Yodify Product Library
Add the 945 Industrial Flue Gas Analyser to your store or catalog
Book Your Demo and See How
or create your store
945 Industrial Flue Gas Analyser
Brand: Kane International Limited
Features
- Measures Temperature, Pressure, O₂ and CO as standard
- Stores 150 sets of test results
- Output to IR Printer (optional)
OPTIONS
- (CO and any two other sensors)
- High range CO sensor
- Low range NO sensor
- High range NO sensor
- NO₂ sensor
- SO₂ sensor
- Wireless upgrade (2.1)
- Teflon Hose
Specifications
Ambient Operating Range
- -5° to +50° C / 10 % to 90 % RH, Non-Condensing
Battery Life
- > 8 Hours from Full Charge
Gas Measurement Accuracy
- Carbon Dioxide: ± 0.3 % of Reading
- Carbon Monoxide (H₂ Compensated), Carbon Monoxide: ± 20 ppm 400 ppm
- Carbon Monoxide: ± 10 % > 5000 ppm
- Carbon Monoxide: ± 5 % 100 ppm
- Oxygen, Excess Air: ± 0.2 %
- Poison Index: ± 0.01
- Pressure: ± 0.5 % of Full Scale
- Sulphur Dioxide (Optional): +5 % > 100 ppm
- Temp (Nett): ± 2° C ± 0.3 % of Reading
Gas Measurement Range
- Carbon Dioxide, Losses, Efficiency: 0 - 99.9 %
- Carbon Monoxide (H₂ Compensated): 0 - 4000 ppm
- Carbon Monoxide: 0 - 100000 ppm
- CO / CO₂ Ratio: 0 - 0.9999
- Excess Air: 0 - 2885.0 %
- Nitric Oxide (Low Range): 0 - 100 ppm
- Nitric Oxide & Sulphur Dioxide (Optional): 0 - 5000 ppm
- Nitrogen Dioxide (Optional): 100 ppm
- Oxygen: 0 - 25 %
- Poison Index: 0 - 99.99
- Pressure: 150 Mbar
- Temp (Nett): 0° C - 1200° C / 32° to 2200° F
Gas Measurement Resolution
- Carbon Monoxide (H₂ Compensated), Carbon Monoxide, Nitric Oxide (Low Range & Optional), Nitrogen Dioxide & Sulphur Dioxide (Optional): 1 ppm
- CO / CO₂ Ratio: 0.0001
- Oxygen, Carbon Dioxide, Losses, Efficiency, Excess Air: 0.1 %
- Poison Index: 0.01 %
- Pressure: 0.1 Mbar
- Temperature (Nett): 1.0° C/F
Power Supply (Battery Charger)
- Input: 110 VAC/220 VAC Nominal
- Output: 12 VAC Off Load
Pre-Programmed Fuels
- Natural Gas, Town Gas, Gascor, Light Oil, Heavy Oil, Propane, Butane, Anthracite, Coke, Coal, Kinsale Gas
Sensor, Probe
- L240 mm x Dia8 mm with 285 mm Long Stainless Steel Shaft, Typical K Thermocouple & 1.5 M Long Neoprene Hose
Temperature Measurement Accuracy
- Flue Temperature: ± 2.0° C ± 0.3 % of Reading
- Inlet Temperature: ± 1° C ± 0.3 % of Reading
Temperature Measurement Range
- Flue Temperature: 0° to 1200° C / 32° to 2200° F with Suitable Probe
- Inlet Temperature: 0° to 50° C / 32° to 122° F
Temperature Measurement Resolution
- Flue Temperature, Inlet Temperature: 0.1° C/F