Yodify Product Library
Instantly add the Switching Repeater Series 9270 and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
Switching Repeater Series 9270
Brand: R. STAHL AGSeries 9270 switching repeaters can be used for operating contacts, NAMUR proximity sensors or optocouplers.
A relay output or electronic output transmits the signals to the control level.
The intrinsically safe digital input is galvanically separated from the output and auxiliary power.
Features- Slim design – 12.5 mm wide – for one- and dual-channel versions
- Can be used for functional safety levels up to SIL 2 (IEC/EN 61508)
- Offers line fault detection with signalization
1 - 5 of 5 Part Numbers
261409
Slim design – 12.5 mm wide – for one- and dual-channel versions
Can be used for functional safety levels up to SIL 2 (IEC/EN 61508)
Offers line fault detection with signalization
Ambient Conditions
- Ambient temperature - -20 °C ... +60 °C
- Ambient temperature max. - +60 °C
- Ambient temperature min. - -20 °C
- Electromagnetic compatibility - EN 61326-1 Use in industrial environment Immunity according to EN 61000-6-2 Interference emission to EN 61000-6-4
- Relative humidity max. - 10 to 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power voltage range - 19,2 ... 30 V
- Nominal current - 21.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 0.65 W
- Power dissipation max. - 0.65 W
- Undervoltage monitoring - No
Electrical Data
- Line fault transparency - No
- Number of channels - 1
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - IBExU17ATEX1151 X
- ATEX gas certificate - IBExU17ATEX1151 X
- Certificates - ATEX (IBE), Canada / USA (UL), IECEx (IBE), SIL (exida)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II (1) G Ex nA nC [Ex ia Ga] IIC T4 Gc
- Gas explosion protection IECEx - Ex nA nC [Ex ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx IBE 17.0043 X
- IECEX gas certificate - IECEx IBE 17.0043 X
- Installation in Division NEC 500 - (Class I, II, III) 2
Galvanic isolation
- Galvanic isolation Ex i input to auxiliary power - 375 V AC peak value
- Galvanic isolation Ex i input to fault message contact - 375 V AC peak value
- Galvanic isolation Ex i input to output - 375 V AC peak value
- Galvanic isolation fault message contact to auxiliary power - 300 Veff
- Galvanic isolation fault message contact to output - 300 Veff
- Galvanic isolation output to auxiliary power - 300 Veff
- Galvanic isolation output to output - 300 Veff
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 61010 / EN 50178
General
- Functional Description - Series 9270 switching repeaters can be used for operating contacts, NAMUR proximity sensors or optocouplers. A relay output or electronic output transmits the signals to the control level. The intrinsically safe digital input is galvanically separated from the output and auxiliary power.
- Highlights - Slim design – 12.5 mm wide – for one- and dual-channel versions Can be used for functional safety levels up to SIL 2 (IEC/EN 61508) Offers line fault detection with signalization
- Product Description - Switching repeater Ex i field circuit
- Product Type - 9270/11-16-14s
- Title Product Variant Technical Data - Relay (250 V / 2 A)
- WebCode - 9270A
Input
- input current for OFF - ≤ 1,2 mA
- input current for ON - ≥ 2,1 mA
- Input internal resistiance R i - 1000.00 Ω
- Input open circuit voltage U a - 8 V
- input signal - In accordance with EN 60947-5-6 (NAMUR)
Mechanical Data
- Connection cross-section - 0.2-2.5 mm² flexible
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 12.50 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.160 kg
Mounting / Installation
- Conduct cross-section flexible max. - 0.2 mm²
- Conduct cross-section flexible max. - 2.5 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Screw terminal
- Mounting position - Vertical
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Error detection wire breakage - IE < 0.05 ... 0.35 mA
- Indication of line fault - "LF" LED, red
- LFD relay - via 9193/21-11-11
- Output - 1 change-over contact - relay
- Output max. load AC - 250 V / 2 A
- Output max. load DC - 30 V / 2 A
- Output mechanical service life - 1 x 10^7 operating cycles
- Output min. load - 5 V / 10 mA
- Output per channel - 1 change-over contact
- Output switching capacity - 500 VA
- Output switching frequency - 20 Hz
- Output version (control) - Relay (250 V / 2 A)
- Short circuit error detection - RE < 100 ... 360 Ω
- Switch user adjustment inverting - Activated / deactivated
- Switch user adjustment line fault - activated / deactivated
- Switching state indication - Yellow LED "OUT"
Safety Data
