Yodify Product Library
Instantly add the PDTech DeltaMaxx Offline Digital Loss Factor/Capacitance Analyzer & Partial Discharge Detector and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
PDTech DeltaMaxx Offline Digital Loss Factor/Capacitance Analyzer & Partial Discharge Detector
Brand: IRIS PowerThe PDTech DELTAMAXX digital system determines with high precision the dielectric loss factor (power factor), capacitance, and partial discharge of:
- Generator and motor windings
- Transformers
- Cables and capacitors
The available systems are:
- PD detector only with or without integrated coupling (reference) capacitor
- Loss factor and capacitance measuring device
- Both functions integrated into one single unit Units for 15 kV, 20 kV, 30 kV and 50 kV test voltages are available.
Specifications
Brand
Coupler Impedance
- Integrated High-Voltage Isolation Transformer
Coupling Capacitor
- 1 NF Nominal up to 20 kV at 23°C
Display
- Phase Resolved Partial Discharge Pattern
Interface
- USB PC Requirement: Desktop or Notebook, Windows® XP, 512 MB (Min.)
Maximum Pulse Repetition Rate
- 40 kHz
PD Band Pass
- Designed According to IEC 60270, 40-800 kHz
PD Ranges
- Depends on Version & Test Object & Noise, 10 PC to 200 NC Typical
Power
- USB & External 6 Vdc Power Supply
Test Frequency
- 10 to 100 Hz (HV Frequency Range)
Test Voltage Range
- 15 kV (DELTA Maximum
- 20 kV (DELTA Maximum
- 30 kV (DELTA Maximum
- 50 kV (DELTA Maximum