Series 9270 switching repeaters can be used for operating contacts, NAMUR proximity sensors or optocouplers.

A relay output or electronic output transmits the signals to the control level. 

The intrinsically safe digital input is galvanically separated from the output and auxiliary power.
Features
  • Slim design – 12.5 mm wide – for one- and dual-channel versions
  • Can be used for functional safety levels up to SIL 2 (IEC/EN 61508)
  • Offers line fault detection with signalization

1 - 5 of 5 Part Numbers
261409
261409
R. STAHL Switching Repeater Ex I Field Circuit
Slim design – 12.5 mm wide – for one- and dual-channel versions

Can be used for functional safety levels up to SIL 2 (IEC/EN 61508)

Offers line fault detection with signalization

Ambient Conditions

  • Ambient temperature - -20 °C ... +60 °C
  • Ambient temperature max. - +60 °C
  • Ambient temperature min. - -20 °C
  • Electromagnetic compatibility - EN 61326-1 Use in industrial environment Immunity according to EN 61000-6-2 Interference emission to EN 61000-6-4
  • Relative humidity max. - 10 to 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - 24 V DC
  • Auxiliary power voltage range - 19,2 ... 30 V
  • Nominal current - 21.00 mA
  • Operation indication - Green "PWR" LED
  • Polarity reversal protection - yes
  • Power consumption - 0.65 W
  • Power dissipation max. - 0.65 W
  • Undervoltage monitoring - No

Electrical Data

  • Line fault transparency - No
  • Number of channels - 1

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - IBExU17ATEX1151 X
  • ATEX gas certificate - IBExU17ATEX1151 X
  • Certificates - ATEX (IBE), Canada / USA (UL), IECEx (IBE), SIL (exida)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II (1) G Ex nA nC [Ex ia Ga] IIC T4 Gc
  • Gas explosion protection IECEx - Ex nA nC [Ex ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx IBE 17.0043 X
  • IECEX gas certificate - IECEx IBE 17.0043 X
  • Installation in Division NEC 500 - (Class I, II, III) 2

Galvanic isolation

  • Galvanic isolation Ex i input to auxiliary power - 375 V AC peak value
  • Galvanic isolation Ex i input to fault message contact - 375 V AC peak value
  • Galvanic isolation Ex i input to output - 375 V AC peak value
  • Galvanic isolation fault message contact to auxiliary power - 300 Veff
  • Galvanic isolation fault message contact to output - 300 Veff
  • Galvanic isolation output to auxiliary power - 300 Veff
  • Galvanic isolation output to output - 300 Veff
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 61010 / EN 50178

General

  • Functional Description - Series 9270 switching repeaters can be used for operating contacts, NAMUR proximity sensors or optocouplers. A relay output or electronic output transmits the signals to the control level. The intrinsically safe digital input is galvanically separated from the output and auxiliary power.
  • Highlights - Slim design – 12.5 mm wide – for one- and dual-channel versions Can be used for functional safety levels up to SIL 2 (IEC/EN 61508) Offers line fault detection with signalization
  • Product Description - Switching repeater Ex i field circuit
  • Product Type - 9270/11-16-14s
  • Title Product Variant Technical Data - Relay (250 V / 2 A)
  • WebCode - 9270A

Input

  • input current for OFF - ≤ 1,2 mA
  • input current for ON - ≥ 2,1 mA
  • Input internal resistiance R i - 1000.00 Ω
  • Input open circuit voltage U a - 8 V
  • input signal - In accordance with EN 60947-5-6 (NAMUR)

Mechanical Data

  • Connection cross-section - 0.2-2.5 mm² flexible
  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 12.50 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.160 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 0.2 mm²
  • Conduct cross-section flexible max. - 2.5 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Screw terminal
  • Mounting position - Vertical
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Error detection wire breakage - IE < 0.05 ... 0.35 mA
  • Indication of line fault - "LF" LED, red
  • LFD relay - via 9193/21-11-11
  • Output - 1 change-over contact - relay
  • Output max. load AC - 250 V / 2 A
  • Output max. load DC - 30 V / 2 A
  • Output mechanical service life - 1 x 10^7 operating cycles
  • Output min. load - 5 V / 10 mA
  • Output per channel - 1 change-over contact
  • Output switching capacity - 500 VA
  • Output switching frequency - 20 Hz
  • Output version (control) - Relay (250 V / 2 A)
  • Short circuit error detection - RE < 100 ... 360 Ω
  • Switch user adjustment inverting - Activated / deactivated
  • Switch user adjustment line fault - activated / deactivated
  • Switching state indication - Yellow LED "OUT"

