Fluke 1625-2 GEO Earth Ground Tester

Brand: Fluke Corporation

The Fluke 1625-2 earth ground tester measures earth ground loop resistances using only clamps, only stakes, or one clamp and stakes. 

With the stakeless test method, the Fluke 1625-2 is able to measure earth ground loop resistances for multi-grounded systems using only current clamps. 

This technique eliminates the dangerous, and time consuming job of disconnecting parallel grounds, and finding suitable locations for auxiliary ground stakes. 

This allows you to perform earth ground tests in places you’ve not considered before, such as inside buildings, on power pylons, or anywhere you don’t have access to soil.
Features
  • A unique earth ground tester that performs testing with and without stakes
  • Tests 3- and 4-pole fall-of-potential, and 4-pole soil resistivity (with stakes)
  • Performs selective earth ground rod testing (one clamp + stakes)
  • Performs stakeless earth ground rod testing (two clamps)
  • Features Automatic Frequency Control (AFC) to minimize the effect of interference

1 - 3 of 3 Part Numbers
EI-1625
EI-1625
Selective/Stakeless Clamp Set for 1625
Fluke-1625-2
Fluke-1625-2
Advanced GEO Earth Ground Tester
Fluke-1625-2 Kit
Fluke-1625-2 Kit
Advanced GEO Earth Ground Tester Kit
1 - 3 of 3 Part Numbers

Specifications

Memory

  • Internal memory storage up to 1500 records accessible via USB port

Measuring Function

  • Interference voltage and frequency, earthing resistance 3- and 4-Pole with/without clip-on current transformer, resistance 2-Pole with AC, 2- and 4-Pole with DC

Operating Temperature

  • -10° C to 50° C
  • 14° F to 122° F

Temperature Coefficient

  • ± 0.1 % of Reading/°C 28° C

Type of Protection

  • IP56 for case, IP40 for battery door according to EN 60529

Safety

  • Protection by double and/or reinforced insulation. Max. 50 V to earth per IEC 61010-1. Pollution Degree 2

Auxiliary Power

  • 6 x 1.5 V alkaline (IEC LR6 or type AA)

Interference Voltage Measuring Range

  • 1 V to 50 V

Interference Voltage Resolution

  • 0.1 V

Interference Voltage Frequency Range

  • DC/AC 45 Hz to 400 Hz sine

Interference Voltage Accuracy

  • ± (5 % of Reading + 5-digit)

Measuring Sequence

  • Approx. 4 measurements/s

Interference Frequency Measuring Range

  • 6.0 Hz to 400 Hz

Interference Frequency Resolution

  • 0.1 Hz to 1 Hz

Interference Frequency Range

  • 1 V to 50 V

Interference Frequency Accuracy

  • ± (1 % of Reading + 2-digit)
Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team
show more