- Internal capacitance C i - 11 nF
- Internal inductance L i - negligible
- Max. Current I o - 10.0 mA
- Max. permissible external capacitance C o for IIA - 210.000 μF
- Max. permissible external capacitance C o for IIB - 26.000 μF
- Max. permissible external capacitance C o for IIC - 3.600 μF
- Max. permissible external inductance L o for IIA - 1000.00 mH
- Max. permissible external inductance L o for IIB - 1000.000 mH
- Max. permissible external inductance L o for IIC - 300.000 mH
- Max. Power P o - 25.000 mW
- Max. Voltage U o - 9.60 V
- Safety-related maximum voltage - 253 V AC
261410
Slim design – 12.5 mm wide – for one- and dual-channel versions
Can be used for functional safety levels up to SIL 2 (IEC/EN 61508)
Offers line fault detection with signalization
Ambient Conditions
- Ambient temperature - -20 °C ... +60 °C
- Ambient temperature max. - +60 °C
- Ambient temperature min. - -20 °C
- Electromagnetic compatibility - EN 61326-1 Use in industrial environment Immunity according to EN 61000-6-2 Interference emission to EN 61000-6-4
- Relative humidity max. - 10 to 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power voltage range - 19,2 ... 30 V
- Nominal current - 30.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 0.95 W
- Power dissipation max. - 0.95 W
- Undervoltage monitoring - No
Electrical Data
- Line fault transparency - No
- Number of channels - 1
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - IBExU17ATEX1151 X
- ATEX gas certificate - IBExU17ATEX1151 X
- Certificates - ATEX (IBE), Canada / USA (UL), IECEx (IBE), SIL (exida)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II (1) G Ex nA nC [Ex ia Ga] IIC T4 Gc
- Gas explosion protection IECEx - Ex nA nC [Ex ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx IBE 17.0043 X
- IECEX gas certificate - IECEx IBE 17.0043 X
- Installation in Division NEC 500 - (Class I, II, III) 2
Galvanic isolation
- Galvanic isolation Ex i input to auxiliary power - 375 V AC peak value
- Galvanic isolation Ex i input to fault message contact - 375 V AC peak value
- Galvanic isolation Ex i input to output - 375 V AC peak value
- Galvanic isolation fault message contact to auxiliary power - 300 Veff
- Galvanic isolation fault message contact to output - 300 Veff
- Galvanic isolation output to auxiliary power - 300 Veff
- Galvanic isolation output to output - 300 Veff
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 61010 / EN 50178
General
- Functional Description - Series 9270 switching repeaters can be used for operating contacts, NAMUR proximity sensors or optocouplers. A relay output or electronic output transmits the signals to the control level. The intrinsically safe digital input is galvanically separated from the output and auxiliary power.
- Highlights - Slim design – 12.5 mm wide – for one- and dual-channel versions Can be used for functional safety levels up to SIL 2 (IEC/EN 61508) Offers line fault detection with signalization
- Product Description - Switching repeater Ex i field circuit
- Product Type - 9270/11-17-15s
- Title Product Variant Technical Data - 9270/11-17-15s switching repeater
- WebCode - 9270A
Input
- input current for OFF - ≤ 1,2 mA
- input current for ON - ≥ 2,1 mA
- Input internal resistiance R i - 1000.00 Ω
- Input open circuit voltage U a - 8 V
- input signal - In accordance with EN 60947-5-6 (NAMUR)
Mechanical Data
- Connection cross-section - 0.2-2.5 mm² flexible
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 12.50 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.165 kg
Mounting / Installation
- Conduct cross-section flexible max. - 0.2 mm²
- Conduct cross-section flexible max. - 2.5 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Screw terminal
- Mounting position - Vertical
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Error detection wire breakage - IE < 0.05 ... 0.35 mA
- Indication of line fault - "LF" LED, red
- LFD relay - via 9193/21-11-11 / opt. out 2
- Output - 2 NO - relays
- Output max. load AC - 250 V / 2 A
- Output max. load DC - 30 V / 2 A
- Output mechanical service life - 1 x 10^7 operating cycles
- Output min. load - 5 V / 10 mA
- Output per channel - 2 NOs
- Output switching capacity - 500 VA
- Output switching frequency - 20 Hz
- Output version (control) - Relay (250 V / 2 A)
- Short circuit error detection - RE < 100 ... 360 Ω
- Switch user adjustment inverting - Activated / deactivated
- Switch user adjustment line fault - activated / deactivated
- Switching state indication - Yellow LED "OUT"
Safety Data
- Internal capacitance C i - 11 nF
- Internal inductance L i - negligible
- Max. Current I o - 10.0 mA