Safety Data

  • Internal capacitance C i - 11 nF
  • Internal inductance L i - negligible
  • Max. Current I o - 10.0 mA
  • Max. permissible external capacitance C o for IIA - 210.000 μF
  • Max. permissible external capacitance C o for IIB - 26.000 μF
  • Max. permissible external capacitance C o for IIC - 3.600 μF
  • Max. permissible external inductance L o for IIA - 1000.00 mH
  • Max. permissible external inductance L o for IIB - 1000.000 mH
  • Max. permissible external inductance L o for IIC - 300.000 mH
  • Max. Power P o - 25.000 mW
  • Max. Voltage U o - 9.60 V
  • Safety-related maximum voltage - 253 V AC
261410
261410
R. STAHL Switching Repeater Ex I Field Circuit
Slim design – 12.5 mm wide – for one- and dual-channel versions

Can be used for functional safety levels up to SIL 2 (IEC/EN 61508)

Offers line fault detection with signalization

Ambient Conditions

  • Ambient temperature - -20 °C ... +60 °C
  • Ambient temperature max. - +60 °C
  • Ambient temperature min. - -20 °C
  • Electromagnetic compatibility - EN 61326-1 Use in industrial environment Immunity according to EN 61000-6-2 Interference emission to EN 61000-6-4
  • Relative humidity max. - 10 to 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - 24 V DC
  • Auxiliary power voltage range - 19,2 ... 30 V
  • Nominal current - 30.00 mA
  • Operation indication - Green "PWR" LED
  • Polarity reversal protection - yes
  • Power consumption - 0.95 W
  • Power dissipation max. - 0.95 W
  • Undervoltage monitoring - No

Electrical Data

  • Line fault transparency - No
  • Number of channels - 1

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - IBExU17ATEX1151 X
  • ATEX gas certificate - IBExU17ATEX1151 X
  • Certificates - ATEX (IBE), Canada / USA (UL), IECEx (IBE), SIL (exida)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II (1) G Ex nA nC [Ex ia Ga] IIC T4 Gc
  • Gas explosion protection IECEx - Ex nA nC [Ex ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx IBE 17.0043 X
  • IECEX gas certificate - IECEx IBE 17.0043 X
  • Installation in Division NEC 500 - (Class I, II, III) 2

Galvanic isolation

  • Galvanic isolation Ex i input to auxiliary power - 375 V AC peak value
  • Galvanic isolation Ex i input to fault message contact - 375 V AC peak value
  • Galvanic isolation Ex i input to output - 375 V AC peak value
  • Galvanic isolation fault message contact to auxiliary power - 300 Veff
  • Galvanic isolation fault message contact to output - 300 Veff
  • Galvanic isolation output to auxiliary power - 300 Veff
  • Galvanic isolation output to output - 300 Veff
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 61010 / EN 50178

General

  • Functional Description - Series 9270 switching repeaters can be used for operating contacts, NAMUR proximity sensors or optocouplers. A relay output or electronic output transmits the signals to the control level. The intrinsically safe digital input is galvanically separated from the output and auxiliary power.
  • Highlights - Slim design – 12.5 mm wide – for one- and dual-channel versions Can be used for functional safety levels up to SIL 2 (IEC/EN 61508) Offers line fault detection with signalization
  • Product Description - Switching repeater Ex i field circuit
  • Product Type - 9270/11-17-15s
  • Title Product Variant Technical Data - 9270/11-17-15s switching repeater
  • WebCode - 9270A

