Yodify Product Library
Add the L4006E1067/U Aquastat, Breaks on Rise, 130-270F Range, 250F Factory Stop, Less Well to your store or catalog  
Book Your Demo and See How
or create your store

L4006E1067/U Aquastat, Breaks on Rise, 130-270F Range, 250F Factory Stop, Less Well

Brand: Resideo Technologies Inc

Aquastat® Controllers from Resideo are immersion type devices for limiting or regulating the temperature of liquids in boilers, storage tanks, and other applications where temperature control is required.

L4006 are used in applications that utilize the existing wells
Features
  • Totally Enclosed Micro Switch™ Snap-acting Switches Operate on Temperature Rise to Setpoint.
  • Visible Control Point Scale and External Adjustment Screw Permit Easy Setting.
  • Horizontal or Vertical Insertion of the Sensing Element.
  • Direct or Well Immersion of the Sensing Element.
  • Models Available for Strap-on Mounting.
  • Remote Bulb Model May be Used to Sense Air Temperature in Ducts and in Outside Air Sensing Applications.
  • Models Include Heat-conductive Compound.
  • Select Models Have Wells.
  • UL Limit Rated Device.

1 - 1 of 1 Part Numbers
L4006E1067/U
L4006E1067/U
Aquastat, Breaks on Rise, 130-270F Range, 250F Factory Stop, Less Well
1 - 1 of 1 Part Numbers

Specifications

Hazmat Information

  • UN 1294, TOLUENE, 3, II

Dimensions

  • Case: 5-5/8 in. high x 2 in. wide x 2-1/8 in. deep
  • Case: 143 mm high x 51 mm wide x 54 mm deep

Temperature Range

  • Maximum 150° F
  • Maximum 66° C

Includes

  • Heat-conductive compound; Stop factory-set at 250 F (121 C); Well adapter

Mounting

  • Horizontal or Vertical

Electrical Ratings

  • Millivolt - 0.25 A @ 0.25 to 12 Vdc; At Full Load - 8A @ 120 Vac: 5.1 A @ 240 Vac; At Locked Rotor - 48 A @ 120 Vac: 30.6A @ 240 Vac

Approvals, Underwriters Laboratories Inc.

  • UL Component Recognized: File MP466, Vol. 6, Sec.1, Guide No. MBPR2

Approvals, Canadian Standards Association

  • Certified: File LR95329-1

Approvals, American Gas Association

  • AGA Certified

Tradeline Value

  • Tradeline

Operating Temperature Range

  • 130° to 270° F
  • 54° to 132° C

Bulb Size

  • 10 mm x 73 mm copper
  • 3/8 in. x 2-7/8 in. copper

Differential Temperature

  • Manual Reset

Switching Action

  • SPST, contacts break on temperature rise.

Capillary Length

  • 3 in.
  • 76 mm

  • High Limit; Manual Reset
Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team