- Max. permissible external capacitance C o for IIA - 210.000 μF
- Max. permissible external capacitance C o for IIB - 26.000 μF
- Max. permissible external capacitance C o for IIC - 3.600 μF
- Max. permissible external inductance L o for IIA - 1000.00 mH
- Max. permissible external inductance L o for IIB - 1000.000 mH
- Max. permissible external inductance L o for IIC - 300.000 mH
- Max. Power P o - 25.000 mW
- Max. Voltage U o - 9.60 V
- Safety-related maximum voltage - 253 V AC
261411
Slim design – 12.5 mm wide – for one- and dual-channel versions
Can be used for functional safety levels up to SIL 2 (IEC/EN 61508)
Offers line fault detection with signalization
Ambient Conditions
- Ambient temperature - -20 °C ... +60 °C
- Ambient temperature max. - +60 °C
- Ambient temperature min. - -20 °C
- Electromagnetic compatibility - EN 61326-1 Use in industrial environment Immunity according to EN 61000-6-2 Interference emission to EN 61000-6-4
- Relative humidity max. - 10 to 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power voltage range - 19,2 ... 30 V
- Nominal current - 35.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 1.00 W
- Power dissipation max. - 1.00 W
- Undervoltage monitoring - No
Electrical Data
- Line fault transparency - No
- Number of channels - 2
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - IBExU17ATEX1151 X
- ATEX gas certificate - IBExU17ATEX1151 X
- Certificates - ATEX (IBE), Canada / USA (UL), IECEx (IBE), SIL (exida)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II (1) G Ex nA nC [Ex ia Ga] IIC T4 Gc
- Gas explosion protection IECEx - Ex nA nC [Ex ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx IBE 17.0043 X
- IECEX gas certificate - IECEx IBE 17.0043 X
- Installation in Division NEC 500 - (Class I, II, III) 2
Galvanic isolation
- Galvanic isolation Ex i input to auxiliary power - 375 V AC peak value
- Galvanic isolation Ex i input to fault message contact - 375 V AC peak value
- Galvanic isolation Ex i input to output - 375 V AC peak value
- Galvanic isolation fault message contact to auxiliary power - 300 Veff
- Galvanic isolation fault message contact to output - 300 Veff
- Galvanic isolation output to auxiliary power - 300 Veff
- Galvanic isolation output to output - 300 Veff
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 61010 / EN 50178
General
- Functional Description - Series 9270 switching repeaters can be used for operating contacts, NAMUR proximity sensors or optocouplers. A relay output or electronic output transmits the signals to the control level. The intrinsically safe digital input is galvanically separated from the output and auxiliary power.
- Highlights - Slim design – 12.5 mm wide – for one- and dual-channel versions Can be used for functional safety levels up to SIL 2 (IEC/EN 61508) Offers line fault detection with signalization
- Product Description - Switching repeater Ex i field circuit
- Product Type - 9270/21-17-14s
- Title Product Variant Technical Data - 9270/21-17-14s switching repeater
- WebCode - 9270A
Input
- input current for OFF - ≤ 1,2 mA
- input current for ON - ≥ 2,1 mA
- Input internal resistiance R i - 1000.00 Ω
- Input open circuit voltage U a - 8 V
- input signal - In accordance with EN 60947-5-6 (NAMUR)
Mechanical Data
- Connection cross-section - 0.2-2.5 mm² flexible
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 12.50 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.170 kg
Mounting / Installation
- Conduct cross-section flexible max. - 0.2 mm²
- Conduct cross-section flexible max. - 2.5 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Screw terminal
- Mounting position - Vertical
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Error detection wire breakage - IE < 0.05 ... 0.35 mA
- Indication of line fault - "LF" LED, red
- LFD relay - via 9193/21-11-11
- Output - 1 NO - relay
- Output max. load AC - 250 V / 2 A
- Output max. load DC - 30 V / 2 A
- Output mechanical service life - 1 x 10^7 operating cycles
- Output min. load - 5 V / 10 mA
- Output per channel - 1 NO
- Output switching capacity - 500 VA
- Output switching frequency - 20 Hz
- Output version (control) - Relay (250 V / 2 A)
- Short circuit error detection - RE < 100 ... 360 Ω
- Switch user adjustment inverting - Activated / deactivated
- Switch user adjustment line fault - activated / deactivated
- Switching state indication - Yellow LED "OUT"
Safety Data
- Internal capacitance C i - 1.1 nF
- Internal inductance L i - negligible
- Max. Current I o - 10.0 mA
- Max. permissible external capacitance C o for IIA - 210.000 μF
- Max. permissible external capacitance C o for IIB - 26.000 μF
