Yodify Product Library
Instantly add the Series SC4 Iso Verter II Signal Conditioning Module and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
Series SC4 Iso Verter II Signal Conditioning Module
Brand: Dwyer Instruments, LLCLinearized and isolated RTD and Thermocouple transmitters are part of the Series SC4000 Iso Verter® II Signal Conditioning Modules.
These modules completely isolate the input from the output and from the ground.
Compatible with industry standard 35 mm DIN Rail mount transmitters and isolators, these modules are easily applied in new or existing installations.
The SC4380 Process Signal Converter/Isolator accepts virtually all standard process signals as input, and isolates and retransmits the signal in either the same units or virtually any other standard process signal.
The SC4380 can be field programmed for reverse or direct action and can receive and transmit single sided or bipolar* signals. Low voltage units (SCL) are also available.
The SC4151 RTD Transmitters each offer a fixed scale range input (selected when ordered) and a linearized, isolated, field selectable 4 to 20 mA or 0 to 10 VDC output.
Output is selected by simple switch settings. Low voltage units (SCL) are also available.
SC4130 Thermocouple Transmitter offers a fixed scale range input (selected when ordered) and a linearized, isolated, field selectable 4 to 20 mA or 0 to 10 VDC output.
Output is selected by simple switch settings. Low voltage units (SCL) are also available.
Features- Up to 1500 Vac RMS Electrical Isolation
- Easily Installed on Industry Standard 35 mm DIN Rail
- Low Voltage SCL Units also Available
1 - 12 of 54 Part Numbers
SC4130C
- Voltage - Standard
- Model - Thermocouple Transmitter
- Temperature Range - J, 0° to 100° C
SC4130E
- Voltage - Standard
- Model - Thermocouple Transmitter
- Temperature Range - J, 0° to 250° C
SC4130H
- Voltage - Standard
- Model - Thermocouple Transmitter
- Temperature Range - K, -150° to 350° F
SC4130J
- Voltage - Standard
- Model - Thermocouple Transmitter
- Temperature Range - K, -100° to 200° C
SC4130L
- Voltage - Standard
- Model - Thermocouple Transmitter
- Temperature Range - K, 0° to 250° C
SC4130N
- Voltage - Standard
- Model - Thermocouple Transmitter
- Temperature Range - K, 0° to 500° C
1 - 12 of 54 Part Numbers
Specifications
Brand
Input
- 0-10 V - Voltage
- 0 to 100 mA - Current
- 0 to 500 mV - Voltage
- RTD Search Current < 500 µA
Input Impedance
- 1 Megaohms - Voltge
- 10 ohms - Current
- 3 megaohms
Isolation
- 1500 Vac RMS
Linearization
- ± 0.1 % of Full Scale
Mounting
- 35 mm DIN Rail
Output
- 0-10 V - Voltage
- 0 to 20 mA - Current
- 500 ohms Min. (20 mA - Max.
- 600 ohms, Max.
Power Requirement
- 12-24 Vdc / Vac
- 50/400 Hz
- 85-265 Vdc/Vac
Thermal Drift
- ± 0.02 %/°C Typical
- ± 0.05 %/°C, Max.
- Signal Conditioners Used in Panels for Isolation
- Converting signals for Boilers and Control Systems