Ex Plug Connector Series 8591/1, 8591/4
Brand: R. STAHL AGR.STAHL Series 8591/1 and 8591/4 4-pole, explosion-protected miniCLIX plug connectors disconnect non-intrinsically safe circuits up to 250 V/10 A and are used as a hot swap plug connection for signal and data cables.
They are available in various versions and materials: Device plugs, flange sockets, plugs/couplers made of polyamide, nickel-plated brass or stainless steel. The cable can be connected using a crimp or spring clamp terminal. Preinstalled cables for device plugs and flange sockets enable fast and safe installation in the end devices.
Features- Multiple options for easy use, simple installation and maintenance
- Safe and fast disconnection under load
- 4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations
- Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
1 - 12 of 29 Part Numbers
153995
Multiple options for easy use, simple installation and maintenance
Safe and fast disconnection under load
4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations
Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
Ambient Conditions
- Ambient temperature - -55 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -55 °C
Components
- Locking device present - No
- Protective cap available - No
Electrical Data
- Frequency Hz (for AC) - 50, 60
- Rated operational voltage AC - 230.00 - 250.00 V
Explosion Protection
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 03 ATEX 1097 X
- ATEX gas certificate - PTB 03 ATEX 1097 X
- Certificates - ATEX (PTB), IECEx (BKI)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T60 °C Db
- Dust explosion protection IECEx - Ex tb IIIC T60 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx BKI 07.0001 X
- IECEX gas certificate - IECEx BKI 07.0001X
General
- Functional Description - R. STAHL Series 8591/1 and 8591/4 4-pole, explosion-protected miniCLIX plug connectors disconnect non-instrinsically safe circuits up to 250 V/10 A and are used as a hot swap plug connection for signal and data cables. They are available in various versions and materials: Device plugs, flange sockets, plugs/couplers made of polyamide, nickel-plated brass or stainless steel. The cable can be connected using a crimp or spring clamp terminal. Preinstalled cables for device plugs and flange sockets enable fast and safe installation in the end devices.
- Highlights - Multiple options for easy use, simple installation and maintenance Safe and fast disconnection under load 4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
- Product Description - miniCLIX plug connector Coupling
- Product Type - 8591/431-10-3001
- Title Product Variant Technical Data - 8591/431-10-3001 4P+PE COU 1 10h B n S04
- WebCode - 8591A
Mechanical Data
- Cable entry max. - 7.50 mm
- Cable entry min. - 4.00 mm
- Clamping range - 4.00 … 7.50 mm
- Coding (clock hour position) - 10
- Degree of protection (IP) - IP66
- Degree of protection note - IP68 (2 m water column, 1 hour) according to IEC/EN 60529 (with protective caps closed and secured as well as properly fitted and secured components)
- Detailed number of poles - 4 P + PE
- Enclosure material - Nickel-plated brass
- Recommended colour ring coding - blue
- Weight - 0.152 kg
Mounting / Installation
- Connection type - 1.5 mm2 crimp
153998
Multiple options for easy use, simple installation and maintenance
Safe and fast disconnection under load
4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations
Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
Ambient Conditions
- Ambient temperature - -55 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -55 °C
Components
- Locking device present - No
- Protective cap available - No
Electrical Data
- Frequency Hz (for AC) - 50, 60
- Rated operational voltage AC - 230.00 - 250.00 V
Explosion Protection
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 03 ATEX 1097 X
- ATEX gas certificate - PTB 03 ATEX 1097 X
- Certificates - ATEX (PTB), IECEx (BKI)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T60 °C Db
- Dust explosion protection IECEx - Ex tb IIIC T60 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx BKI 07.0001 X
- IECEX gas certificate - IECEx BKI 07.0001X
General
- Functional Description - R. STAHL Series 8591/1 and 8591/4 4-pole, explosion-protected miniCLIX plug connectors disconnect non-instrinsically safe circuits up to 250 V/10 A and are used as a hot swap plug connection for signal and data cables. They are available in various versions and materials: Device plugs, flange sockets, plugs/couplers made of polyamide, nickel-plated brass or stainless steel. The cable can be connected using a crimp or spring clamp terminal. Preinstalled cables for device plugs and flange sockets enable fast and safe installation in the end devices.