Input

  • input current for OFF - ≤ 1,2 mA
  • input current for ON - ≥ 2,1 mA
  • Input internal resistiance R i - 1000.00 Ω
  • Input open circuit voltage U a - 8 V
  • input signal - In accordance with EN 60947-5-6 (NAMUR)

Mechanical Data

  • Connection cross-section - 0.2-2.5 mm² flexible
  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 12.50 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.165 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 0.2 mm²
  • Conduct cross-section flexible max. - 2.5 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Screw terminal
  • Mounting position - Vertical
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Error detection wire breakage - IE < 0.05 ... 0.35 mA
  • Indication of line fault - "LF" LED, red
  • LFD relay - via 9193/21-11-11 / opt. out 2
  • Output - 2 NO - relays
  • Output max. load AC - 250 V / 2 A
  • Output max. load DC - 30 V / 2 A
  • Output mechanical service life - 1 x 10^7 operating cycles
  • Output min. load - 5 V / 10 mA
  • Output per channel - 2 NOs
  • Output switching capacity - 500 VA
  • Output switching frequency - 20 Hz
  • Output version (control) - Relay (250 V / 2 A)
  • Short circuit error detection - RE < 100 ... 360 Ω
  • Switch user adjustment inverting - Activated / deactivated
  • Switch user adjustment line fault - activated / deactivated
  • Switching state indication - Yellow LED "OUT"

Safety Data

  • Internal capacitance C i - 11 nF
  • Internal inductance L i - negligible
  • Max. Current I o - 10.0 mA
  • Max. permissible external capacitance C o for IIA - 210.000 μF
  • Max. permissible external capacitance C o for IIB - 26.000 μF
  • Max. permissible external capacitance C o for IIC - 3.600 μF
  • Max. permissible external inductance L o for IIA - 1000.00 mH
  • Max. permissible external inductance L o for IIB - 1000.000 mH
  • Max. permissible external inductance L o for IIC - 300.000 mH
  • Max. Power P o - 25.000 mW
  • Max. Voltage U o - 9.60 V
  • Safety-related maximum voltage - 253 V AC
261411
261411
R. STAHL Switching Repeater Ex I Field Circuit
Slim design – 12.5 mm wide – for one- and dual-channel versions

Can be used for functional safety levels up to SIL 2 (IEC/EN 61508)

Offers line fault detection with signalization

Ambient Conditions

  • Ambient temperature - -20 °C ... +60 °C
  • Ambient temperature max. - +60 °C
  • Ambient temperature min. - -20 °C
  • Electromagnetic compatibility - EN 61326-1 Use in industrial environment Immunity according to EN 61000-6-2 Interference emission to EN 61000-6-4
  • Relative humidity max. - 10 to 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - 24 V DC
  • Auxiliary power voltage range - 19,2 ... 30 V
  • Nominal current - 35.00 mA
  • Operation indication - Green "PWR" LED
  • Polarity reversal protection - yes
  • Power consumption - 1.00 W
  • Power dissipation max. - 1.00 W
  • Undervoltage monitoring - No

Electrical Data

  • Line fault transparency - No
  • Number of channels - 2

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - IBExU17ATEX1151 X
  • ATEX gas certificate - IBExU17ATEX1151 X
  • Certificates - ATEX (IBE), Canada / USA (UL), IECEx (IBE), SIL (exida)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II (1) G Ex nA nC [Ex ia Ga] IIC T4 Gc
  • Gas explosion protection IECEx - Ex nA nC [Ex ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx IBE 17.0043 X
  • IECEX gas certificate - IECEx IBE 17.0043 X
  • Installation in Division NEC 500 - (Class I, II, III) 2

Galvanic isolation

  • Galvanic isolation Ex i input to auxiliary power - 375 V AC peak value
  • Galvanic isolation Ex i input to fault message contact - 375 V AC peak value
  • Galvanic isolation Ex i input to output - 375 V AC peak value
  • Galvanic isolation fault message contact to auxiliary power - 300 Veff
  • Galvanic isolation fault message contact to output - 300 Veff
  • Galvanic isolation output to auxiliary power - 300 Veff
  • Galvanic isolation output to output - 300 Veff
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 61010 / EN 50178

