Yodify Product Library
Instantly add the ACS880-307LC Liquid-Cooled Diode Supply Unit and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
ACS880-307LC Liquid-Cooled Diode Supply Unit
Brand: ABB GroupOur liquid-cooled diode supply units take compactness to a new level.
The unit is designed to be compact and light, with integrated AC-chokes, current measurements and inbuilt DC-charging functionality.
The units, which can be connected in parallel to achieve higher power, have half-controlled diode-thyristor supply unit.
Features- Available for single drives and multi drives
- One core diode supply module, which can be connected in parallel for higher powers
- Inbuilt AC-chokes
- Half-controlled diode-thyristor supply unit
- DC-charging capability
- Internal current measurement
- 6/12 pulse AC supplies are supported
1 - 12 of 1,728 Part Numbers
ACS880-307LC-0490A-7+A018+E202+E205+F255
- Voltage - 690 V (Range 525-690 V)
- Pulse - 6-Pulse, Half-Controlled Diode Bridge
- Current Rating - 490 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Air Circuit Breaker
- Safety Function - None (Not Required)
- Earth Fault Protection - Earth Fault Monitoring, Earthed Mains, Standard
ACS880-307LC-0490A-7+A018+E202+E205+F255+Q951
- Voltage - 690 V (Range 525-690 V)
- Pulse - 6-Pulse, Half-Controlled Diode Bridge
- Current Rating - 490 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Air Circuit Breaker
- Safety Function - Emergency Stop, Category 0 with Opening the Main Contactor/Breaker, with Safety Relay
- Earth Fault Protection - Earth Fault Monitoring, Earthed Mains, Standard
ACS880-307LC-0490A-7+A018+E202+E205+F255+Q951+Q954
- Voltage - 690 V (Range 525-690 V)
- Pulse - 6-Pulse, Half-Controlled Diode Bridge
- Current Rating - 490 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Air Circuit Breaker
- Safety Function - Emergency Stop, Category 0 with Opening the Main Contactor/Breaker, with Safety Relay
- Earth Fault Protection - Earth Fault Monitoring, Unearthed Mains
ACS880-307LC-0490A-7+A018+E202+E205+F255+Q952
- Voltage - 690 V (Range 525-690 V)
- Pulse - 6-Pulse, Half-Controlled Diode Bridge
- Current Rating - 490 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Air Circuit Breaker
- Safety Function - Emergency Stop, Category 1 with Opening the Main Contactor/Breaker, with Safety Relay
- Earth Fault Protection - Earth Fault Monitoring, Earthed Mains, Standard
ACS880-307LC-0490A-7+A018+E202+E205+F255+Q952+Q954
- Voltage - 690 V (Range 525-690 V)
- Pulse - 6-Pulse, Half-Controlled Diode Bridge
- Current Rating - 490 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Air Circuit Breaker
- Safety Function - Emergency Stop, Category 1 with Opening the Main Contactor/Breaker, with Safety Relay
- Earth Fault Protection - Earth Fault Monitoring, Unearthed Mains
ACS880-307LC-0490A-7+A018+E202+E205+F255+Q954
- Voltage - 690 V (Range 525-690 V)
- Pulse - 6-Pulse, Half-Controlled Diode Bridge
- Current Rating - 490 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Air Circuit Breaker
- Safety Function - None (Not Required)
- Earth Fault Protection - Earth Fault Monitoring, Unearthed Mains
ACS880-307LC-0490A-7+A018+E202+E205+F255+Q963
- Voltage - 690 V (Range 525-690 V)
- Pulse - 6-Pulse, Half-Controlled Diode Bridge
