
Power Requirement
- Transmitter: 24 Vac (22.8-26.4 Under Load) @ 16 V-A
Alarm
- Airflow: Low and/or High User Defined Set Point Alarm
- System Status Alarm: Sensor Diagnostic System Trouble Indication
Measured Accuracy
- Temperature: ± 0.15° F (0.08° C) to NIST-traceable Temperature Standards
- Airflow: ± 2 % of Reading to NIST-traceable Airflow Standards
- Fan Airflow Tracking
- Air Change Verification & Monitoring
- Fan Performance Monitoring