General

  • Functional Description - Series 9270 switching repeaters can be used for operating contacts, NAMUR proximity sensors or optocouplers. A relay output or electronic output transmits the signals to the control level. The intrinsically safe digital input is galvanically separated from the output and auxiliary power.
  • Highlights - Slim design – 12.5 mm wide – for one- and dual-channel versions Can be used for functional safety levels up to SIL 2 (IEC/EN 61508) Offers line fault detection with signalization
  • Product Description - Switching repeater Ex i field circuit
  • Product Type - 9270/21-17-14s
  • Title Product Variant Technical Data - 9270/21-17-14s switching repeater
  • WebCode - 9270A

Input

  • input current for OFF - ≤ 1,2 mA
  • input current for ON - ≥ 2,1 mA
  • Input internal resistiance R i - 1000.00 Ω
  • Input open circuit voltage U a - 8 V
  • input signal - In accordance with EN 60947-5-6 (NAMUR)

Mechanical Data

  • Connection cross-section - 0.2-2.5 mm² flexible
  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 12.50 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.170 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 0.2 mm²
  • Conduct cross-section flexible max. - 2.5 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Screw terminal
  • Mounting position - Vertical
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Error detection wire breakage - IE < 0.05 ... 0.35 mA
  • Indication of line fault - "LF" LED, red
  • LFD relay - via 9193/21-11-11
  • Output - 1 NO - relay
  • Output max. load AC - 250 V / 2 A
  • Output max. load DC - 30 V / 2 A
  • Output mechanical service life - 1 x 10^7 operating cycles
  • Output min. load - 5 V / 10 mA
  • Output per channel - 1 NO
  • Output switching capacity - 500 VA
  • Output switching frequency - 20 Hz
  • Output version (control) - Relay (250 V / 2 A)
  • Short circuit error detection - RE < 100 ... 360 Ω
  • Switch user adjustment inverting - Activated / deactivated
  • Switch user adjustment line fault - activated / deactivated
  • Switching state indication - Yellow LED "OUT"

Safety Data

  • Internal capacitance C i - 1.1 nF
  • Internal inductance L i - negligible
  • Max. Current I o - 10.0 mA
  • Max. permissible external capacitance C o for IIA - 210.000 μF
  • Max. permissible external capacitance C o for IIB - 26.000 μF
  • Max. permissible external capacitance C o for IIC - 3.600 μF
  • Max. permissible external inductance L o for IIA - 1000.00 mH
  • Max. permissible external inductance L o for IIB - 1000.000 mH
  • Max. permissible external inductance L o for IIC - 300.000 mH
  • Max. Power P o - 25.000 mW
  • Max. Voltage U o - 9.60 V
  • Safety-related maximum voltage - 253 V AC
261412
261412
R. STAHL Switching Repeater Ex I Field Circuit
Slim design – 12.5 mm wide – for one- and dual-channel versions

Can be used for functional safety levels up to SIL 2 (IEC/EN 61508)

Offers line fault detection with signalization

Ambient Conditions

  • Ambient temperature - -20 °C ... +60 °C
  • Ambient temperature max. - +60 °C
  • Ambient temperature min. - -20 °C
  • Electromagnetic compatibility - EN 61326-1 Use in industrial environment Immunity according to EN 61000-6-2 Interference emission to EN 61000-6-4
  • Relative humidity max. - 10 to 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - 24 V DC
  • Auxiliary power voltage range - 19,2 ... 30 V
  • Nominal current - 28.00 mA
  • Operation indication - Green "PWR" LED
  • Polarity reversal protection - yes
  • Power consumption - 0.80 W
  • Power dissipation max. - 0.80 W
  • Undervoltage monitoring - No

Electrical Data

  • Line fault transparency - No
  • Number of channels - 1

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - IBExU17ATEX1157 X
  • ATEX gas certificate - IBExU17ATEX1157 X
  • Certificates - ATEX (IBE), Canada / USA (UL), IECEx (IBE), SIL (exida)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II (1) G Ex nA Gc, [Ex ia Ga] IIC T4 Gc
  • Gas explosion protection IECEx - Ex nA Gc, [Ex ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx IBE 17.0046 X
  • IECEX gas certificate - IECEx IBE 17.0046 X
  • Installation in Division NEC 500 - (Class I, II, III) 2

