Yodify Product Library
Instantly add the PHU Paperless Recorder and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
PHU Paperless Recorder
Brand: Fuji Electric Co, LtdThis is a paperless recorder that displays measured data on the LCD in real time and stores data in CompactFlash.
The type of input such as thermocouple, resistance bulb, D.C. voltage (current), etc. can be arbitrarily set to 36 channels at the maximum.
The data stored in CompactFlash can be regenerated on the screen, and the use of supplied support software allows the data to be regenerated on a PC screen.
The data recorded in ASCII format can be directly read in a spreadsheet such as Excel, which facilitates the processing on a PC.
Features- Large capacity storage by CompactFlash
- Quick search and display of past data
- Various display capability
- PC support software supplied as standard
- 36-point recording
- LCD extinguishing function
- Ethernet function
Specifications
Brand
Accuracy
- Clock: ± 50 ppm
- Digital Indication (K Thermocouple): ± (0.3 % + 1-Digit)
- Digital Indication (Ni100, Cu50 Resistance Bulb): ± (0.5 % + 1-Digit)
- Digital Indication (R Thermocouple, JPt100, Pt100, Pt50 Resistance Bulb, DC Voltage): ± (0.15 % + 1-Digit)
Ambient Temperature Range
- With Ethernet Function: 0° to 40° C (32° to 104° F)
- Without Ethernet Function: 0° to 50° C (32° to 122° F)
Approvals & Certifications
- EMC EN 61326
- IEC 61010-1
Burn-Out
- Approximately 0.2 µA
Communication
- Ethernet
- FTP
- HTTP
- Modbus TCP/IP
- SMTP (E-mail Client)
Consumption
- Power: 65 VA at 100 Vac
- Power: 80 VA at 240 Vac
Electrical Connectors
- External Terminal Board (Input Terminal): M3 Screw Terminal
- External Terminal Board (Power Terminal): M4 Screw Terminal
Electrical Rating
- Alarm Relay: 3 A at 240 Vac (Resistive Load)
- Alarm Relay: 3 A at 30 Vdc - Resistive Load
- Alarm: 0.1 A at 30 Vdc - Resistive Load
Enclosure, Body Material
- Stainless Steel
Frequency
- Effect of Power Supply Fluctuation Conditions: 47 to 63 Hz (100 Vac) [Reading Change: ± (0.2 % + 1-Digit) or Lower]
- Power Supply: 50/60 Hz ± 2 % (Both Employable & Sharing)
Function
- Burn-Out
- Computation
- F Value Calculation
- Input Filter
- Scaling
- Square Rooter
- Subtraction
- Totalization
Humidity
- Ambient: 20 to 80 % Relative Humidity
- Transportation/Storage Conditions: 5 to 90 % Relative Humidity
Hysteresis
- Alarm Function: 0 to 100 %
Indication
- 12” TFT Color LCD (800 x 600 Dots) with Backlight, No Contrast Adjustment
Input
- 0-5 Vdc
- DC Voltage: 0-500 mV
- Thermocouple, Resistance Bulb, DC Voltage: ± 10 Vdc (Continuous) - Max.
Input Impedance
- Thermocouple, DC Voltage: 1 Megaohm
Insulation Resistance
- 100 megaohms (When Measured between Each Terminal & Ground by Using A 500 Vdc Megger)
Materials of Construction
- Bezel: PC-ABS
Measuring Error
- K, E, J, T, N, L, U, PN Thermocouple: ± 0.5° C (0.9° F)
- R, S, B, W Thermocouple: ± 1° C (1.8° F)
Measuring Range
- Resistance Bulb: -200° to 600° C (-328° to 1,112° F)
- Thermocouple: -200° to 1,760° C (-328° to 3,200° F)
Mounting
- Panel-Mounted (Vertical Panel)
Mounting Position
- Backward 30° Slant [Reading Change: ± (0.2 % + 1-Digit) or Lower]
Operating Voltages
- 90-264 Vac
Power Supply
- 90-264 Vac at 50/60 Hz
- Rated: 100-240 Vac
Pulse Range
- Input Pulse Width (ON/OFF): 400 milliseconds
Resistance
- Signal Source Resistance (Resistance Bulb Input): 10 ohms/Wire or Less [Reading Change: ± (0.2 % + 1-Digit) or Lower]
- Signal Source Resistance (Thermocouple Input): 1 Kiloohm or Less
Resistance Effect
- Effect of Input Signal Resistance (Thermocouple Input): 50 μV ± 1-Digit/100 ohms
Resolution
- Digital Indication: 0.1° C (0.18° F) for Thermocouple & Resistance Bulb
- Digital Indication: 1 mV for 5 Vdc
- Digital Indication: 10 V for 50 mVdc
- Digital Indication: 100 V for 500 mVdc
RTD Type
- Cu50
- JPt100
- Ni100
- Pt100
- Pt50
Sensor, Probe Type
- B Thermocouple
- E Thermocouple
- J Thermocouple
- K Thermocouple
- L Thermocouple
- N Thermocouple
- PN Thermocouple
- R Thermocouple
- S Thermocouple
- T Thermocouple
- U Thermocouple
- W Thermocouple
Shock
- Transportation/Storage Conditions: 294 m/sec² or Lower (Packed State)
Storage Temperature
- -10° to 60° C (14° to 140° F)
System Requirements
- Windows® 2000/XP (Windows® Vista is Not Supported)
Temperature Effect
- Ambient (Reading Change): ± (0.3 % + 1-Digit)/10° C or Lower
Temperature Range
- Transportation: -10° to 60° C (14° to 140° F)
Time Constant
- Input Filter Function: 0 to 900 seconds
Vibration
- 10-60 Hz with the Acceleration of 0.2 m/sec² or Less [Reading Change: ± (0.2 % + 1-Digit) or Lower]
- Transportation/Storage Conditions: 10-60 Hz, 2.45 m/sec² or Lower
Voltage
- Withstand Voltage [Alarm Terminal (Contact Output) - Alarm Terminal (Contact Output)]: 750 Vac, 1 Minute
- Withstand Voltage [Input Terminal - Input Terminal, Input Terminal - Ground, Communication Terminal - Ground, Alarm Terminal (Open Collector) - Ground, Power Terminal - Input Terminal]: 500 Vac, 1 Minute
- Withstand Voltage [Power Terminal - Ground, Alarm Terminal (Contact Output) - Ground]: 2,000 Vac, 1 Minute