Binary Output Series 9275

Brand: R. STAHL AG

Series 9275 digital outputs issue signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices feature three-way galvanic separation.
Features
  • Space savings due to a slim design – 12.5 mm wide
  • Can be used for functional safety levels up to SIL 3 (IEC/EN 61508)
  • Offers line fault detection with signalization

1 - 2 of 2 Part Numbers
261434
261434
R. STAHL Binary Output Ex I Field Circuit
Space savings due to a slim design – 12.5 mm wide



Can be used for functional safety levels up to SIL 3 (IEC/EN 61508)



Offers line fault detection with signalization

Ambient Conditions

  • Ambient temperature - -20 °C ... +60 °C
  • Ambient temperature max. - +60 °C
  • Ambient temperature min. - -20 °C
  • Electromagnetic compatibility - EN 61326-1 Use in industrial environment Immunity according to EN 61000-6-2 Interference emission to EN 61000-6-4
  • Relative humidity max. - 10 to 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - 24 V DC
  • Auxiliary power voltage range - 19,2 … 30 V
  • Nominal current - 50.00 mA
  • Operation indication - Green "PWR" LED
  • Polarity reversal protection - yes
  • Power consumption - 1.20 W
  • Power dissipation max. - 0.80 W
  • Undervoltage monitoring - No

Electrical Data

  • Number of channels - 1

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - IBExU 17 ATEX 1152 X
  • ATEX gas certificate - IBExU 17 ATEX 1152 X
  • Certificates - ATEX (IBE), Canada / USA (UL), IECEx (IBE), SIL (BVS)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
  • Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx IBE 17.0044X
  • IECEX gas certificate - IECEx IBE 17.0044X
  • Installation in Division NEC 500 - (Class I, II, III) 2

Galvanic isolation

  • Galvanic isolation Ex i output to auxiliary power - 375 V AC peak value
  • Galvanic isolation Ex i output to fault message contact - 375 V AC peak value
  • Galvanic isolation Ex i output to input - 375 V AC peak value
  • Galvanic isolation fault message contact to auxiliary power - 300 Veff
  • Galvanic isolation fault message contact to input - 300 Veff
  • Galvanic isolation input to auxiliary power - 300 Veff
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 61010 / EN 50178

General

  • Functional Description - Series 9275 digital outputs issue signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices feature three-way galvanic separation.
  • Highlights - Space savings due to a slim design – 12.5 mm wide Can be used for functional safety levels up to SIL 3 (IEC/EN 61508) Offers line fault detection with signalization
  • Product Description - Binary output Ex i field circuit
  • Product Type - 9275/10-21-25-11s
  • Title Product Variant Technical Data - 9275/10-21-25-11s
  • WebCode - 9275A

Input

  • Control current - < 12 mA
  • Input voltage for OFF - 0 - 5 V
  • Input voltage for ON - 15.0 - 30.0 V

Mechanical Data

  • Connection cross-section - 0.2-2.5 mm² rigid 0.25-2.5 mm² flexible core end sleeve
  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 12.50 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.160 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 2.5 mm²
  • Conduct cross-section flexible max. - 0.2 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Screw terminal
  • Mounting position - vertical horizontal
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Error detection wire breakage - > 10 kΩ
  • Indication of line fault - "LF" LED, red
  • LFD relay - Yes
  • Max. output current I a max - 25.10 mA
  • Output internal resistiance R i - 641.00 Ω
  • Output open circuit voltage U a - 21,1 V
  • Response time output - < 30 ms
  • Short circuit error detection - < 50 Ω
  • Switch user adjustment line fault - activated / deactivated
  • Switching capacity fault message contact - 30 V / 50 mA
  • Switching delay ON/OFF - < 30 ms
  • Switching state indication - Yellow LED "STAT"
  • test current - < 0.6 mA

Safety Data

  • Internal capacitance C i - 11 nF
  • Internal inductance L i - negligible
  • Max. current I o (Ex ia) - 37.40 mA
  • Max. permissible external capacitance C o for IIA - 3.330 μF
  • Max. permissible external capacitance C o for IIB - 0.910 μF
  • Max. permissible external capacitance C o for IIC - 0.110 μF
  • Max. permissible external inductance L o for IIA - 200.00 mH
  • Max. permissible external inductance L o for IIB - 100.000 mH
  • Max. permissible external inductance L o for IIC - 22.000 mH
  • Max. Power P o - 224.000 mW
  • Max. Voltage U o - 23.98 V
  • Safety-related maximum voltage - 253 V AC
261435
261435
R. STAHL Binary Output Ex I Field Circuit
Space savings due to a slim design – 12.5 mm wide



