Yodify Product Library
Instantly add the CPU & Power Module for Zone 1 / Div. 1 Series 9440/22 and 50,000+ more product series to your store or catalog  
Book Your Demo and See How
or create your store

CPU & Power Module for Zone 1 / Div. 1 Series 9440/22

Brand: R. STAHL AG

9440/22 series CPU & power modules (CPM) for Zone 1 are used for the intrinsically safe supply of power to up to eight IS1+ I/O modules and to field circuits. 

Intrinsically safe RS485-IS with PROFIBUS DP or Modbus RTU is used for communicating with the automation system. These CPMs support system and optical rings and can be replaced while the system is in operation (i.e. hot swapped) in Zone 1/Division 1.
Features
  • Suitable for Ex i V0/V1 HART PROFIBUS DP, Modbus RTU
  • Supporting system redundancy and optical rings
  • CPM in Zone 1 can be hot swapped
  • Integration in plant asset management systems via ServiceBus and FDT/DTM

1 - 8 of 8 Part Numbers
162211
162211
R. STAHL Remote I/O IS1 CPU and Power Module
Suitable for Ex i V0/V1 HART PROFIBUS DP, Modbus RTU

Supporting system redundancy and optical rings

CPM in Zone 1 can be hot swapped

Integration in plant asset management systems via ServiceBus and FDT/DTM

Ambient Conditions

  • Ambient temperature - -20 °C ... +65 °C
  • Ambient temperature max. - +65 °C
  • Ambient temperature min. - -20 °C
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +70 °C
  • Storage temperature max. - +70 °C
  • Storage temperature min. - -40 °C

Auxiliary power

  • Current consumption (with 8 I/O modules) - 0.4 A (230 V AC), 0.8 A (120 V AC)
  • Current consumption (without I/O modules) - 25 mA (230 V AC), 48 mA (120 V AC)
  • Nominal voltage - 120 V / 230 V AC
  • Power dissipation (per I/O module) - 1.0 W
  • Power dissipation (without I/O modules) - 8.4 W

Electrical Data

  • Connection RS-485 Interface - 3 x Sub-D socket, 9-pole
  • Field side of interfaces - RS-485-IS (Profibus specification)
  • Protocol RS-485 Interface - Profibus DP V1 HART
  • Protocols - Profibus DP V1 HART
  • Redundancy - STAHL standard
  • Transmission speed RS-485 - ≤ 1.5 Mbps

Explosion Protection

  • Application range (zones) - 1, 2, 21, 22
  • ATEX gas certificate - KEMA 02 ATEX 1333 X
  • Certificate EAC - TS RU S-DE.GB04.B.00448
  • Certificates - ATEX (DEK), Brazil (ULB), Canada (CSA), Canada (FM), EAC (STV), IECEx (DEK), Korea (KTL), USA (FM)
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 1, 2, 21, 22
  • Gas explosion protection ATEX - II 2 G Ex d [ia] [ib] IIC T4 Gb
  • Gas explosion protection EAC - 1 Ex d [ia Ga] [ib] IIC T4 Gb X
  • Gas explosion protection IECEx - Ex d [ia] [ib] IIC T4 Gb
  • IECEX gas certificate - IECEx KEM 08.0038X
  • Installation - Zone 1 / Division 1
  • Installation in Division NEC 500 - (Class I, II, III) 1, 2
  • Ship approval - ABS, CCS, ClassNK, DNVGL, RINA

General

  • Functional Description - 9440/22 series CPU & power modules (CPM) for Zone 1 are used for the intrinsically safe supply of power to up to eight IS1+ I/O modules and to field circuits. Intrinsically safe RS485-IS with PROFIBUS DP or Modbus RTU is used for communicating with the automation system. These CPMs support system and optical rings and can be replaced while the system is in operation (i.e. hot swapped) in Zone 1/Division 1.
  • Highlights - Suitable for Ex i V0/V1 HART PROFIBUS DP, Modbus RTU Supporting system redundancy and optical rings CPM in Zone 1 can be hot swapped Integration in plant asset management systems via ServiceBus and FDT/DTM
  • Product Description - Remote I/O IS1 CPU and Power Module
  • Product Type - 9440/22-01-21-C1243
  • Title Product Variant Technical Data - 9440/22-01-21-C1243 DPV1 CPU&powermodul
  • WebCode - 9440A