- Highlights - Multiple options for easy use, simple installation and maintenance Safe and fast disconnection under load 4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
- Product Description - miniCLIX plug connector Coupling
- Product Type - 8591/431-10-0001
- Title Product Variant Technical Data - 8591/431-10-0001 4P+PE COU 1 10h P n S04
- WebCode - 8591A
Mechanical Data
- Cable entry max. - 7.50 mm
- Cable entry min. - 4.00 mm
- Clamping range - 4.00 … 7.50 mm
- Coding (clock hour position) - 10
- Degree of protection (IP) - IP66
- Degree of protection note - IP68 (2 m water column, 1 hour) according to IEC/EN 60529 (with protective caps closed and secured as well as properly fitted and secured components)
- Detailed number of poles - 4 P + PE
- Enclosure material - Plastic
- Recommended colour ring coding - blue
- Weight - 0.083 kg
Mounting / Installation
- Connection type - 1.5 mm2 crimp
154004
Multiple options for easy use, simple installation and maintenance
Safe and fast disconnection under load
4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations
Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
Ambient Conditions
- Ambient temperature - -55 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -55 °C
Components
- Locking device present - No
- Protective cap available - No
Electrical Data
- Frequency Hz (for AC) - 50, 60
- Rated operational voltage AC - 230.00 - 250.00 V
Explosion Protection
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 03 ATEX 1097 X
- ATEX gas certificate - PTB 03 ATEX 1097 X
- Certificates - ATEX (PTB), IECEx (BKI)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T60 °C Db
- Dust explosion protection IECEx - Ex tb IIIC T60 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx BKI 07.0001 X
- IECEX gas certificate - IECEx BKI 07.0001X
General
- Functional Description - R. STAHL Series 8591/1 and 8591/4 4-pole, explosion-protected miniCLIX plug connectors disconnect non-instrinsically safe circuits up to 250 V/10 A and are used as a hot swap plug connection for signal and data cables. They are available in various versions and materials: Device plugs, flange sockets, plugs/couplers made of polyamide, nickel-plated brass or stainless steel. The cable can be connected using a crimp or spring clamp terminal. Preinstalled cables for device plugs and flange sockets enable fast and safe installation in the end devices.
- Highlights - Multiple options for easy use, simple installation and maintenance Safe and fast disconnection under load 4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
- Product Description - miniCLIX plug connector Plug
- Product Type - 8591/471-10-3001
- Title Product Variant Technical Data - 8591/471-10-3001 4P+PE PLU 1 10h B n S04
- WebCode - 8591A
Mechanical Data
- Cable entry max. - 7.50 mm
- Cable entry min. - 4.00 mm
- Clamping range - 4.00 … 7.50 mm
- Coding (clock hour position) - 10
- Degree of protection (IP) - IP66
- Degree of protection note - IP68 (2 m water column, 1 hour) according to IEC/EN 60529 (with protective caps closed and secured as well as properly fitted and secured components)
- Detailed number of poles - 4 P + PE
- Enclosure material - Nickel-plated brass
- Recommended colour ring coding - blue
- Weight - 0.162 kg
Mounting / Installation
- Connection type - 1.5 mm2 crimp
154007
Multiple options for easy use, simple installation and maintenance
Safe and fast disconnection under load
4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations
Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
Ambient Conditions
- Ambient temperature - -55 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -55 °C
Components
- Locking device present - No
- Protective cap available - No
Electrical Data
- Frequency Hz (for AC) - 50, 60
- Rated operational voltage AC - 230.00 - 250.00 V
Explosion Protection
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 03 ATEX 1097 X
- ATEX gas certificate - PTB 03 ATEX 1097 X
- Certificates - ATEX (PTB), IECEx (BKI)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T60 °C Db
- Dust explosion protection IECEx - Ex tb IIIC T60 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx BKI 07.0001 X
- IECEX gas certificate - IECEx BKI 07.0001X
General
- Functional Description - R. STAHL Series 8591/1 and 8591/4 4-pole, explosion-protected miniCLIX plug connectors disconnect non-instrinsically safe circuits up to 250 V/10 A and are used as a hot swap plug connection for signal and data cables. They are available in various versions and materials: Device plugs, flange sockets, plugs/couplers made of polyamide, nickel-plated brass or stainless steel. The cable can be connected using a crimp or spring clamp terminal. Preinstalled cables for device plugs and flange sockets enable fast and safe installation in the end devices.
