Yodify Product Library
Instantly add the EF-x2000-T Airflow Measurement with Temperature & Alarm Capability and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
EF-x2000-T Airflow Measurement with Temperature & Alarm Capability
Brand: EBTRON, IncThe EF-x2000-T is EBTRON’s top-of-the-line measurement solution for round ducts between 4 and 16 inches in diameter.
Ideal for most small duct airflow measurement and volumetric airflow tracking applications.
More features than the EF-x1000-T make this the best choice for all small duct measurement applications.
Features- Thermal Dispersion Technology
- Cost Effective Single Probe
- NIST-traceable Calibration
- %‐of‐reading Accuracy
- Airflow and Status Alarm
- Temperature Output Capability
- Analog and RS‐485 Output Models
- Dry Contact Relay
- Remote Transmitter with LCD Display
- 3‐year Warranty
1 - 1 of 1 Part Numbers
EF-x2000-T
The EF-x2000-T is EBTRON’s top-of-the-line measurement solution for round ducts between 4 and 16 inches in diameter. Ideal for most small duct airflow measurement and volumetric airflow tracking applications. More features than the EF-x1000-T make this the best choice for all small duct measurement applications.
1 - 1 of 1 Part Numbers
Specifications
Brand
Certifications & Approvals
- cULus
- FCC
- RoHS
Probe and Sensor Node Configurations
- 1 Probe x 2 Sensor Nodes/Probe [5” to 16” (27.0 to 406.4 mm) Probes]
- 1 Probe x 1 Sensor Node/Probe [4” (101.6 mm) Probe]
Installed Airflow Accuracy
- ± 3 % of Reading
Measured Accuracy
- Temperature: ± 0.15° F (0.08° C) to NIST-traceable Temperature Standards
- Airflow: ± 3 % of Reading to Volumetric Airflow Standards
Temperature Range
- Transmitter: -20° to 120° F (-28.9° to 48.9° C)
- Probe: -20° to 160° F (-28.9° to 71.1° C)
Humidity
- Transmitter: 5 to 95 %
- Probes: 0 to 100 %
Material of Construction
- Probe to Transmitter Cables: FEP Jacket, Plenum Rated CMP/CL2P, UL/cUL Listed, -67° to 302° F (-55° to 150° C), UV Tolerant
- Mounting Brackets: 304 Stainless Steel
- Tube: Mill Finish 6063 Aluminum (316 Stainless Steel with Stainless Steel Option)
- Sensing Node Internal Wiring: Kynar-Coated Copper
- Sensor Potting: Waterproof Marine Epoxy
- Sensing Node Housing: Glass-filled Polypropylene (Kynar with Stainless Steel Option)
Power Requirement
- Transmitter: 24 Vac (22.8-26.4 Under Load) @ 8 V-A
Alarm
- System Status Alarm: Sensor Diagnostic System Trouble Indication
- Airflow Alarm: Low and/or High User Defined Set Point Alarm
- High-Performance CV/VAV Terminal Box Measurement
- Small Duct Outdoor Air Delivery Monitoring
- Small Duct Airflow Tracking
- Hospital Pressurization
- Laboratory Pressurization