Mechanical Data

  • Height - 170.000 mm
  • Length - 250.000 mm
  • Weight - 2.963 kg
  • Width - 96.500 mm
162214
162214
R. STAHL Remote I/O IS1 CPU and Power Module
Suitable for Ex i V0/V1 HART PROFIBUS DP, Modbus RTU

Supporting system redundancy and optical rings

CPM in Zone 1 can be hot swapped

Integration in plant asset management systems via ServiceBus and FDT/DTM

Ambient Conditions

  • Ambient temperature - -20 °C ... +65 °C
  • Ambient temperature max. - +65 °C
  • Ambient temperature min. - -20 °C
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +70 °C
  • Storage temperature max. - +70 °C
  • Storage temperature min. - -40 °C

Auxiliary power

  • Current consumption (with 8 I/O modules) - 0.4 A (230 V AC), 0.8 A (120 V AC)
  • Current consumption (without I/O modules) - 25 mA (230 V AC), 48 mA (120 V AC)
  • Nominal voltage - 120 V / 230 V AC
  • Power dissipation (per I/O module) - 1.0 W
  • Power dissipation (without I/O modules) - 8.4 W

Electrical Data

  • Connection RS-485 Interface - 3 x Sub-D socket, 9-pole
  • Field side of interfaces - RS-485-IS (Profibus specification)
  • Protocol RS-485 Interface - Modbus RTU
  • Protocols - Modbus RTU
  • Redundancy - Yes
  • Transmission speed RS-485 - ≤ 1.5 Mbps

Explosion Protection

  • Application range (zones) - 1, 2, 21, 22
  • ATEX gas certificate - KEMA 02 ATEX 1333 X
  • Certificate EAC - TS RU S-DE.GB04.B.00448
  • Certificates - ATEX (DEK), Brazil (ULB), Canada (CSA), Canada (FM), EAC (STV), IECEx (DEK), Korea (KTL), USA (FM)
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 1, 2, 21, 22
  • Gas explosion protection ATEX - II 2 G Ex d [ia] [ib] IIC T4 Gb
  • Gas explosion protection EAC - 1 Ex d [ia Ga] [ib] IIC T4 Gb X
  • Gas explosion protection IECEx - Ex d [ia] [ib] IIC T4 Gb
  • IECEX gas certificate - IECEx KEM 08.0038X
  • Installation - Zone 1 / Division 1
  • Installation in Division NEC 500 - (Class I, II, III) 1, 2
  • Ship approval - ABS, CCS, ClassNK, DNVGL, RINA

General

  • Functional Description - 9440/22 series CPU & power modules (CPM) for Zone 1 are used for the intrinsically safe supply of power to up to eight IS1+ I/O modules and to field circuits. Intrinsically safe RS485-IS with PROFIBUS DP or Modbus RTU is used for communicating with the automation system. These CPMs support system and optical rings and can be replaced while the system is in operation (i.e. hot swapped) in Zone 1/Division 1.
  • Highlights - Suitable for Ex i V0/V1 HART PROFIBUS DP, Modbus RTU Supporting system redundancy and optical rings CPM in Zone 1 can be hot swapped Integration in plant asset management systems via ServiceBus and FDT/DTM
  • Product Description - Remote I/O IS1 CPU and Power Module
  • Product Type - 9440/22-01-21-C1202
  • Title Product Variant Technical Data - 120 V / 230 V AC
  • WebCode - 9440A

Mechanical Data

  • Height - 170.000 mm
  • Length - 250.000 mm
  • Weight - 2.963 kg
  • Width - 96.500 mm
162218
162218
R. STAHL Remote I/O IS1 CPU and Power Module
Suitable for Ex i V0/V1 HART PROFIBUS DP, Modbus RTU

Supporting system redundancy and optical rings

CPM in Zone 1 can be hot swapped

Integration in plant asset management systems via ServiceBus and FDT/DTM

Ambient Conditions

  • Ambient temperature - -20 °C ... +65 °C
  • Ambient temperature max. - +65 °C
  • Ambient temperature min. - -20 °C
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +70 °C
  • Storage temperature max. - +70 °C
  • Storage temperature min. - -40 °C