- Highlights - Multiple options for easy use, simple installation and maintenance Safe and fast disconnection under load 4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
- Product Description - miniCLIX plug connector Plug
- Product Type - 8591/471-10-0001
- Title Product Variant Technical Data - 8591/471-10-0001 4P+PE PLU 1 10h P n S04
- WebCode - 8591A
Mechanical Data
- Cable entry max. - 7.50 mm
- Cable entry min. - 4.00 mm
- Clamping range - 4.00 … 7.50 mm
- Coding (clock hour position) - 10
- Degree of protection (IP) - IP66
- Degree of protection note - IP68 (2 m water column, 1 hour) according to IEC/EN 60529 (with protective caps closed and secured as well as properly fitted and secured components)
- Detailed number of poles - 4 P + PE
- Enclosure material - Plastic
- Recommended colour ring coding - blue
- Weight - 0.082 kg
Mounting / Installation
- Connection type - 1.5 mm2 crimp
154013
Multiple options for easy use, simple installation and maintenance
Safe and fast disconnection under load
4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations
Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
Ambient Conditions
- Ambient temperature - -55 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -55 °C
Components
- Locking device present - No
- Protective cap available - No
Electrical Data
- Frequency Hz (for AC) - 50, 60
- Rated operational voltage AC - 230.00 - 250.00 V
Explosion Protection
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 03 ATEX 1097 X
- ATEX gas certificate - PTB 03 ATEX 1097 X
- Certificates - ATEX (PTB), IECEx (BKI)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T60 °C Db
- Dust explosion protection IECEx - Ex tb IIIC T60 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx BKI 07.0001 X
- IECEX gas certificate - IECEx BKI 07.0001X
General
- Functional Description - R. STAHL Series 8591/1 and 8591/4 4-pole, explosion-protected miniCLIX plug connectors disconnect non-instrinsically safe circuits up to 250 V/10 A and are used as a hot swap plug connection for signal and data cables. They are available in various versions and materials: Device plugs, flange sockets, plugs/couplers made of polyamide, nickel-plated brass or stainless steel. The cable can be connected using a crimp or spring clamp terminal. Preinstalled cables for device plugs and flange sockets enable fast and safe installation in the end devices.
- Highlights - Multiple options for easy use, simple installation and maintenance Safe and fast disconnection under load 4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
- Product Description - miniCLIX plug connector Flange socket
- Product Type - 8591/481-10-3000
- Title Product Variant Technical Data - 8591/481-10-3000 4P+PE FLA 1 10h B n S00
- WebCode - 8591A
Mechanical Data
- Cable entry plug - M20
- Coding (clock hour position) - 10
- Degree of protection (IP) - IP66
- Degree of protection note - IP68 (2 m water column, 1 hour) according to IEC/EN 60529 (with protective caps closed and secured as well as properly fitted and secured components)
- Detailed number of poles - 4 P + PE
- Enclosure material - Nickel-plated brass
- Recommended colour ring coding - blue
- Weight - 0.174 kg
Mounting / Installation
- Connection type - 1.5 mm2 conductor 30 cm
154016
Multiple options for easy use, simple installation and maintenance
Safe and fast disconnection under load
4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations
Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
154019
Multiple options for easy use, simple installation and maintenance
Safe and fast disconnection under load
4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations
Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
Ambient Conditions
- Ambient temperature - -55 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -55 °C
Components
- Locking device present - No
- Protective cap available - No
Electrical Data
- Frequency Hz (for AC) - 50, 60
- Rated operational voltage AC - 230.00 - 250.00 V
Explosion Protection
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 03 ATEX 1097 X
- ATEX gas certificate - PTB 03 ATEX 1097 X
- Certificates - ATEX (PTB), IECEx (BKI)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T60 °C Db
- Dust explosion protection IECEx - Ex tb IIIC T60 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx BKI 07.0001 X
- IECEX gas certificate - IECEx BKI 07.0001X
General
- Functional Description - R. STAHL Series 8591/1 and 8591/4 4-pole, explosion-protected miniCLIX plug connectors disconnect non-instrinsically safe circuits up to 250 V/10 A and are used as a hot swap plug connection for signal and data cables. They are available in various versions and materials: Device plugs, flange sockets, plugs/couplers made of polyamide, nickel-plated brass or stainless steel. The cable can be connected using a crimp or spring clamp terminal. Preinstalled cables for device plugs and flange sockets enable fast and safe installation in the end devices.