- Current Rating - 490 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Air Circuit Breaker
- Safety Function - Emergency Stop, Category 0 with STO, with Safety Relay
- Earth Fault Protection - Earth Fault Monitoring, Earthed Mains, Standard
ACS880-307LC-0490A-7+A018+E202+E205+F255+Q963+Q954
- Voltage - 690 V (Range 525-690 V)
- Pulse - 6-Pulse, Half-Controlled Diode Bridge
- Current Rating - 490 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Air Circuit Breaker
- Safety Function - Emergency Stop, Category 0 with STO, with Safety Relay
- Earth Fault Protection - Earth Fault Monitoring, Unearthed Mains
ACS880-307LC-0490A-7+A018+E202+E205+F255+Q964
- Voltage - 690 V (Range 525-690 V)
- Pulse - 6-Pulse, Half-Controlled Diode Bridge
- Current Rating - 490 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Air Circuit Breaker
- Safety Function - Emergency Stop, Category 1 with STO, with Safety Relay
- Earth Fault Protection - Earth Fault Monitoring, Earthed Mains, Standard
ACS880-307LC-0490A-7+A018+E202+E205+F255+Q964+Q954
- Voltage - 690 V (Range 525-690 V)
- Pulse - 6-Pulse, Half-Controlled Diode Bridge
- Current Rating - 490 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Air Circuit Breaker
- Safety Function - Emergency Stop, Category 1 with STO, with Safety Relay
- Earth Fault Protection - Earth Fault Monitoring, Unearthed Mains
ACS880-307LC-0490A-7+A018+E202+E205+F255+Q979 +Q973/ +Q972
- Voltage - 690 V (Range 525-690 V)
- Pulse - 6-Pulse, Half-Controlled Diode Bridge
- Current Rating - 490 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Air Circuit Breaker
- Safety Function - Emergency Stop, Configurable Category 0 or 1 with STO & Safety Functions Module (FSO-12/-21)
- Earth Fault Protection - Earth Fault Monitoring, Earthed Mains, Standard
ACS880-307LC-0490A-7+A018+E202+E205+F255+Q979 +Q973/ +Q972+Q954
- Voltage - 690 V (Range 525-690 V)
- Pulse - 6-Pulse, Half-Controlled Diode Bridge
- Current Rating - 490 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Air Circuit Breaker
- Safety Function - Emergency Stop, Configurable Category 0 or 1 with STO & Safety Functions Module (FSO-12/-21)
- Earth Fault Protection - Earth Fault Monitoring, Unearthed Mains
1 - 12 of 1,728 Part Numbers
Specifications
Brand
Voltage & Power Range
- Mains: 3-Phase, UN3 380-415 V, +10 %/-10 %
- Mains: 585 to 7,027 kVA
- Motor: 3-Phase output Voltage 0 to UN3 /UN5 /UN7
- Mains: 3-Phase, UN7 525-690 V, +10 %/-10 %
Frequency
- Motor: 0 to ± 598 Hz
- Mains: 50/60 Hz ± 5 %
Storage / Transport Temperature
- -40° to 70° C
Operating Temperature
- Liquid-Cooled: 45° to 55° C with Derating of 0.5 %/1° C
- Liquid-Cooled: 0° to 45° C, No Frost Allowed
Motor Control
- Direct torque Control (DTC)
Certifications & Approvals
- cULus, CSA
- RCM, EAC
- TÜV
- RoHS
- LVD
- ATEX
- CE
- EMC
Environmental Protection
- IP54
- IP42
- IP22
Altitude
- 0 to 1,000 m, without derating
- 1,000 to 4,000 m, with derating of 1 %/100 m
Humidity
- 5 % to 95 % Relative Humidity, no condensation
Documentation
Certificate
- ACS880-x4 (frames R8i), -04XT, -04FXT, -x7(LC), -x04, -x04LC, -x07 and multidrives, EU Declaration of Conformity pdf 3.9 MB
- EU Declaration of Conformity, According to LVD 2014/35/EU and EMCD 2014/30/EU, ACS880-107, -107LC, -207, -207LC, -307, -307LC, -607, -607LC -907, -1007LC, -1607, -1607LC pdf 1.6 MB