Yodify Product Library
Add the NAMUR Digital Input Output Module for Ex n Zone 2 Series 9471/35 to your store or catalog
Book Your Demo and See How
or create your store
NAMUR Digital Input Output Module for Ex n Zone 2 Series 9471/35
Brand: R. STAHL AGThe 9471/35 series digital input/output module for Zone 2 has 16 channels, which can be used in pairs for operation as inputs for contacts, NAMUR proximity sensors (EN 60947-5-6) and PNP proximity switches or as outputs for indicator lamps and low-power solenoid valves.
Eight inputs can be used for frequencies of up to 20 kHz, and four can be used for detecting the direction of rotation. All inputs/outputs are short-circuit proof and galvanically separated from the system.
Features- Sixteen channels can be used in pairs as inputs or outputs
- Ex nA inputs/outputs with line fault monitoring and LED error and status indication for each channel
- Module in Zone 2 can be hot swapped
1 - 1 of 1 Part Numbers
230225
Sixteen channels can be used in pairs as inputs or outputs
Ex nA inputs/outputs with line fault monitoring and LED error and status indication for each channel
module in Zone 2 can be hot swapped
Ambient Conditions
- Ambient temperature - -40°C ... +75°C
- Ambient temperature max. - +75°C
- Ambient temperature min. - -40°C
- Max. operating height - < 2000 m
- Max. relative humidity - 95% (without condensation)
- Note - (observe operating instructions)
- Storage temperature - -40°C ... +80°C
- storage temperature °C - -40 - 80 °C
- Storage temperature max. - +80°C
- Storage temperature min. - -40°C
Auxiliary power
- Auxiliary power Version - Intrin. safe Ex ia via BusRail
- Behaviour in case undervoltage - all outputs "OFF"
- Current consumption - 90 mA
- Max. power consumption - 2.20 W
- Power consumption max. - 2.20 W
- Power dissipation max. - 0.7 W
- Power supply connection - BusRail types 9494
Camera data
- Resolution - 16 Bit / 32 Bit
Device Specific Data
- Counter control - Stop Run Reset
- Counting event - positive slope negative slope
- In. behaviour in case of error - replacement value "1" hold (initial value 1) hold (initial value 0) Replacement value "0"
- Inverting input/output - normal inverted
- LED channel error - LED for each channel, red
- LED channel status - LED for each channel, yellow
- LED group error - "ERR" LED, red
- LED operating state - "RUN" LED, green
- LEDmodule requires maintenance - "M/S" LED, blue
- Line fault monitoring - OFF ON
- Module diagnostics message - OFF ON
- Operat.mode counter/frequency - up/down counter 32 bit up/down counter 16 bit Counter 16 bit 1 Hz ... 3 kHz 1 Hz ... 20 kHz with direction 1 Hz ... 20 kHz 0.1 ... 600 Hz
- Pulse extension/freq.filter - 2.4 s / large 0.6 s / small 1.2 s / medium 0 s / off
- Retrievable parameters - Serial number Software revision Type Manufacturer Hardware revision
- Signal settings note - Settings are made for channel pairs
- Signal status bit - "1" = Output is supplied "0" = Output high-impedance
- Signal type - NAMUR proximity switch / contact; 3-conductor PNP proximity switch; output
Electrical Data
- Number of channels - 16 Ex ec/nA inputs/outputs Adjustable parameters in pairs
Explosion Protection
- Ambient temperature °C - -40 - 75 °C
- Application range (zones) - 2
- ATEX gas certificate - DEKRA 16 ATEX 0016 X
- Certificates - ATEX (DEK), Canada (FM), EAC (Sertium), IECEx (DEK), India (PESO), Korea (KTL), USA (FM)
- Ex interface zone - 2
- Gas explosion protection ATEX - II 3 (1) G Ex ec/nA ic [ia Ga] IIC T4 Gc
- Gas explosion protection IECEx - Ex ec/nA ic [ia Ga] IIC T4 Gc
- IECEX gas certificate - IECEx DEK 16.0010X
- Installation - Zone 2, 22 and safe area
Galvanic isolation
- Aux. power/system components - ≥ 1800 V AC
- I/O channels / ground (PA) - ≥ 1800 V AC
- I/O channels/system components - ≥ 1800 V AC
- Test volt. for gal. separation - acc. to standard EN 60079-11
General
- Functional Description - The 9471/35 series digital input/output module for Zone 2 has 16 channels, which can be used in pairs for operation as inputs for contacts, NAMUR proximity sensors (EN 60947-5-6) and PNP proximity switches or as outputs for indicator lamps and low-power solenoid valves. Eight inputs can be used for frequencies of up to 20 kHz, and four can be used for detecting the direction of rotation. All inputs/outputs are short-circuit proof and galvanically separated from the system.
- Highlights - Sixteen channels can be used in pairs as inputs or outputs Ex nA inputs/outputs with line fault monitoring and LED error and status indication for each channel module in Zone 2 can be hot swapped
- Product Description - Remote I/O IS1+ Digital input-output module for Zone 2 Ex n
- Product Type - 9471/35-16-11
- Title Product Variant Technical Data - 9471/35-16-11 DIOM 16 Z2 Ex n LED
- WebCode - 9471B
Input
- Counting range - 0 ... 65535 as UINT16
- Function - frequency with direction Up/down counter
- hysteresis - ≥ 0,2 mA
- internal resistance - 1
- Max. number counter inputs - 8 (channel 8 ... 15)
- Max. number frequency inputs - 8 (channel 8 ... 15)
- Max. number of 3-wire PNP inputs - 16
- Max. supply voltage - 24 V
- Min. pulse width - 25 Microsecond
- Number of inputs - 16 (NAMUR)
- operating point - 1.65 mA
- Signal input - EN 60947 (NAMUR)
- Supply voltage input - 8 V
- Supply voltage note - ± 5 %
Mechanical Data
- Degree of protection IP (IEC 60529) - IP 20
- Fire resistance (UL 94) - V2
- Height - 67.000 mm
- Length - 128.000 mm
- Module enclosure - Polyamide 6GF
- Pollutant class - Corresponds to G3
- Weight - 0.275 kg
- Width - 96.500 mm
Mounting / Installation
- Mounting position - horizontal vertical
- Mounting type - on DIN rail NS 35/15
- Mounting type 2 - (DIN EN 60715)
Output
- Application - low-power solenoid valves
- Internal resistance outputs - 1.0
- Max. number of outputs - 16
- Open-circuit voltage U a - 8.20 V
- Output current max. - 8.20 mA
- Output rated operation - 6 V / 2 mA
1 - 1 of 1 Part Numbers