Yodify Product Library
Add the Spare Sensor, Kayden CLASSIC 812, Flanged, P12 Series to your store or catalog
Book Your Demo and See How
or create your store
Spare Sensor, Kayden CLASSIC 812, Flanged, P12 Series
Brand: Kayden Instruments- Replacement Sensor for Kayden CLASSIC 812 Series
- Process Connection - Flanged
- Raised Face - RF
- Ring-Type Joint - RTJ
- Flange Size
- 1-1/2", DN 40
- 2", DN 50
- 3", DN 80
- 4", DN 100
- ANSI Rating
- 150#
- 300#
- 600#
- 900#
- Insertion 'U' Length
- Available in 1/2" or 1 cm increments
- Minimum 2.5" to Maximum 120" (6.0 - 305 cm)
- Temperature Range - Sensor
- -45° to 200° C
- -50° to 392° F
- Adjustable Set Point Range
- 0 - 254 feet/s
- 0 - 77 meters/s
- Materials of Construction - Sensor and Flange
- 316/316L Stainless Steel
- Hastelloy C-276
- Titanium Grade 2
- Other Metals Available
- Sensor Connection
- Molex 8-Pin
- Approvals (with Classic 812 Switch)
- UL, CSA, CRN, Single Seal, NACE
Specifications
Brand
Applications
- Flow
- Level
- Interface
Principle of Operation
- Thermal, Calorimetric
Insertion 'U' Length - Custom
- 6.4 cm to 305 cm (in 1 cm increments)
- 2.5" to 120" (in 1/2" increments)
Flange Type
- RF - Raised Face
- RTJ - Ring Typical Joint
Flange Class
- 150#
- 300#
- 600#
- 900#
Flange Size
- 1" DN 25
- 1-1/2" DN 40
- 2" DN 50
- 3" DN 80
- 4" DN 100
- 5" DN 125
- 6" DN 150
- 8" DN 200
- 10 DN 250
Flange Material
- 316, 316L Stainless Steel
- Hastelloy C-276
- Titanium Grade 2
- Other metals available
Wetted Materials
- 316, 316L Stainless Steel
- Hastelloy C-276
- Titanium Grade 2
- Other Metals Available
Sensor Construction
- All-Welded Construction
Operating Pressure Maximum - Sensor
- Per Flange Rating, ASME B16.5
Operating Temperature - Sensor
- -55° to 200° C
- -67° to 392° F
Sensor, Probe Style
- Insertion
Switch Point Range
- Air & Gases: 0.25 to 200 sfps, 0.08 to 60 smps - Standard Condition 21° C (70° F) at 14.7 psi (1 Atm)
- Hydrocarbon-based Liquids: 0.01 - 5.0 fps, 0.003 - 1.50 mps
- Water-based Liquids: 0.01 - 3.00 fps, 0.003 - 0.9 mps
Response Time
- Approximately 0.5 to 30 seconds
Sensor, Probe to Electronics Connection Type
- Molex 8-Pin
Accuracy
- Flow Service: ± 1.0 % of Set Point Velocity over Operating Range of ± 28° C (± 50° F)
- Level Service: ± 0.64 cm (0.25")
Approvals & Certifications - CLASSIC 812 Series
- CSA - Local (Sensor) Enclosure Flameproof: Class I, Div. 1, Groups B, C, D, Ex d IIB + H₂ AEx d IIB + H₂ (Class I, Zone 1, Group IIB + H₂) Temperature Code: T3 Enclosure Typical 4, IP55 Single Seal Approved per ANSI / ISA 12.27.01-2003
- CRN - Canadian Registration Numbers - 1" & 1-1/2" - Flanges Approved for All Provinces & Territories 812-RAA Series: CRN # 0F13787.2C 316, 316L Stainless Steel, Pipe NPS 1/2" Schedule 80 Code of Construction: ASME B31.3, max.
- CRN - Canadian Registration Numbers - 2" through 10" Flanges - Approved for All Provinces & Territories 812-RAA Series: CRN # 0F13773.2C 316, 316L Stainless Steel, Pipe NPS 3/4" Schedule 80 Code of Construction: ASME B31.3, max.