- Max. permissible external capacitance C o for IIC - 3.600 μF
- Max. permissible external inductance L o for IIA - 1000.00 mH
- Max. permissible external inductance L o for IIB - 1000.000 mH
- Max. permissible external inductance L o for IIC - 300.000 mH
- Max. Power P o - 25.000 mW
- Max. Voltage U o - 9.60 V
- Safety-related maximum voltage - 253 V AC
261412
Slim design – 12.5 mm wide – for one- and dual-channel versions
Can be used for functional safety levels up to SIL 2 (IEC/EN 61508)
Offers line fault detection with signalization
Ambient Conditions
- Ambient temperature - -20 °C ... +60 °C
- Ambient temperature max. - +60 °C
- Ambient temperature min. - -20 °C
- Electromagnetic compatibility - EN 61326-1 Use in industrial environment Immunity according to EN 61000-6-2 Interference emission to EN 61000-6-4
- Relative humidity max. - 10 to 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power voltage range - 19,2 ... 30 V
- Nominal current - 28.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 0.80 W
- Power dissipation max. - 0.80 W
- Undervoltage monitoring - No
Electrical Data
- Line fault transparency - No
- Number of channels - 1
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - IBExU17ATEX1157 X
- ATEX gas certificate - IBExU17ATEX1157 X
- Certificates - ATEX (IBE), Canada / USA (UL), IECEx (IBE), SIL (exida)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II (1) G Ex nA Gc, [Ex ia Ga] IIC T4 Gc
- Gas explosion protection IECEx - Ex nA Gc, [Ex ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx IBE 17.0046 X
- IECEX gas certificate - IECEx IBE 17.0046 X
- Installation in Division NEC 500 - (Class I, II, III) 2
Galvanic isolation
- Galvanic isolation Ex i input to auxiliary power - 375 V AC peak value
- Galvanic isolation Ex i input to fault message contact - 375 V AC peak value
- Galvanic isolation Ex i input to output - 375 V AC peak value
- Galvanic isolation fault message contact to auxiliary power - 300 Veff
- Galvanic isolation fault message contact to output - 300 Veff
- Galvanic isolation output to auxiliary power - 300 Veff
- Galvanic isolation output to output - 300 Veff
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 61010 / EN 50178
General
- Functional Description - Series 9270 switching repeaters can be used for operating contacts, NAMUR proximity sensors or optocouplers. A relay output or electronic output transmits the signals to the control level. The intrinsically safe digital input is galvanically separated from the output and auxiliary power.
- Highlights - Slim design – 12.5 mm wide – for one- and dual-channel versions Can be used for functional safety levels up to SIL 2 (IEC/EN 61508) Offers line fault detection with signalization
- Product Description - Switching repeater Ex i field circuit
- Product Type - 9270/11-19-15s
- Title Product Variant Technical Data - Electronic (30 V / 50 mA)
- WebCode - 9270A
Input
- input current for OFF - ≤ 1,2 mA
- input current for ON - ≥ 2,1 mA
- Input internal resistiance R i - 1000.00 Ω
- Input open circuit voltage U a - 8 V
- input signal - In accordance with EN 60947-5-6 (NAMUR)
Mechanical Data
- Connection cross-section - 0.2-2.5 mm² flexible
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 12.50 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.160 kg
Mounting / Installation
- Conduct cross-section flexible max. - 0.2 mm²
- Conduct cross-section flexible max. - 2.5 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Screw terminal
- Mounting position - Vertical
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Error detection wire breakage - IE < 0.05 ... 0.35 mA
- Indication of line fault - "LF" LED, red
- LFD relay - via 9193/21-11-11 / opt. out 2
- Output - 2 electronic outputs
- Output max. load DC - 30 V / 50 mA
- Output min. load - 3 V / 5 mA
- Output per channel - 2 electronic outputs
- Output switching capacity - 30 V DC
- Output switching frequency - 5 kHz
- Output version (control) - Electronic (30 V / 50 mA)
- Short circuit error detection - RE < 100 ... 360 Ω
- Switch user adjustment inverting - Activated / deactivated
- Switch user adjustment line fault - activated / deactivated
- Switching state indication - Yellow LED "OUT"
Safety Data
- Internal capacitance C i - 1.1 nF
- Internal inductance L i - negligible
- Max. Current I o - 10.0 mA
- Max. permissible external capacitance C o for IIA - 210.000 μF
- Max. permissible external capacitance C o for IIB - 26.000 μF
- Max. permissible external capacitance C o for IIC - 3.600 μF
- Max. permissible external inductance L o for IIA - 1000.00 mH
- Max. permissible external inductance L o for IIB - 1000.000 mH
