Yodify Product Library
Add the NAMUR Digital Input Output Module for Ex n Zone 2 Series 9471/35 to your store or catalog  
Book Your Demo and See How
or create your store

NAMUR Digital Input Output Module for Ex n Zone 2 Series 9471/35

Brand: R. STAHL AG

The 9471/35 series digital input/output module for Zone 2 has 16 channels, which can be used in pairs for operation as inputs for contacts, NAMUR proximity sensors (EN 60947-5-6) and PNP proximity switches or as outputs for indicator lamps and low-power solenoid valves.

Eight inputs can be used for frequencies of up to 20 kHz, and four can be used for detecting the direction of rotation. All inputs/outputs are short-circuit proof and galvanically separated from the system.
Features
  • Sixteen channels can be used in pairs as inputs or outputs
  • Ex nA inputs/outputs with line fault monitoring and LED error and status indication for each channel
  • Module in Zone 2 can be hot swapped

1 - 1 of 1 Part Numbers
230225
230225
R. STAHL Remote I/O IS1+ Digital Input-Output Module for Zone 2 Ex N
Sixteen channels can be used in pairs as inputs or outputs

Ex nA inputs/outputs with line fault monitoring and LED error and status indication for each channel

module in Zone 2 can be hot swapped

Ambient Conditions

  • Ambient temperature - -40°C ... +75°C
  • Ambient temperature max. - +75°C
  • Ambient temperature min. - -40°C
  • Max. operating height - < 2000 m
  • Max. relative humidity - 95% (without condensation)
  • Note - (observe operating instructions)
  • Storage temperature - -40°C ... +80°C
  • storage temperature °C - -40 - 80 °C
  • Storage temperature max. - +80°C
  • Storage temperature min. - -40°C

Auxiliary power

  • Auxiliary power Version - Intrin. safe Ex ia via BusRail
  • Behaviour in case undervoltage - all outputs "OFF"
  • Current consumption - 90 mA
  • Max. power consumption - 2.20 W
  • Power consumption max. - 2.20 W
  • Power dissipation max. - 0.7 W
  • Power supply connection - BusRail types 9494

Camera data

  • Resolution - 16 Bit / 32 Bit

Device Specific Data

  • Counter control - Stop Run Reset
  • Counting event - positive slope negative slope
  • In. behaviour in case of error - replacement value "1" hold (initial value 1) hold (initial value 0) Replacement value "0"
  • Inverting input/output - normal inverted
  • LED channel error - LED for each channel, red
  • LED channel status - LED for each channel, yellow
  • LED group error - "ERR" LED, red
  • LED operating state - "RUN" LED, green
  • LEDmodule requires maintenance - "M/S" LED, blue
  • Line fault monitoring - OFF ON
  • Module diagnostics message - OFF ON
  • Operat.mode counter/frequency - up/down counter 32 bit up/down counter 16 bit Counter 16 bit 1 Hz ... 3 kHz 1 Hz ... 20 kHz with direction 1 Hz ... 20 kHz 0.1 ... 600 Hz
  • Pulse extension/freq.filter - 2.4 s / large 0.6 s / small 1.2 s / medium 0 s / off
  • Retrievable parameters - Serial number Software revision Type Manufacturer Hardware revision
  • Signal settings note - Settings are made for channel pairs
  • Signal status bit - "1" = Output is supplied "0" = Output high-impedance
  • Signal type - NAMUR proximity switch / contact; 3-conductor PNP proximity switch; output

Electrical Data

  • Number of channels - 16 Ex ec/nA inputs/outputs Adjustable parameters in pairs

Explosion Protection

  • Ambient temperature °C - -40 - 75 °C
  • Application range (zones) - 2
  • ATEX gas certificate - DEKRA 16 ATEX 0016 X
  • Certificates - ATEX (DEK), Canada (FM), EAC (Sertium), IECEx (DEK), India (PESO), Korea (KTL), USA (FM)
  • Ex interface zone - 2
  • Gas explosion protection ATEX - II 3 (1) G Ex ec/nA ic [ia Ga] IIC T4 Gc
  • Gas explosion protection IECEx - Ex ec/nA ic [ia Ga] IIC T4 Gc
  • IECEX gas certificate - IECEx DEK 16.0010X
  • Installation - Zone 2, 22 and safe area

Galvanic isolation

  • Aux. power/system components - ≥ 1800 V AC
  • I/O channels / ground (PA) - ≥ 1800 V AC
  • I/O channels/system components - ≥ 1800 V AC
  • Test volt. for gal. separation - acc. to standard EN 60079-11

General

  • Functional Description - The 9471/35 series digital input/output module for Zone 2 has 16 channels, which can be used in pairs for operation as inputs for contacts, NAMUR proximity sensors (EN 60947-5-6) and PNP proximity switches or as outputs for indicator lamps and low-power solenoid valves. Eight inputs can be used for frequencies of up to 20 kHz, and four can be used for detecting the direction of rotation. All inputs/outputs are short-circuit proof and galvanically separated from the system.
  • Highlights - Sixteen channels can be used in pairs as inputs or outputs Ex nA inputs/outputs with line fault monitoring and LED error and status indication for each channel module in Zone 2 can be hot swapped
  • Product Description - Remote I/O IS1+ Digital input-output module for Zone 2 Ex n
  • Product Type - 9471/35-16-11
  • Title Product Variant Technical Data - 9471/35-16-11 DIOM 16 Z2 Ex n LED
  • WebCode - 9471B

Input

  • Counting range - 0 ... 65535 as UINT16
  • Function - frequency with direction Up/down counter
  • hysteresis - ≥ 0,2 mA
  • internal resistance - 1
  • Max. number counter inputs - 8 (channel 8 ... 15)
  • Max. number frequency inputs - 8 (channel 8 ... 15)
  • Max. number of 3-wire PNP inputs - 16
  • Max. supply voltage - 24 V
  • Min. pulse width - 25 Microsecond
  • Number of inputs - 16 (NAMUR)
  • operating point - 1.65 mA
  • Signal input - EN 60947 (NAMUR)
  • Supply voltage input - 8 V
  • Supply voltage note - ± 5 %

Mechanical Data

  • Degree of protection IP (IEC 60529) - IP 20
  • Fire resistance (UL 94) - V2
  • Height - 67.000 mm
  • Length - 128.000 mm
  • Module enclosure - Polyamide 6GF
  • Pollutant class - Corresponds to G3
  • Weight - 0.275 kg
  • Width - 96.500 mm

Mounting / Installation

  • Mounting position - horizontal vertical
  • Mounting type - on DIN rail NS 35/15
  • Mounting type 2 - (DIN EN 60715)

Output

  • Application - low-power solenoid valves
  • Internal resistance outputs - 1.0
  • Max. number of outputs - 16
  • Open-circuit voltage U a - 8.20 V
  • Output current max. - 8.20 mA
  • Output rated operation - 6 V / 2 mA
1 - 1 of 1 Part Numbers
Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team
show more