Can be used for functional safety levels up to SIL 3 (IEC/EN 61508)



Offers line fault detection with signalization

Ambient Conditions

  • Ambient temperature - -20 °C ... +60 °C
  • Ambient temperature max. - +60 °C
  • Ambient temperature min. - -20 °C
  • Electromagnetic compatibility - EN 61326-1 Use in industrial environment Immunity according to EN 61000-6-2 Interference emission to EN 61000-6-4
  • Relative humidity max. - 10 to 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - 24 V DC
  • Auxiliary power voltage range - 19,2 … 30 V
  • Nominal current - 90.00 mA
  • Operation indication - Green "PWR" LED
  • Polarity reversal protection - yes
  • Power consumption - 2.16 W
  • Power dissipation max. - 1.62 W
  • Undervoltage monitoring - No

Electrical Data

  • Number of channels - 1

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - IBExU 17 ATEX 1152 X
  • ATEX gas certificate - IBExU 17 ATEX 1152 X
  • Certificates - ATEX (IBE), Canada / USA (UL), IECEx (IBE), SIL (BVS)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
  • Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx IBE 17.0044X
  • IECEX gas certificate - IECEx IBE 17.0044X
  • Installation in Division NEC 500 - (Class I, II, III) 2

Galvanic isolation

  • Galvanic isolation Ex i output to auxiliary power - 375 V AC peak value
  • Galvanic isolation Ex i output to fault message contact - 375 V AC peak value
  • Galvanic isolation Ex i output to input - 375 V AC peak value
  • Galvanic isolation fault message contact to auxiliary power - 300 Veff
  • Galvanic isolation fault message contact to input - 300 Veff
  • Galvanic isolation input to auxiliary power - 300 Veff
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 61010 / EN 50178

General

  • Functional Description - Series 9275 digital outputs issue signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices feature three-way galvanic separation.
  • Highlights - Space savings due to a slim design – 12.5 mm wide Can be used for functional safety levels up to SIL 3 (IEC/EN 61508) Offers line fault detection with signalization
  • Product Description - Binary output Ex i field circuit
  • Product Type - 9275/10-24-48-11s
  • Title Product Variant Technical Data - 9275/10-24-48-11s
  • WebCode - 9275A

Input

  • Control current - < 12 mA
  • Input voltage for OFF - 0 - 5 V
  • Input voltage for ON - 15.0 - 30.0 V

Mechanical Data

  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 12.50 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.160 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 2.5 mm²
  • Conduct cross-section flexible max. - 0.2 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Screw terminal
  • Mounting position - vertical horizontal
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Error detection wire breakage - > 10 kΩ
  • Indication of line fault - "LF" LED, red
  • LFD relay - Yes
  • Max. output current I a max - 48.00 mA
  • Output internal resistiance R i - 297.00 Ω
  • Output open circuit voltage U a - 24,3 V
  • Response time output - < 30 ms
  • Short circuit error detection - < 50 Ω
  • Switch user adjustment line fault - activated / deactivated
  • Switching capacity fault message contact - 30 V / 50 mA
  • Switching delay ON/OFF - < 30 ms
  • Switching state indication - Yellow LED "STAT"
  • test current - < 0.6 mA

Safety Data

  • Internal capacitance C i - 11 nF
  • Internal inductance L i - negligible
  • Max. current I o (Ex ia) - 91.11 mA
  • Max. permissible external capacitance C o for IIA - 2.290 μF
  • Max. permissible external capacitance C o for IIB - 0.686 μF
  • Max. permissible external capacitance C o for IIC - 0.078 μF
  • Max. permissible external inductance L o for IIA - 32.00 mH
  • Max. permissible external inductance L o for IIB - 15.000 mH
  • Max. permissible external inductance L o for IIC - 3.500 mH
  • Max. Power P o - 616.000 mW
  • Max. Voltage U o - 27.06 V
  • Safety-related maximum voltage - 253 V AC
1 - 2 of 2 Part Numbers