Brand: EurothermThe field configurable AP4382 isolator offers wide ranging input and output capability for scaling and transmitting Analog DC signals.
The AP4382 will accept input voltage spans from 10 mV up to 100 volts, as well as input current spans from 1 to 100 mA.
The input zero and span potentiometers enable 50% input zero and span adjustability. For example, the 0 to 10 V input range can be elevated to 5 to 10 V, or compressed to 0 to 5 V.
The AP4382 offers two (2) bipolar output ranges: -5 to 5 V and -10 to 10 V.
Features- Eliminates ground loops
- Field configurable input ranges: 10 mV to 100 V, 1 to 100 mA
- Two field configurable output ranges: -5 to 5 V and -10 to 10 V
- Plug-in installation
- Selectable 120 / 240 Vac input power (9 to 30 Vdc available)
- ASIC Technology for enhanced reliability
1 - 8 of 8 Part Numbers
AP4382-2000
- Coating - None
- Line Power - Standard 120/240VAC
- Factory Calibration - None
AP4382-2000C620
- Coating - None
- Line Power - Standard 120/240VAC
- Factory Calibration - Factory Calibration of Input Range, Set Points, and Output Relays
AP4382-2000P
- Coating - None
- Line Power - 9 to 30VDC Inverter Isolated
- Factory Calibration - None
AP4382-2000PC620
- Coating - None
- Line Power - 9 to 30VDC Inverter Isolated
- Factory Calibration - Factory Calibration of Input Range, Set Points, and Output Relays
AP4382-2000U
- Coating - Urethane Coating of Internal Circuitry for Protection From Corrosive Atmospheres
- Line Power - Standard 120/240VAC
- Factory Calibration - None
AP4382-2000UC620
- Coating - Urethane Coating of Internal Circuitry for Protection From Corrosive Atmospheres
- Line Power - Standard 120/240VAC
- Factory Calibration - Factory Calibration of Input Range, Set Points, and Output Relays
AP4382-2000UP
- Coating - Urethane Coating of Internal Circuitry for Protection From Corrosive Atmospheres
- Line Power - 9 to 30VDC Inverter Isolated
- Factory Calibration - None
AP4382-2000UPC620
- Coating - Urethane Coating of Internal Circuitry for Protection From Corrosive Atmospheres
- Line Power - 9 to 30VDC Inverter Isolated
- Factory Calibration - Factory Calibration of Input Range, Set Points, and Output Relays
1 - 8 of 8 Part Numbers
Specifications
Brand
Approvals & Certifications
- CSA C22.2 No. M1982 (File No. LR42272-54)
- IEC 801-2
- UL (C,US), 508 (File No. E150323)
Voltage Input
- Full Scale Range: 10 mV to 100 V
Voltage Output
- -10 to 10 V or -5 to 5 V
Impedance
- Input: > 100K ohms
- Output: < 10 ohms
Accuracy
- < 20 mV/2 mA: ± 0.35 % of Full Scale
Temperature Stability
- ± 0.025 % of Full Scale/°C
- ± 0.05 %/°C Max.
Temperature Range
- -15° C to 60° C
- 5° F to 140° F