Galvanic isolation

  • Galvanic isolation Ex i input to auxiliary power - 375 V AC peak value
  • Galvanic isolation Ex i input to fault message contact - 375 V AC peak value
  • Galvanic isolation Ex i input to output - 375 V AC peak value
  • Galvanic isolation fault message contact to auxiliary power - 300 Veff
  • Galvanic isolation fault message contact to output - 300 Veff
  • Galvanic isolation output to auxiliary power - 300 Veff
  • Galvanic isolation output to output - 300 Veff
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 61010 / EN 50178

General

  • Functional Description - Series 9270 switching repeaters can be used for operating contacts, NAMUR proximity sensors or optocouplers. A relay output or electronic output transmits the signals to the control level. The intrinsically safe digital input is galvanically separated from the output and auxiliary power.
  • Highlights - Slim design – 12.5 mm wide – for one- and dual-channel versions Can be used for functional safety levels up to SIL 2 (IEC/EN 61508) Offers line fault detection with signalization
  • Product Description - Switching repeater Ex i field circuit
  • Product Type - 9270/11-19-15s
  • Title Product Variant Technical Data - Electronic (30 V / 50 mA)
  • WebCode - 9270A

Input

  • input current for OFF - ≤ 1,2 mA
  • input current for ON - ≥ 2,1 mA
  • Input internal resistiance R i - 1000.00 Ω
  • Input open circuit voltage U a - 8 V
  • input signal - In accordance with EN 60947-5-6 (NAMUR)

Mechanical Data

  • Connection cross-section - 0.2-2.5 mm² flexible
  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 12.50 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.160 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 0.2 mm²
  • Conduct cross-section flexible max. - 2.5 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Screw terminal
  • Mounting position - Vertical
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Error detection wire breakage - IE < 0.05 ... 0.35 mA
  • Indication of line fault - "LF" LED, red
  • LFD relay - via 9193/21-11-11 / opt. out 2
  • Output - 2 electronic outputs
  • Output max. load DC - 30 V / 50 mA
  • Output min. load - 3 V / 5 mA
  • Output per channel - 2 electronic outputs
  • Output switching capacity - 30 V DC
  • Output switching frequency - 5 kHz
  • Output version (control) - Electronic (30 V / 50 mA)
  • Short circuit error detection - RE < 100 ... 360 Ω
  • Switch user adjustment inverting - Activated / deactivated
  • Switch user adjustment line fault - activated / deactivated
  • Switching state indication - Yellow LED "OUT"

Safety Data

  • Internal capacitance C i - 1.1 nF
  • Internal inductance L i - negligible
  • Max. Current I o - 10.0 mA
  • Max. permissible external capacitance C o for IIA - 210.000 μF
  • Max. permissible external capacitance C o for IIB - 26.000 μF
  • Max. permissible external capacitance C o for IIC - 3.600 μF
  • Max. permissible external inductance L o for IIA - 1000.00 mH
  • Max. permissible external inductance L o for IIB - 1000.000 mH
  • Max. permissible external inductance L o for IIC - 300.000 mH
  • Max. Power P o - 25.000 mW
  • Max. Voltage U o - 9.60 V
  • Safety-related maximum voltage - 253 V AC
261413
261413
R. STAHL Switching Repeater Ex I Field Circuit
Slim design – 12.5 mm wide – for one- and dual-channel versions

Can be used for functional safety levels up to SIL 2 (IEC/EN 61508)

Offers line fault detection with signalization

Ambient Conditions

  • Ambient temperature - -20 °C ... +60 °C
  • Ambient temperature max. - +60 °C
  • Ambient temperature min. - -20 °C
  • Electromagnetic compatibility - EN 61326-1 Use in industrial environment Immunity according to EN 61000-6-2 Interference emission to EN 61000-6-4
  • Relative humidity max. - 10 to 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - 24 V DC
  • Auxiliary power voltage range - 19,2 ... 30 V
  • Nominal current - 34.00 mA
  • Operation indication - Green "PWR" LED
  • Polarity reversal protection - yes
  • Power consumption - 1.00 W
  • Power dissipation max. - 1.00 W
  • Undervoltage monitoring - No

