Yodify Product Library
Instantly add the PD686 Loop-Powered NEMA 4X Intrinsically Safe & Non-Incendive Digital Meter and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
PD686 Loop-Powered NEMA 4X Intrinsically Safe & Non-Incendive Digital Meter
Brand: Precision Digital CorporationThe PD686 is an FM Approved, CSA Certified intrinsically safe and non-incendive, NEMA 4X, IP67 loop-powered indicator that is easy to install and program.
It can be seen from considerable distance and even in bright sunlight.
The fact that this meter is loop-powered means that there is no need to run additional, costly power lines into a hazardous area.
The meter gets all of the power it needs from the 4-20 mA loop and its 1 V drop results in a minimal burden on the loop.
The meter features a wide -40° to +85° C operating temperature range and is available with a ½" conduit hole in a location of your choice for easy installation.
Calibration is a quick two-step process involving the adjustment of only high and low, non-interacting potentiometers.
Features- NEMA 4X, IP67 Loop-Powered Field-Mount Process Meter
- 4-20 mA Input
- 1.0" (25.4 mm) 3½ Digits LCD Display; -1999 to 1999
- 1 V Drop
- HART® Protocol Transparent
- Operates from -40 to 85° C (-40 to 185° F)
- Operates from -40 to 40° C (-40 to 104° F) for Canadian Installations
- Zero & Span Potentiometer Adjustments for Easy Field Scaling
- Plastic NEMA 4X, IP67 Enclosure
- FM Approved & CSA Certified as Intrinsically Safe & Non-incendive
- Conformal Coated PCBs for Dust and Humidity Protection
- One ½" Conduit Hole (Rear, Top, Bottom or None)
- Pipe & Panel Mounting Kits
- Stainless Steel Tag Available
1 - 4 of 4 Part Numbers
PD686
- Loop-Powered Remote Display
- Display:
- 1.0" (25.4mm)
- 3-1/2 (1999) Digit LCD
- Performance:
- 2-step calibration
- Input: 4-20mA @ 30 VDC Maximum
- Power Supply:
- Loop-Powered,
- Removable Screw Terminals
- 12-26 AWG
- Connections:
- 1/2" Conduit Hole on Bottom
- Operating Temperature: -40°C to +85°C (-40°F to +185°F)
- Enclosure Materials:
- Impact-resistant glass-filled polycarbonate body
- Impact-resistant clear polycarbonate cover
- Environmental:
- NEMA 4X
- IP67
- Agency Approvals:
- FM
- CSA Approved for Class I,II,III; Division 1; Groups A,B,C,D,E,F&G Hazardous Locations
PD686-X
- 1/2" Conduit Hole Location - Rear
PD686-Y
- 1/2" Conduit Hole Location - Top
PD686-Z
- Loop-Powered Remote Display with no Holes
- Display:
- 1.0" (25.4mm)
- 3-1/2 (1999) Digit LCD
- Performance:
- 2-step calibration
- Input: 4-20mA @ 30 VDC Maximum
- Power Supply:
- Loop-Powered,
- Removable Screw Terminals
- 12-26 AWG
- Connections:
- Removable screw terminals
- 12 to 26 AWG
- Operating Temperature: -40°C to +85°C (-40°F to +185°F)
- Enclosure Materials:
- Impact-resistant glass-filled polycarbonate body
- Impact-resistant clear polycarbonate cover
- Environmental:
- NEMA 4X
- IP67
- Agency Approvals:
- FM
- CSA Approved for Class I,II,III; Division 1; Groups A,B,C,D,E,F&G Hazardous Locations
1 - 4 of 4 Part Numbers
Specifications
Accuracy
- ± 0.1 % of Full Scale ± 1 Count
Approvals & Certifications
- CSA
- FM
Conduit Hole
- One 1/2” Conduit Hole
Electrical Connectors
- Terminal Block for 12 to 22 AWG Wire
Enclosure, Body Material
- Impact-Resistant Glass-Filled Polycarbonate
Environmental Protection
- IP66
- NEMA 4X / IP66
Humidity
- 0 to 90 % Non-Condensing
Input
- 4-20 mA
Operating Temperature
- -40° to 85° C (-40° to 185° F)
Voltage Drop
- 1 V at 20 mA