Auxiliary power

  • Current consumption (with 8 I/O modules) - 2.5 A (24 V DC)
  • Current consumption (without I/O modules) - 0.21 A (24 V DC)
  • Nominal voltage - 24 V DC
  • Power dissipation (per I/O module) - 1.4 W
  • Power dissipation (without I/O modules) - 5.0 W

Electrical Data

  • Connection RS-485 Interface - 3 x Sub-D socket, 9-pole
  • Field side of interfaces - RS-485-IS (Profibus specification)
  • Protocol RS-485 Interface - Profibus DP V1 HART
  • Protocols - Profibus DP V1 HART
  • Redundancy - STAHL standard
  • Transmission speed RS-485 - ≤ 1.5 Mbps

Explosion Protection

  • Application range (zones) - 1, 2, 21, 22
  • ATEX gas certificate - KEMA 02 ATEX 1333 X
  • Certificate EAC - TS RU S-DE.GB04.B.00448
  • Certificates - ATEX (DEK), Brazil (ULB), Canada (CSA), Canada (FM), EAC (STV), IECEx (DEK), Korea (KTL), USA (FM)
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 1, 2, 21, 22
  • Gas explosion protection ATEX - II 2 G Ex d [ia] [ib] IIC T4 Gb
  • Gas explosion protection EAC - 1 Ex d [ia Ga] [ib] IIC T4 Gb X
  • Gas explosion protection IECEx - Ex d [ia] [ib] IIC T4 Gb
  • IECEX gas certificate - IECEx KEM 08.0038X
  • Installation - Zone 1 / Division 1
  • Installation in Division NEC 500 - (Class I, II, III) 1, 2
  • Ship approval - ABS, CCS, ClassNK, DNVGL, RINA

General

  • Functional Description - 9440/22 series CPU & power modules (CPM) for Zone 1 are used for the intrinsically safe supply of power to up to eight IS1+ I/O modules and to field circuits. Intrinsically safe RS485-IS with PROFIBUS DP or Modbus RTU is used for communicating with the automation system. These CPMs support system and optical rings and can be replaced while the system is in operation (i.e. hot swapped) in Zone 1/Division 1.
  • Highlights - Suitable for Ex i V0/V1 HART PROFIBUS DP, Modbus RTU Supporting system redundancy and optical rings CPM in Zone 1 can be hot swapped Integration in plant asset management systems via ServiceBus and FDT/DTM
  • Product Description - Remote I/O IS1 CPU and Power Module
  • Product Type - 9440/22-01-11-C1243
  • Title Product Variant Technical Data - 9440/22-01-11-C1243 DPV1 CPU&power modul
  • WebCode - 9440A

Mechanical Data

  • Height - 170.000 mm
  • Length - 250.000 mm
  • Weight - 2.963 kg
  • Width - 96.500 mm
162221
162221
R. STAHL Remote I/O IS1 CPU and Power Module
Suitable for Ex i V0/V1 HART PROFIBUS DP, Modbus RTU

Supporting system redundancy and optical rings

CPM in Zone 1 can be hot swapped

Integration in plant asset management systems via ServiceBus and FDT/DTM

Ambient Conditions

  • Ambient temperature - -20 °C ... +65 °C
  • Ambient temperature max. - +65 °C
  • Ambient temperature min. - -20 °C
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +70 °C
  • Storage temperature max. - +70 °C
  • Storage temperature min. - -40 °C

Auxiliary power

  • Current consumption (with 8 I/O modules) - 2.5 A (24 V DC)
  • Current consumption (without I/O modules) - 0.21 A (24 V DC)
  • Nominal voltage - 24 V DC
  • Power dissipation (per I/O module) - 1.4 W
  • Power dissipation (without I/O modules) - 5.0 W

Electrical Data

  • Connection RS-485 Interface - 3 x Sub-D socket, 9-pole
  • Field side of interfaces - RS-485-IS (Profibus specification)
  • Protocol RS-485 Interface - Modbus RTU
  • Protocols - Modbus RTU
  • Redundancy - Yes
  • Transmission speed RS-485 - ≤ 1.5 Mbps