Electrical Data

  • Line fault transparency - No
  • Number of channels - 2

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - IBExU17ATEX1157 X
  • ATEX gas certificate - IBExU17ATEX1157 X
  • Certificates - ATEX (IBE), Canada / USA (UL), IECEx (IBE), SIL (exida)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II (1) G Ex nA Gc, [Ex ia Ga] IIC T4 Gc
  • Gas explosion protection IECEx - Ex nA Gc, [Ex ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx IBE 17.0046 X
  • IECEX gas certificate - IECEx IBE 17.0046 X
  • Installation in Division NEC 500 - (Class I, II, III) 2

Galvanic isolation

  • Galvanic isolation Ex i input to auxiliary power - 375 V AC peak value
  • Galvanic isolation Ex i input to fault message contact - 375 V AC peak value
  • Galvanic isolation Ex i input to output - 375 V AC peak value
  • Galvanic isolation fault message contact to auxiliary power - 300 Veff
  • Galvanic isolation fault message contact to output - 300 Veff
  • Galvanic isolation output to auxiliary power - 300 Veff
  • Galvanic isolation output to output - 300 Veff
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 61010 / EN 50178

General

  • Functional Description - Series 9270 switching repeaters can be used for operating contacts, NAMUR proximity sensors or optocouplers. A relay output or electronic output transmits the signals to the control level. The intrinsically safe digital input is galvanically separated from the output and auxiliary power.
  • Highlights - Slim design – 12.5 mm wide – for one- and dual-channel versions Can be used for functional safety levels up to SIL 2 (IEC/EN 61508) Offers line fault detection with signalization
  • Product Description - Switching repeater Ex i field circuit
  • Product Type - 9270/21-14-14s
  • Title Product Variant Technical Data - 9270/21-14-14s switching repeater
  • WebCode - 9270A

Input

  • input current for OFF - ≤ 1,2 mA
  • input current for ON - ≥ 2,1 mA
  • Input internal resistiance R i - 1000.00 Ω
  • Input open circuit voltage U a - 8 V
  • input signal - In accordance with EN 60947-5-6 (NAMUR)

Mechanical Data

  • Connection cross-section - 0.2-2.5 mm² flexible
  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 12.50 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.165 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 2.5 mm²
  • Conduct cross-section flexible max. - 0.2 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Screw terminal
  • Mounting position - Vertical
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Error detection wire breakage - IE < 0.05 ... 0.35 mA
  • Indication of line fault - "LF" LED, red
  • LFD relay - via 9193/21-11-11
  • Output - 1 electronic output
  • Output max. load DC - 30 V / 50 mA
  • Output min. load - 3 V / 5 mA
  • Output per channel - 1 electronic output
  • Output switching capacity - 30 V DC
  • Output switching frequency - 5 kHz
  • Output version (control) - Electronic (30 V / 50 mA)
  • Short circuit error detection - RE < 100 ... 360 Ω
  • Switch user adjustment inverting - Activated / deactivated
  • Switch user adjustment line fault - activated / deactivated
  • Switching state indication - Yellow LED "OUT"

Safety Data

  • Internal capacitance C i - 1.1 nF
  • Internal inductance L i - negligible
  • Max. Current I o - 10.0 mA
  • Max. permissible external capacitance C o for IIA - 210.000 μF
  • Max. permissible external capacitance C o for IIB - 26.000 μF
  • Max. permissible external capacitance C o for IIC - 3.600 μF
  • Max. permissible external inductance L o for IIA - 1000.00 mH
  • Max. permissible external inductance L o for IIB - 1000.000 mH
  • Max. permissible external inductance L o for IIC - 300.000 mH
  • Max. Power P o - 25.000 mW
  • Max. Voltage U o - 9.60 V
  • Safety-related maximum voltage - 253 V AC
1 - 5 of 5 Part Numbers