55UV5 Series Scanner

Brand: Fireye, Inc

The Fireye® 55UV5 scanners use a UV-eye detector.

This detector is a sealed, gas filled, UV-sensitive tube containing two electrodes connected to a source of AC voltage.

55UV5 self-checking scanners are used to detect ultraviolet emissions from fossil fuel flames such as natural gas, coke oven gas, propane, methane, butane, kerosene, light petroleum distillates and diesel fuels and are suitable for use in Class I, Div. 2, Groups A, B, C, D and Class II, Div. 2 Groups F and G hazardous locations.

These 55UV5 models are used only with the Flame Monitor, D-Series, FlameWorx and MicroM control models to provide flame safeguard and monitoring systems for supervised manual, semi-automatic and fully automatic single burner boilers, process ovens and heaters.

1 - 8 of 8 Part Numbers
4-314-1
4-314-1
UV Tube
55UV5-1007
55UV5-1007
Fireye Scanner, 55UV5
  • UV Self-Check Scanner, NEMA 4X, IP66, Meets Class I, Div. 2, Groups A, B, C, D and Class II, Div. 2 Groups F and G
  • Scanner Head is 1” BSP with 3/4” BSP Purge Hole, 20 foot Cable and Liquid Tight Connector
55UV5-1009
55UV5-1009
Fireye Scanner, 55UV5
  • UV Self-Check Scanner, NEMA 4X, IP66, Meets Class I, Div. 2, Groups A, B, C D and Class II, Div. 2 Groups F and G
  • Scanner Head is 1” NPT with 3/4” NPT Purge Hole, 20 foot Cable and Liquid Tight Connector
60-2815-5
60-2815-5
Replacement, UV Self-Check Scanner Electronics Assembly, 55UV5-1009 Series
60-2815-6
60-2815-6
Replacement, UV Self-Check Scanner Electronics Assembly, 55UV5-1007 Series
61-7074-3
61-7074-3
Replacement, Front Mount, 1” NPT, 3/4” NPT Purge Hole, 20 foot Cable, Liquid Tight Fitting
61-7074-4
61-7074-4
Replacement, Front Mount, 1” BSP, 3/4” BSP Purge Hole, 20 foot Cable, Liquid Tight Fitting
61-7075-1
61-7075-1
Shutter Replacement Assembly
1 - 8 of 8 Part Numbers

Specifications

Brand

Approvals & Certifications

  • FM
  • UL (C,US)

Enclosure, Body Material

  • Cast Aluminum with Grey Epoxy Coat Finish

Environmental Protection

  • IP66
  • NEMA 4X

Frequency

  • 60 Hz

Power Requirement

  • 4 Vac

Temperature Range

  • -40° to 125° C (-40° to 257° F)