FP302 Series Fieldbus to Pneumatic Signal Converter
Brand: Smar International Corp
Features
- Output Signal:
- Standard: 3 to 15 psi (0.2 to 1.0 kgf/cm²)
- Extended: 3 to 30 psi (0.2 to 2.0 kgf/cm²)
- Materials of Construction:
- Injected aluminum with polyester painting, epoxy painting
- 316 Stainless Steel - CF8M (ASTM - A351) housing. Buna N for cover.
- Electrical Connection:
- 1/2" -14 NPT
- 1/2" - 14 NPT x 3/4 NPT (Al316) - with adapter
- 1/2" - 14 NPT x 3/4 BSP (Al316) - with adapter
- 1/2" - 14 NPT x 1/2 BSP (Al316) - with adapter
- PG 13.5 DIN
- M20 x 1.5
- Pneumatic Connections:
- Air supply and output: 1/4"-18 NPT
- Gauges: 1/8"-27 NPT
- Input Signal: Digital only, 31.25 Kbit/s voltage mode with bus power.
- Output Load Limitation: External Output Supply Voltage 3-45 Vdc.
- Power Supply:
- Bus powered 9-32 Vdc.
- Current consumption quiescent 12 mA
- Output Impedance @ 7.8 to 39 kHz
- Temperature Range: -40° to +90°C
- Indication: Digital Indicator (LCD) 4-1/2 numeric and 5 alphanumeric digits.
- Accuracy: 0.4% of Span; including hysteresis and stability effects.
- Air Supply: 18 to 100 psi (1.24 to 7 kgf/cm²)
- Air Consumption:
- 0.3 Nm³/h (0.18 scfm) @ 1.24 bar (18 psi) air supply
- 0.45 Nm³/h (0.26 scfm) @ 2.8 bar (40 psi) air supply
- 0.80 Nm³/h (0.47 scfm) @ 7 bar (100 psi) air supply
- Electromagnetic Interference Effect: Designed according to the IEC 801 and European EN50081 and EN50082 standards.
- Humidity Limit: 0 to 100% RH
1 - 12 of 12 Part Numbers
FP302-000-I3
FP302-000-I3-G1
FP302-010-I3
FP302-010-I3-G1
FP302-100-I3-G1
FP302-11-0/H0/I5/J1/G0/P0
FP302-110-I3
FP302-110-I3-G1
FP302-120-H0-I3-P0-J0-G0
- FP302: Foundation Fieldbus
- 1: With LCD Indicator
- 2: 316SST bracket and accessories
- 0: 1/2" - 14 NPT
- H0: Aluminum Housing Material (Default) (IP/TYPE)
- I3: CSA: XP, IS, NI, DI, Certificate for use in Hazardous Locations (CEPEL, CSA e FM)
- P0: Gray Munsell N 6,5 Paint
- J0: With Name Tag
- G0: 3 (min) to 15 (max) psi
1 - 12 of 12 Part Numbers
Specifications
Brand
Accuracy
- 0.4 % of Span, Including Hysteresis & Stability Effects
Air Consumption
- Maximum
Air Flow Capacity
- 3.40 Nm³/hour (2 scfm) at 1.24 bar (18 psi, 124 kPa) Air Supply
- 6.80 Nm³/hour (4 scfm) at 2.8 bar (40 psi, 280 kPa) Air Supply
Air Supply
- 18 to 100 psi (1.24 to 6.9 bar, 124 to 689 kPa)
Ambient Temperature Range
- -40° to 85° C (-40° to 185° F)
Approvals & Certifications
- CRN - Canadian Registration Number
Configuration
- Local Adjustment Via FOUNDATION Fieldbus. System 302-7 or Any Other FF Configurator
- Local Basic Configuration Via Magnetic Tool for Converts with Local Display. Complete Configuration with Remote Configurator (PROFIBUS PA)
Cover - for Local Enclosure
- Buna-N
Display
- Optional 4-1/2-Digit Numerical & 5-Character Alphanumerical LCD Indicator
Electrical Connectors
- 1/2" NPT
- 1/2" NPT x 1/2" BSP (AI316) - with Adapter
- 1/2" NPT x 3/4" BSP (AI316) - with Adapter
- 1/2" NPT x 3/4" NPT (AI316) - with Adapter
- M20 x 1.5
- PG13.5
Electromagnetic Interference Effect
- Designed According to the IEC 801 & European EN 50081 & EN 50082 Standards
Enclosure Finish
- Epoxy Paint
Enclosure, Body Material
- 316 Stainless Steel
- ASTM - A351
Environmental Protection
- Explosion & Weatherproof, Intrinsic Safe as Per FISCO
Humidity
- 0 to 100 % RH
Input Power
- 7.8 kHz to 39 kHz, Output Impedence
- Bus Powered: 9-32 Vdc
Input Signal
- Digital Only, FOUNDATION Fieldbus, 31.25 Kbit/s Voltage Mode with Bus Power.
- Digital, According to the IEC 1158-2 (H1) Standard, Voltage Mode 31.25 Kbit/s, Bus Powered.
Operating Temperature - Display
- -40° to 85° C (-40° to 185° F)
Output
- 3 to 15 psi (0.2 to 1.0 bar, 20.7 to 103.4 kPa)
- 3 to 30 psi (0.2 to 2.0 bar, 20.7 to 206.8 kPa), Extended Range
Process Temperature
- -10° to 60° C (15° to 175° F)
Storage Temperature
- -40° to 90° C (-40° to 194° F)
Turn-On Time
- Approximately 10 seconds
Update Time
- Approximately 0.5 second