- Highlights - Multiple options for easy use, simple installation and maintenance Safe and fast disconnection under load 4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
- Product Description - miniCLIX plug connector Device plug < 2 dm3
- Product Type - 8591/491-10-3000
- Title Product Variant Technical Data - 8591/491-10-3000 4P+PE DP< 1 10h B n S00
- WebCode - 8591A
Mechanical Data
- Cable entry plug - M20
- Coding (clock hour position) - 10
- Degree of protection (IP) - IP66
- Degree of protection note - IP68 (2 m water column, 1 hour) according to IEC/EN 60529 (with protective caps closed and secured as well as properly fitted and secured components)
- Detailed number of poles - 4 P + PE
- Enclosure material - Nickel-plated brass
- Recommended colour ring coding - blue
- Weight - 0.193 kg
Mounting / Installation
- Connection type - 1.5 mm2 conductor 30 cm
154022
Multiple options for easy use, simple installation and maintenance
Safe and fast disconnection under load
4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations
Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
Ambient Conditions
- Ambient temperature - -55 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -55 °C
Components
- Locking device present - No
- Protective cap available - No
Electrical Data
- Frequency Hz (for AC) - 50, 60
- Rated operational voltage AC - 230.00 - 250.00 V
Explosion Protection
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 03 ATEX 1097 X
- ATEX gas certificate - PTB 03 ATEX 1097 X
- Certificates - ATEX (PTB), IECEx (BKI)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T60 °C Db
- Dust explosion protection IECEx - Ex tb IIIC T60 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx BKI 07.0001 X
- IECEX gas certificate - IECEx BKI 07.0001X
General
- Functional Description - R. STAHL Series 8591/1 and 8591/4 4-pole, explosion-protected miniCLIX plug connectors disconnect non-instrinsically safe circuits up to 250 V/10 A and are used as a hot swap plug connection for signal and data cables. They are available in various versions and materials: Device plugs, flange sockets, plugs/couplers made of polyamide, nickel-plated brass or stainless steel. The cable can be connected using a crimp or spring clamp terminal. Preinstalled cables for device plugs and flange sockets enable fast and safe installation in the end devices.
- Highlights - Multiple options for easy use, simple installation and maintenance Safe and fast disconnection under load 4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
- Product Description - miniCLIX plug connector Device plug < 2 dm3
- Product Type - 8591/491-10-0000
- Title Product Variant Technical Data - 8591/491-10-0000 4P+PE DP< 1 10h P n S00
- WebCode - 8591A
Mechanical Data
- Cable entry plug - M20
- Coding (clock hour position) - 10
- Degree of protection (IP) - IP66
- Degree of protection note - IP68 (2 m water column, 1 hour) according to IEC/EN 60529 (with protective caps closed and secured as well as properly fitted and secured components)
- Detailed number of poles - 4 P + PE
- Enclosure material - Plastic
- Recommended colour ring coding - blue
- Weight - 0.193 kg
Mounting / Installation
- Connection type - 1.5 mm2 crimp
154025
Multiple options for easy use, simple installation and maintenance
Safe and fast disconnection under load
4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations
Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
Ambient Conditions
- Ambient temperature - -55 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -55 °C
Components
- Locking device present - No
- Protective cap available - No
Electrical Data
- Frequency Hz (for AC) - 50, 60
- Rated operational voltage AC - 230.00 - 250.00 V
Explosion Protection
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 03 ATEX 1097 X
- ATEX gas certificate - PTB 03 ATEX 1097 X
- Certificates - ATEX (PTB), IECEx (BKI)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T60 °C Db
- Dust explosion protection IECEx - Ex tb IIIC T60 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx BKI 07.0001 X
- IECEX gas certificate - IECEx BKI 07.0001X
General
- Functional Description - R. STAHL Series 8591/1 and 8591/4 4-pole, explosion-protected miniCLIX plug connectors disconnect non-instrinsically safe circuits up to 250 V/10 A and are used as a hot swap plug connection for signal and data cables. They are available in various versions and materials: Device plugs, flange sockets, plugs/couplers made of polyamide, nickel-plated brass or stainless steel. The cable can be connected using a crimp or spring clamp terminal. Preinstalled cables for device plugs and flange sockets enable fast and safe installation in the end devices.