Explosion Protection

  • Application range (zones) - 1, 2, 21, 22
  • ATEX gas certificate - KEMA 02 ATEX 1333 X
  • Certificate EAC - TS RU S-DE.GB04.B.00448
  • Certificates - ATEX (DEK), Brazil (ULB), Canada (CSA), Canada (FM), EAC (STV), IECEx (DEK), Korea (KTL), USA (FM)
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 1, 2, 21, 22
  • Gas explosion protection ATEX - II 2 G Ex d [ia] [ib] IIC T4 Gb
  • Gas explosion protection EAC - 1 Ex d [ia Ga] [ib] IIC T4 Gb X
  • Gas explosion protection IECEx - Ex d [ia] [ib] IIC T4 Gb
  • IECEX gas certificate - IECEx KEM 08.0038X
  • Installation - Zone 1 / Division 1
  • Installation in Division NEC 500 - (Class I, II, III) 1, 2
  • Ship approval - ABS, CCS, ClassNK, DNVGL, RINA

General

  • Functional Description - 9440/22 series CPU & power modules (CPM) for Zone 1 are used for the intrinsically safe supply of power to up to eight IS1+ I/O modules and to field circuits. Intrinsically safe RS485-IS with PROFIBUS DP or Modbus RTU is used for communicating with the automation system. These CPMs support system and optical rings and can be replaced while the system is in operation (i.e. hot swapped) in Zone 1/Division 1.
  • Highlights - Suitable for Ex i V0/V1 HART PROFIBUS DP, Modbus RTU Supporting system redundancy and optical rings CPM in Zone 1 can be hot swapped Integration in plant asset management systems via ServiceBus and FDT/DTM
  • Product Description - Remote I/O IS1 CPU and Power Module
  • Product Type - 9440/22-01-11-C1202
  • Title Product Variant Technical Data - 24 V DC
  • WebCode - 9440A

Mechanical Data

  • Height - 170.000 mm
  • Length - 250.000 mm
  • Weight - 2.963 kg
  • Width - 96.500 mm
162712
162712
R. STAHL Remote I/O IS1 Base for Digital Output Module Relay
Suitable for Ex i V0/V1 HART PROFIBUS DP, Modbus RTU

Supporting system redundancy and optical rings

CPM in Zone 1 can be hot swapped

Integration in plant asset management systems via ServiceBus and FDT/DTM

Ambient Conditions

  • Ambient temperature - -20 °C ... +65 °C
  • Ambient temperature max. - +65 °C
  • Ambient temperature min. - -20 °C

Auxiliary power

  • Nominal voltage - 60 V AC

Explosion Protection

  • Certificates - Canada (FM), USA (FM)

General

  • Description - Division 1; Connection via conduit for digital output module relay Art. no. 162627
  • Functional Description - 9440/22 series CPU & power modules (CPM) for Zone 1 are used for the intrinsically safe supply of power to up to eight IS1+ I/O modules and to field circuits. Intrinsically safe RS485-IS with PROFIBUS DP or Modbus RTU is used for communicating with the automation system. These CPMs support system and optical rings and can be replaced while the system is in operation (i.e. hot swapped) in Zone 1/Division 1.
  • Highlights - Suitable for Ex i V0/V1 HART PROFIBUS DP, Modbus RTU Supporting system redundancy and optical rings CPM in Zone 1 can be hot swapped Integration in plant asset management systems via ServiceBus and FDT/DTM
  • Product Description - Remote I/O IS1 Base for digital output Module relay
  • Product Type - 9490/12-33
  • Product Variant - Socket for Digital Output Module Relay
  • Title Product Variant Technical Data - 9490/12-33 base for 9477 div. 1
  • WebCode - 9440A

Mechanical Data

  • Version - Connection via a conduit
  • Weight - 0.760 kg
162713
162713
R. STAHL Remote I/O IS1 Base for Digital Output Module Relay
Suitable for Ex i V0/V1 HART PROFIBUS DP, Modbus RTU

