Yodify Product Library
Instantly add the GTx116e-PC Airflow and Temperature Measurement Device with Integral Relative Humidity Sensor (With /H Option) and 50,000+ more product series to your store or catalog  
Book Your Demo and See How
or create your store

GTx116e-PC Airflow and Temperature Measurement Device with Integral Relative Humidity Sensor (With /H Option)

Brand: EBTRON, Inc

The GTx116e-PC is EBTRON’s top-of-the-line solution for accurate and repeatable measurement in ducts and plenums. 

Ruggedized RH sensor option (/H), onboard barometric pressure sensor and velocity-weighted temperature results in accurate relative humidity,  enthalpy and dew point calculations. 

Ideal for supply, return and outdoor air intake applications on systems with an airside economizer. Bluetooth® low energy technology interface.
Features
  • Thermal Dispersion Airflow Technology
  • Supports up to 16 Sensor Nodes
  • NIST-traceable Calibration
  • %-of-reading Airflow Accuracy
  • Airflow and Status Alarms
  • Velocity-weighted Temperature
  • Output %RH, Enthalpy or Dew Point (Requires /H option)
  • Three Mounting Styles
  • Remote Transmitter with LCD Display
  • 3-year Warranty

1 - 1 of 1 Part Numbers
GTx116e-PC
GTx116e-PC
EBTRON Airflow and Temperature Measurement Device with Integral Relative Humidity Sensor (with /H Option)
The GTx116e-PC is EBTRON’s top-of-the-line solution for accurate and repeatable measurement in ducts and plenums. Ruggedized RH sensor option (/H), onboard barometric pressure sensor and velocity-weighted temperature results in accurate relative humidity,  enthalpy and dew point calculations. 

Ideal for supply, return and outdoor air intake applications on systems with an airside economizer. Bluetooth® low energy technology interface.
1 - 1 of 1 Part Numbers

Specifications

Brand

Probe and Sensor Node Configurations (Maximum)

  • 2 Probes x 8 Sensor Nodes/Probe
  • 4 Probes x 4 Sensor Nodes/Probe

Certifications & Approvals

  • CE
  • RoHS
  • BTL
  • cULus
  • FCC

NIST

  • NIST-traceable Calibration

Installed Airflow Accuracy

  • Ducts/Plenum: ± 3 % of Reading
  • Non-ducted OA Intakes: Better than or Equal to ± 5 % of Reading

Measured Accuracy

  • Airflow: ± 2 % of Reading to NIST-traceable Airflow Standards
  • Temperature: ± 0.15° F (0.08° C) to NIST-traceable Temperature Standards

Temperature Range

  • Transmitter: -20° to 120° F (-28.9° to 48.9° C)
  • Probe: -20° to 160° F (-28.9° to 71.1° C)

Humidity

  • Transmitter: 5 to 95 % Non-Condensing
  • Probes: 0 to 100 % Non-Condensing

Material of Construction

  • Sensing Node Housing: Glass-filled Polypropylene (Kynar with Stainless Steel Option)
  • Sensor Potting: Waterproof marine Epoxy
  • Sensing Node Internal Wiring: Kynar-Coated Copper
  • Mounting Brackert: 304 Stainless Steel
  • Tube: Gold Anodized 6063 Aluminum (316 Stainless Steel with Stainless Steel Option)

Power Requirement

  • Transmitter: 24 Vac (22.8-26.4 Under Load) @ 20 V-A Max.

Alarm

  • Airflow: Low and/or High User Defined Set Point Alarm
  • System Status Alarm: Sensor Diagnostic System Trouble Indication

  • Outdoor Air Delivery  Monitoring and Control  
  • Differential Airflow Tracking  for Building Pressurization  Control  
  • Airside Economizer Enthalpy  Switchover Detection  
  • Supply Air Humidity  Monitoring and Control  
  • DOAS Dew Point Monitoring
Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team
show more