- Max. permissible external inductance L o for IIC - 300.000 mH
- Max. Power P o - 25.000 mW
- Max. Voltage U o - 9.60 V
- Safety-related maximum voltage - 253 V AC
261413
Slim design – 12.5 mm wide – for one- and dual-channel versions
Can be used for functional safety levels up to SIL 2 (IEC/EN 61508)
Offers line fault detection with signalization
Ambient Conditions
- Ambient temperature - -20 °C ... +60 °C
- Ambient temperature max. - +60 °C
- Ambient temperature min. - -20 °C
- Electromagnetic compatibility - EN 61326-1 Use in industrial environment Immunity according to EN 61000-6-2 Interference emission to EN 61000-6-4
- Relative humidity max. - 10 to 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power voltage range - 19,2 ... 30 V
- Nominal current - 34.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 1.00 W
- Power dissipation max. - 1.00 W
- Undervoltage monitoring - No
Electrical Data
- Line fault transparency - No
- Number of channels - 2
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - IBExU17ATEX1157 X
- ATEX gas certificate - IBExU17ATEX1157 X
- Certificates - ATEX (IBE), Canada / USA (UL), IECEx (IBE), SIL (exida)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II (1) G Ex nA Gc, [Ex ia Ga] IIC T4 Gc
- Gas explosion protection IECEx - Ex nA Gc, [Ex ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx IBE 17.0046 X
- IECEX gas certificate - IECEx IBE 17.0046 X
- Installation in Division NEC 500 - (Class I, II, III) 2
Galvanic isolation
- Galvanic isolation Ex i input to auxiliary power - 375 V AC peak value
- Galvanic isolation Ex i input to fault message contact - 375 V AC peak value
- Galvanic isolation Ex i input to output - 375 V AC peak value
- Galvanic isolation fault message contact to auxiliary power - 300 Veff
- Galvanic isolation fault message contact to output - 300 Veff
- Galvanic isolation output to auxiliary power - 300 Veff
- Galvanic isolation output to output - 300 Veff
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 61010 / EN 50178
General
- Functional Description - Series 9270 switching repeaters can be used for operating contacts, NAMUR proximity sensors or optocouplers. A relay output or electronic output transmits the signals to the control level. The intrinsically safe digital input is galvanically separated from the output and auxiliary power.
- Highlights - Slim design – 12.5 mm wide – for one- and dual-channel versions Can be used for functional safety levels up to SIL 2 (IEC/EN 61508) Offers line fault detection with signalization
- Product Description - Switching repeater Ex i field circuit
- Product Type - 9270/21-14-14s
- Title Product Variant Technical Data - 9270/21-14-14s switching repeater
- WebCode - 9270A
Input
- input current for OFF - ≤ 1,2 mA
- input current for ON - ≥ 2,1 mA
- Input internal resistiance R i - 1000.00 Ω
- Input open circuit voltage U a - 8 V
- input signal - In accordance with EN 60947-5-6 (NAMUR)
Mechanical Data
- Connection cross-section - 0.2-2.5 mm² flexible
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 12.50 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.165 kg
Mounting / Installation
- Conduct cross-section flexible max. - 2.5 mm²
- Conduct cross-section flexible max. - 0.2 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Screw terminal
- Mounting position - Vertical
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Error detection wire breakage - IE < 0.05 ... 0.35 mA
- Indication of line fault - "LF" LED, red
- LFD relay - via 9193/21-11-11
- Output - 1 electronic output
- Output max. load DC - 30 V / 50 mA
- Output min. load - 3 V / 5 mA
- Output per channel - 1 electronic output
- Output switching capacity - 30 V DC
- Output switching frequency - 5 kHz
- Output version (control) - Electronic (30 V / 50 mA)
- Short circuit error detection - RE < 100 ... 360 Ω
- Switch user adjustment inverting - Activated / deactivated
- Switch user adjustment line fault - activated / deactivated
- Switching state indication - Yellow LED "OUT"
Safety Data
- Internal capacitance C i - 1.1 nF
- Internal inductance L i - negligible
- Max. Current I o - 10.0 mA
- Max. permissible external capacitance C o for IIA - 210.000 μF
- Max. permissible external capacitance C o for IIB - 26.000 μF
- Max. permissible external capacitance C o for IIC - 3.600 μF
- Max. permissible external inductance L o for IIA - 1000.00 mH
- Max. permissible external inductance L o for IIB - 1000.000 mH
- Max. permissible external inductance L o for IIC - 300.000 mH
- Max. Power P o - 25.000 mW
- Max. Voltage U o - 9.60 V
- Safety-related maximum voltage - 253 V AC
1 - 5 of 5 Part Numbers