Supporting system redundancy and optical rings

CPM in Zone 1 can be hot swapped

Integration in plant asset management systems via ServiceBus and FDT/DTM

Ambient Conditions

  • Ambient temperature - -20 °C ... +65 °C
  • Ambient temperature max. - +65 °C
  • Ambient temperature min. - -20 °C

Auxiliary power

  • Nominal voltage - 250 V AC

Explosion Protection

  • Certificates - Canada (FM), USA (FM)

General

  • Description - Division 1; Connection via conduit for digital output module relay Art. no. 162630
  • Functional Description - 9440/22 series CPU & power modules (CPM) for Zone 1 are used for the intrinsically safe supply of power to up to eight IS1+ I/O modules and to field circuits. Intrinsically safe RS485-IS with PROFIBUS DP or Modbus RTU is used for communicating with the automation system. These CPMs support system and optical rings and can be replaced while the system is in operation (i.e. hot swapped) in Zone 1/Division 1.
  • Highlights - Suitable for Ex i V0/V1 HART PROFIBUS DP, Modbus RTU Supporting system redundancy and optical rings CPM in Zone 1 can be hot swapped Integration in plant asset management systems via ServiceBus and FDT/DTM
  • Product Description - Remote I/O IS1 Base for digital output Module relay
  • Product Type - 9490/12-34
  • Product Variant - Socket for Digital Output Module Relay
  • Title Product Variant Technical Data - 9490/12-34 base for 9477 div. 1
  • WebCode - 9440A

Mechanical Data

  • Version - Connection via a conduit
  • Weight - 0.760 kg
203585
203585
R. STAHL Remote I/O IS1 CPU and Power Module
Suitable for Ex i V0/V1 HART PROFIBUS DP, Modbus RTU

Supporting system redundancy and optical rings

CPM in Zone 1 can be hot swapped

Integration in plant asset management systems via ServiceBus and FDT/DTM

Ambient Conditions

  • Ambient temperature - -20 °C ... +65 °C
  • Ambient temperature max. - +65 °C
  • Ambient temperature min. - -20 °C
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +70 °C
  • Storage temperature max. - +70 °C
  • Storage temperature min. - -40 °C

Auxiliary power

  • Current consumption (with 8 I/O modules) - 2.5 A (24 V DC)
  • Current consumption (without I/O modules) - 0.21 A (24 V DC)
  • Nominal voltage - 24 V DC
  • Power dissipation (per I/O module) - 1.4 W
  • Power dissipation (without I/O modules) - 5.0 W

Electrical Data

  • Connection RS-485 Interface - 3 x Sub-D socket, 9-pole
  • Field side of interfaces - RS-485-IS (Profibus specification)
  • Protocol RS-485 Interface - Profibus DP V1 HART
  • Protocols - Profibus DP V1 HART
  • Redundancy - Profibus standard
  • Transmission speed RS-485 - ≤ 1.5 Mbps

Explosion Protection

  • Application range (zones) - 1, 2, 21, 22
  • ATEX gas certificate - KEMA 02 ATEX 1333 X
  • Certificate EAC - TS RU S-DE.GB04.B.00448
  • Certificates - ATEX (DEK), Brazil (ULB), Canada (CSA), Canada (FM), EAC (STV), IECEx (DEK), Korea (KTL), USA (FM)
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 1, 2, 21, 22
  • Gas explosion protection ATEX - II 2 G Ex d [ia] [ib] IIC T4 Gb
  • Gas explosion protection EAC - 1 Ex d [ia Ga] [ib] IIC T4 Gb X
  • Gas explosion protection IECEx - Ex d [ia] [ib] IIC T4 Gb
  • IECEX gas certificate - IECEx KEM 08.0038X
  • Installation - Zone 1 / Division 1
  • Installation in Division NEC 500 - (Class I, II, III) 1, 2
  • Ship approval - ABS, CCS, ClassNK, DNVGL, RINA

