Transformer Series STA
Brand: R. STAHL AGThe application of a control transformer is demanding EN 60204-1for control circuits (few exceptions).
The protection of transformers has to be primary with a Motor protection circuit-breaker in tripping class 10 or 10 A.
Our circuit breaker (Type 8523/8.) will be adjusted according the current rating of the transformer (see attached table).
Secondary a miniature fuse or a MCB should be used.
The criterions are: Protective measures against direct or indirect contact (see also IEC 60364-4-43), line protection, overload protection of switching devices (welding of contacts).
All electrical settings of control circuit according to manufacturers' instructions.
A minimum distance of 40 mm to all other components has to be kept.
Features- Low voltage drop in switching inductive loads
- Flexible voltage adjustment by primary tapping (±5%)
- Limitation of short-circuit current in control circuit
- Typical applications: Control voltage circuits, functional extra-low voltage PELV, safety extra-low voltage SELV, protective separation (of circuits)
1 - 1 of 1 Part Numbers
STAA
Low voltage drop in switching inductive loads
Flexible voltage adjustment by primary tapping (±5%)
Limitation of short-circuit current in control circuit
Typical applications: Control voltage circuits, functional extra-low voltage PELV, safety extra-low voltage SELV, protective separation (of circuits)
General
- Functional Description - The application of a control transformer is demanding EN 60204-1for control circuits (few exceptions).The protection of transformers has to be primary with a Motor protection circuit-breaker in tripping class 10 or 10 A. Our circuitbreaker (Type 8523/8.) will be adjusted according the current rating of the transformer (see attached table). Secondary a miniature fuse or a MCB should be used. The criterions are: Protective measures against direct or indirect contact (see also IEC 60364-4-43), line protection, overload protection of switching devices (welding of contacts). all electrical settings of control circuit according to manufacturers' instructions. A minimum distance of 40 mm to all other components has to be kept.
- Highlights - Low voltage drop in switching inductive loads Flexible voltage adjustment by primary tapping (±5%) Limitation of short-circuit current in control circuit Typical applications: Control voltage circuits, functional extra-low voltage PELV, safety extra-low voltage SELV, protective separation (of circuits)
- Product Description - Transformer
- Product Type - STA
- Product Variant - Transformer Series STA
- WebCode - STAA