Yodify Product Library
Instantly add the SEM210 Temperature Transmitter and 50,000+ more product series to your store or catalog  
Book Your Demo and See How
or create your store

SEM210 Temperature Transmitter

Brand: Status Instruments

The SEM210 is a second generation ‘Smart’ Universal input in-head temperature transmitter that accepts RTD, Thermocouple, Potentiometer, Slidewire transducer or Millivolt signal and converts the output to the industry standard 4-20 mA transmission signal. 

The sensor type and range are easily programmed using a PC and our free configuration software download from our web site. 

Connection from the PC USB port and the SEM210 is made using the USB port powered configurator. 

This simplifies connection and allows for re-programming or interrogation of the SEM210 while it is installed in the loop or not. 

Sensors can be changed without the need for re-calibration.
Features
  • Dual RTD, Thermocouple, Potentiometer and mV Inputs
  • UKEX, ATEX, IECEx Approved Versions For Hazardous Areas
  • Isolated Input to Output 4kV DC Flash Tested
  • Maths Functions Between Inputs
  • SIL 2 Hardware Safety Integrity

1 - 2 of 2 Part Numbers
SEM210
SEM210
  • Transmitter - Standard
SEM210X
SEM210X
  • Transmitter - IS Version
1 - 2 of 2 Part Numbers

Specifications

Accuracy

  • ± 5 µA
  • Basic Measurement Accuracy: ± 0.01 % of Full Range Input (FRI) ± 0.05 % of Reading
  • Basic Measurement Accuracy: ± 0.04 % of FRI ± 0.04 % of Reading or 0.5° C (0.9° F), whichever is greater
  • Basic Measurement Accuracy: ± 10 µV ± 0.07 % of Reading
  • Basic Measurement Accuracy: 0.1 %
  • Cold Junction Error: ± 0.5° C (± 0.9° F)

Approvals & Certifications

  • ATEX: II 1 G EEx ia IIC T4-T6
  • EMC: BS EN 61326
  • FM: IS/I/1/ABCD/T4

Cable Length

  • 3,281 feet (1,000 metres) - Max.

Communication

  • PC Interface: USB Connector

Control Functions Characteristics

  • Linear

Current

  • Excitation Current: 300-500 µA

Enclosure, Body Material

  • Noryl

Humidity

  • Ambient Humidity: 10 to 90 % Relative Humidity, Non-Condensing
  • I.S Version: 0 to 100 % Relative Humidity

Input

  • 3-Wire Potentiometer
  • Voltage Source

Input Impedance

  • 10 megaohms

Isolation

  • Input/Output Breakdown Isolation: 500 Vac RMS

Linearization

  • RTD: BS 1904
  • RTD: BS EN 60751
  • RTD: DIN 43760
  • RTD: JISC 1604
  • Thermocouple: BS 4937
  • Thermocouple: IEC 584-3

Operating Temperature

  • Ambient Operating Range & Cold Junction Range: -40° to 85° C (-40° to 185° F)

Output

  • 20.2 mA
  • 23 mA - Max.

Output Load

  • 700 ohms at 24 V, Max.

Power Supply Effect

  • Voltage Effect: 0.2 μA/V

Range

  • -10 to 75 mV

Resistance

  • 10 to 390 ohms
  • Maximum

Response Time

  • Filter OFF: < 1 second

RTD Type

  • Pt100

Sensor Protection

  • Burn-Out

Sensor, Probe Type

  • E Thermocouple
  • J Thermocouple
  • K Thermocouple
  • L Thermocouple
  • N Thermocouple
  • RTD
  • R Thermocouple
  • S Thermocouple
  • T Thermocouple

Span - Minimum

  • 25° to 100° C (77° to 212° F)
  • 5 mV
  • 5%

Stability

  • 0.1 % of Full Range Input or 0.1° C (0.18° F)/Year

Storage Temperature

  • Ambient Storage Temperature: -50° to 100° C (-58° to 212° F)

Supply Voltage

  • 10-35 V

Temperature Effect

  • Cold Junction Tracking: 0.05° C/°C
  • Lead Resistance Effect: 0.002° C/ohm

Temperature Range

  • Sensor: -200° to 1,760° C (-328° to 3,200° F)
  • Sensor: -200° to 850° C (-328° to 1,562° F)

Thermal Drift

  • Span: 0.01 %/°C
  • Zero: 0.008° C/°C
  • Zero: 0.1 µV/°C

Update Time

  • 250 milliseconds, Max.
  • Warm-Up: 120 seconds to Full Accuracy
Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team
show more