- Highlights - Multiple options for easy use, simple installation and maintenance Safe and fast disconnection under load 4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
- Product Description - miniCLIX plug connector Coupling
- Product Type - 8591/131-06-3001
- Title Product Variant Technical Data - 8591/131-06-3001 2P+PE COU 1 6h B n S04
- WebCode - 8591A
Mechanical Data
- Cable entry max. - 7.50 mm
- Cable entry min. - 4.00 mm
- Clamping range - 4.00 … 7.50 mm
- Coding (clock hour position) - 6
- Degree of protection (IP) - IP66
- Degree of protection note - IP68 (2 m water column, 1 hour) according to IEC/EN 60529 (with protective caps closed and secured as well as properly fitted and secured components)
- Detailed number of poles - 2 P + PE
- Enclosure material - Nickel-plated brass
- Recommended colour ring coding - red
- Weight - 0.145 kg
Mounting / Installation
- Connection type - 1.5 mm2 crimp
154034
Multiple options for easy use, simple installation and maintenance
Safe and fast disconnection under load
4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations
Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
Ambient Conditions
- Ambient temperature - -55 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -55 °C
Components
- Locking device present - No
- Protective cap available - No
Electrical Data
- Frequency Hz (for AC) - 50, 60
- Rated operational voltage AC - 230.00 - 250.00 V
Explosion Protection
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 03 ATEX 1097 X
- ATEX gas certificate - PTB 03 ATEX 1097 X
- Certificates - ATEX (PTB), IECEx (BKI)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T60 °C Db
- Dust explosion protection IECEx - Ex tb IIIC T60 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx BKI 07.0001 X
- IECEX gas certificate - IECEx BKI 07.0001X
General
- Functional Description - R. STAHL Series 8591/1 and 8591/4 4-pole, explosion-protected miniCLIX plug connectors disconnect non-instrinsically safe circuits up to 250 V/10 A and are used as a hot swap plug connection for signal and data cables. They are available in various versions and materials: Device plugs, flange sockets, plugs/couplers made of polyamide, nickel-plated brass or stainless steel. The cable can be connected using a crimp or spring clamp terminal. Preinstalled cables for device plugs and flange sockets enable fast and safe installation in the end devices.
- Highlights - Multiple options for easy use, simple installation and maintenance Safe and fast disconnection under load 4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
- Product Description - miniCLIX plug connector Plug
- Product Type - 8591/171-06-3001
- Title Product Variant Technical Data - 8591/171-06-3001 2P+PE PLU 1 6h B n S04
- WebCode - 8591A
Mechanical Data
- Cable entry max. - 7.50 mm
- Cable entry min. - 4.00 mm
- Clamping range - 4.00 … 7.50 mm
- Coding (clock hour position) - 6
- Degree of protection (IP) - IP66
- Degree of protection note - IP68 (2 m water column, 1 hour) according to IEC/EN 60529 (with protective caps closed and secured as well as properly fitted and secured components)
- Detailed number of poles - 2 P + PE
- Enclosure material - Nickel-plated brass
- Recommended colour ring coding - red
- Weight - 0.168 kg
Mounting / Installation
- Connection type - 1.5 mm2 crimp
154040
Multiple options for easy use, simple installation and maintenance
Safe and fast disconnection under load
4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations
Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
Ambient Conditions
- Ambient temperature - -55 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -55 °C
Components
- Locking device present - No
- Protective cap available - No
Electrical Data
- Frequency Hz (for AC) - 50, 60
- Rated operational voltage AC - 230.00 - 250.00 V
Explosion Protection
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 03 ATEX 1097 X
- ATEX gas certificate - PTB 03 ATEX 1097 X
- Certificates - ATEX (PTB), IECEx (BKI)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T60 °C Db
- Dust explosion protection IECEx - Ex tb IIIC T60 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx BKI 07.0001 X
- IECEX gas certificate - IECEx BKI 07.0001X
General
- Functional Description - R. STAHL Series 8591/1 and 8591/4 4-pole, explosion-protected miniCLIX plug connectors disconnect non-instrinsically safe circuits up to 250 V/10 A and are used as a hot swap plug connection for signal and data cables. They are available in various versions and materials: Device plugs, flange sockets, plugs/couplers made of polyamide, nickel-plated brass or stainless steel. The cable can be connected using a crimp or spring clamp terminal. Preinstalled cables for device plugs and flange sockets enable fast and safe installation in the end devices.
