Yodify Product Library
Instantly add the CPS Fixed Gas Detection and 50,000+ more product series to your store or catalog  
Book Your Demo and See How
or create your store

CPS Fixed Gas Detection

Brand: Oldham

The CPS Car Park System provides accurate and reliable monitoring for the highest level of protection in parking facilities and tunnels. 

The system was designed to comply with the high safety standards enforced in such European countries as Germany, the Netherlands and Belgium. 

Continuous monitoring significantly reduces your operating costs by optimizing the efficiency of ventilation systems and servo controls. Such efficiencies can produce energy savings of up to 40% when used with specific equipment.
Features
  • Up to 256 points per system
  • Up to 1,000 times faster than a pump system
  • Parking facility electricity savings of up to 40%

Specifications

Brand

Ambient Temperature Range

  • -10° to 40° C (14° to 104° F)

Approvals & Certifications

  • ANSI/UL 61010-1-2005 CAN/CSA C22.2 No. 61010-1
  • CE
  • EMC EN 50270
  • ETL
  • LVD Directive 2014/35/EU, 61010-1
  • TÜV

Cable Entry

  • 2 M16 Cable Glands (4 to 8 mm Diameter Power Supply/Local Relays) - CPS 10 Sensor Module
  • 5 M20 Cable Glands (Diameter: 5 to 12 mm for Power Supply & Local Relays) - CPS Central Detection Controller
  • 9 Grommets (Diameter: 5 to 7 mm) - CPS Central Detection Controller
  • PG9 - CPS Central Detection Controller

Cable Type

  • 2 Shielded Twisted Pairs RS-485 Cable

Calibration

  • Automatic Calibration
  • Non-Intrusive

Communication

  • Digital Output: RS-232 - Alarm
  • Digital Output: USB Protocol Priority - Alarm
  • Modbus RS-485 - Measuring Line (Digital Module Network [1 to 32 Addresses Selected with Mini Switches]), Alarm (Digital Output)

Consumption

  • 130 mA (256 mA - Max.
  • 140 mA + 12 mA Per Measurement Line (240 mA - Max.
  • 2.5 mA for the Toxic Sensor (4-20 mA - Max.
  • 3.2 mA (5.5 mA - Max.
  • 3.4 mA (5.7 mA - Max.
  • 50 mA Explo (90.7 mA - Max.

Display

  • Backlit LCD Display Screen (2 Lines of 32 Characters Each - 1 Line of Pictograms) 3 Operation Status LEDs: OK, Fault, Alarms

Electrical Connectors

  • Screwing Terminals (Cable: 1.5 mm²)

Electrical Contacts

  • RCT-Typical

Electrical Rating

  • 2 A at 250 V - CPS RM4 or RM8 Relay Module
  • 2 A at 250 Vac-30 Vcc (Resistive Charge) - Alarm

Environmental Protection

  • IP 31
  • IP54

Humidity

  • 5 to 95 % - Non-Condensing

Indication

  • Local Buzzer: Audible Alarm - Measuring Line
  • Local Buzzer: Fault Signals - Measuring Line
  • Status Indication after Calibration: Red/Green Electroluminescent Diode - CPS 10 Sensor Module

Isolation

  • 1500 V between the Power Supply & the Digital Network

Measuring Range

  • Carbon Monoxide: 0 to 300 ppm in 1 ppm Increments
  • Methane, Liquefied Petroleum Gas, Hydrogen: 0 to 100 % Lower Explosive Limit (LEL) in 1 % Increments
  • Nitric Oxide: 0 to 100 ppm in 1 ppm Increments
  • Nitrogen Dioxide: 0 to 30 ppm in 0.1 ppm Increments

Mounting

  • On DIN Rail
  • Rack-Mounted
  • Wall Mounted

Power Supply

  • Main: 0.8 A at 230 Vac
  • Main: 1.5 A at 115 Vac
  • Main: 85-264 Vac
  • Module: 12-30 Vac

Relay Output

  • Number of Relays: 4 Relays (CPS RM4)
  • Number of Relays: 8 Relays (CPS RM8)

Storage Temperature

  • -20° to 85° C (-4° to 185° F)

Documentation

Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team
show more