Yodify Product Library
Add the RY2 Relay Input Card to your store or catalog  
Book Your Demo and See How
or create your store

This unit receives wet contact signal from the field and outputs 2 contact signals (1 for use of DCS status card input and the other is re-transmit contact signal) isolated electrically from the field. One unit stores 2 channels.
Features
  • Output contact consists of 2 contacts; 1 for DCS contact and the other for re-transmit contact (transfer contact) of current capacity 1A
  • The circuits between wet contact input signal and output signal is isolated electrically, isolated by means of photo-isolator
  • Furnished with test switch convenient for debugging of DCS or checking operation and LED for status display

1 - 6 of 6 Part Numbers
RY2-10
RY2-10
  • Input Signal - 100 Vac Wet Voltage Contacts (85-132 Vac)
  • Test Switch - No Test Switch
RY2-11
RY2-11
  • Input Signal - 100 Vac Wet Voltage Contacts (85-132 Vac)
  • Test Switch - With Test Switch (AUT-OFF-ON)
RY2-20
RY2-20
  • Input Signal - 200 Vac Wet Voltage Contacts (170-264 Vac)
  • Test Switch - No Test Switch
RY2-21
RY2-21
  • Input Signal - 200 Vac Wet Voltage Contacts (170-264 Vac)
  • Test Switch - With Test Switch (AUT-OFF-ON)
RY2-30
RY2-30
  • Input Signal - 24 Vdc Wet Voltage Contacts (24 Vdc ± 10%)
  • Test Switch - No Test Switch
RY2-31
RY2-31
  • Input Signal - 24 Vdc Wet Voltage Contacts (24 Vdc ± 10%)
  • Test Switch - With Test Switch (AUT-OFF-ON)
1 - 6 of 6 Part Numbers

Specifications

Alarm

  • Output of Dry Contact is Generated from Alarm Terminals of Nest when Power Fuse is OFF

Ambient Temperature Range

  • 0° to 50° C (32° to 122° F)

Dissipation

  • 50 mA at 24 Vdc - Current Dissipation

Electrical Connectors

  • M3.5 Screw Terminal - Output-2 (Re-Transmit Output) & Input

Electrical Rating

  • 0.2 A at 125 Vac, 0.5 A at Vdc - Output-2 Inductance Load
  • 0.2 A at 30 Vdc - Output-1 (Both Resistance & Inductance Loads)
  • 0.4 A at 125 Vac, 1 A at 30 Vdc - Output-2 Resistance Load

Humidity

  • 5 to 90 % RH - Normal Operating Conditions
  • 5 to 95 % RH, Non-Condensing - Operating Limit/Storage Conditions

Indication

  • LED - Light on (Green) when Relay Magnetized

Insulation Resistance

  • 100 MΩ at 500 Vdc between Input, Output-1, Output-2, Alarm Contact Output

Mounting

  • Nest-Mounting

Operating Temperature

  • -10° to 60° C (14° to 140° F)

Operating Voltages

  • 125 Vdc - Max.
  • 250 Vac - Max.

Output Format

  • Relay Output

Power

  • 0.5 A Alarm Fuse

Screw Material

  • Nickel-Plated-Iron

Storage Temperature

  • -40° to 70° C (-40° to 158° F)

Supply Voltage

  • 1,500 Vac/minute between Input, Output-2, Output-1, Power Supply or Alarm Contacts - Withstanding Voltage
  • 24 Vdc ± 10 % (Ripple Content Below 5 % Peak-to-Peak)
  • 500 Vac/minute between Output, Alarm Contact, Power Supply - Withstanding Voltage

Torque

  • Below 6.94 in/lb - Fastening Torque

Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team
show more