- Highlights - Multiple options for easy use, simple installation and maintenance Safe and fast disconnection under load 4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
- Product Description - miniCLIX plug connector Flange socket
- Product Type - 8591/181-06-0000
- Title Product Variant Technical Data - 8591/181-06-0000 2P+PE FLA 1 6h P n S00
- WebCode - 8591A
Mechanical Data
- Cable entry plug - M20
- Coding (clock hour position) - 6
- Degree of protection (IP) - IP66
- Degree of protection note - IP68 (2 m water column, 1 hour) according to IEC/EN 60529 (with protective caps closed and secured as well as properly fitted and secured components)
- Detailed number of poles - 2 P + PE
- Enclosure material - Plastic
- Recommended colour ring coding - red
- Weight - 0.064 kg
Mounting / Installation
- Connection type - 1.5 mm2 crimp
154042
Multiple options for easy use, simple installation and maintenance
Safe and fast disconnection under load
4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations
Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
Ambient Conditions
- Ambient temperature - -55 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -55 °C
Components
- Locking device present - No
- Protective cap available - No
Electrical Data
- Frequency Hz (for AC) - 50, 60
- Rated operational voltage AC - 230.00 - 250.00 V
Explosion Protection
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 03 ATEX 1097 X
- ATEX gas certificate - PTB 03 ATEX 1097 X
- Certificates - ATEX (PTB), IECEx (BKI)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T60 °C Db
- Dust explosion protection IECEx - Ex tb IIIC T60 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx BKI 07.0001 X
- IECEX gas certificate - IECEx BKI 07.0001X
General
- Functional Description - R. STAHL Series 8591/1 and 8591/4 4-pole, explosion-protected miniCLIX plug connectors disconnect non-instrinsically safe circuits up to 250 V/10 A and are used as a hot swap plug connection for signal and data cables. They are available in various versions and materials: Device plugs, flange sockets, plugs/couplers made of polyamide, nickel-plated brass or stainless steel. The cable can be connected using a crimp or spring clamp terminal. Preinstalled cables for device plugs and flange sockets enable fast and safe installation in the end devices.
- Highlights - Multiple options for easy use, simple installation and maintenance Safe and fast disconnection under load 4/4+1-pole, up to 10 A, high transfer rate (100 MBit/s) ideal for fieldbus installations Suitable for harsh industry environments, IP66/IP68, for Zones 1, 2, 21 and 22
- Product Description - miniCLIX plug connector Flange socket
- Product Type - 8591/181-06-3000
- Title Product Variant Technical Data - 8591/181-06-3000 2P+PE FLA 1 6h B n S00
- WebCode - 8591A
Mechanical Data
- Cable entry plug - M20
- Coding (clock hour position) - 6
- Degree of protection (IP) - IP66
- Degree of protection note - IP68 (2 m water column, 1 hour) according to IEC/EN 60529 (with protective caps closed and secured as well as properly fitted and secured components)
- Detailed number of poles - 2 P + PE
- Enclosure material - Nickel-plated brass
- Recommended colour ring coding - red
- Weight - 0.148 kg
Mounting / Installation
- Connection type - 1.5 mm2 conductor 30 cm
1 - 12 of 29 Part Numbers