General

  • Functional Description - 9440/22 series CPU & power modules (CPM) for Zone 1 are used for the intrinsically safe supply of power to up to eight IS1+ I/O modules and to field circuits. Intrinsically safe RS485-IS with PROFIBUS DP or Modbus RTU is used for communicating with the automation system. These CPMs support system and optical rings and can be replaced while the system is in operation (i.e. hot swapped) in Zone 1/Division 1.
  • Highlights - Suitable for Ex i V0/V1 HART PROFIBUS DP, Modbus RTU Supporting system redundancy and optical rings CPM in Zone 1 can be hot swapped Integration in plant asset management systems via ServiceBus and FDT/DTM
  • Product Description - Remote I/O IS1 CPU and Power Module
  • Product Type - 9440/22-01-11-C1455
  • Title Product Variant Technical Data - 9440/22-01-11-C1455 CPM DPV1 PNORed
  • WebCode - 9440A

Mechanical Data

  • Height - 170.000 mm
  • Length - 250.000 mm
  • Weight - 2.963 kg
  • Width - 96.500 mm
203586
203586
R. STAHL Remote I/O IS1 CPU and Power Module
Suitable for Ex i V0/V1 HART PROFIBUS DP, Modbus RTU

Supporting system redundancy and optical rings

CPM in Zone 1 can be hot swapped

Integration in plant asset management systems via ServiceBus and FDT/DTM

Ambient Conditions

  • Ambient temperature - -20 °C ... +65 °C
  • Ambient temperature max. - +65 °C
  • Ambient temperature min. - -20 °C
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +70 °C
  • Storage temperature max. - +70 °C
  • Storage temperature min. - -40 °C

Auxiliary power

  • Current consumption (with 8 I/O modules) - 0.4 A (230 V AC), 0.8 A (120 V AC)
  • Current consumption (without I/O modules) - 25 mA (230 V AC), 48 mA (120 V AC)
  • Nominal voltage - 120 V / 230 V AC
  • Power dissipation (per I/O module) - 1.0 W
  • Power dissipation (without I/O modules) - 8.4 W

Electrical Data

  • Connection RS-485 Interface - 3 x Sub-D socket, 9-pole
  • Field side of interfaces - RS-485-IS (Profibus specification)
  • Protocol RS-485 Interface - Profibus DP V1 HART
  • Protocols - Profibus DP V1 HART
  • Redundancy - Profibus standard
  • Transmission speed RS-485 - ≤ 1.5 Mbps

Explosion Protection

  • Application range (zones) - 1, 2, 21, 22
  • ATEX gas certificate - KEMA 02 ATEX 1333 X
  • Certificate EAC - TS RU S-DE.GB04.B.00448
  • Certificates - ATEX (DEK), Brazil (ULB), Canada (CSA), Canada (FM), EAC (STV), IECEx (DEK), Korea (KTL), USA (FM)
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 1, 2, 21, 22
  • Gas explosion protection ATEX - II 2 G Ex d [ia] [ib] IIC T4 Gb
  • Gas explosion protection EAC - 1 Ex d [ia Ga] [ib] IIC T4 Gb X
  • Gas explosion protection IECEx - Ex d [ia] [ib] IIC T4 Gb
  • IECEX gas certificate - IECEx KEM 08.0038X
  • Installation - Zone 1 / Division 1
  • Installation in Division NEC 500 - (Class I, II, III) 1, 2
  • Ship approval - ABS, CCS, ClassNK, DNVGL, RINA

General

  • Functional Description - 9440/22 series CPU & power modules (CPM) for Zone 1 are used for the intrinsically safe supply of power to up to eight IS1+ I/O modules and to field circuits. Intrinsically safe RS485-IS with PROFIBUS DP or Modbus RTU is used for communicating with the automation system. These CPMs support system and optical rings and can be replaced while the system is in operation (i.e. hot swapped) in Zone 1/Division 1.
  • Highlights - Suitable for Ex i V0/V1 HART PROFIBUS DP, Modbus RTU Supporting system redundancy and optical rings CPM in Zone 1 can be hot swapped Integration in plant asset management systems via ServiceBus and FDT/DTM
  • Product Description - Remote I/O IS1 CPU and Power Module
  • Product Type - 9440/22-01-21-C1455
  • Title Product Variant Technical Data - 9440/22-01-21-C1455 CPM DPV1 PNORed
  • WebCode - 9440A

Mechanical Data

  • Height - 170.000 mm
  • Length - 250.000 mm
  • Weight - 2.963 kg
  • Width - 96.500 mm
1 - 8 of 8 Part Numbers
Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team
show more