Yodify Product Library
Instantly add the Series 616W Differential Pressure Transmitter and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
Series 616W Differential Pressure Transmitter
Brand: Dwyer Instruments, LLCPositive, negative and differential pressures can be measured within a full span accuracy of ±0.25 with the SERIES 616W Differential Pressure Transmitter.
Units are enclosed in a polycarbonate case, rated NEMA 4X (IP66) and operate by sensing the pressure of air and compatible gases then sending a standard 4-20 mA output signal. Design enables operation in 2-wire current loops.
A wide range of models are available factory calibrated to specific ranges. The span and zero controls are for use when checking calibration. They are not intended for re-ranging to a significantly different span. The LCD display allows local indication of pressure.
Features- NEMA 4X rated enclosure provides protection in harsh environments permitting outdoor monitoring or in areas where dust and particulate matter exists
- Easy to read LCD display provides immediate local alerts allowing corrective action to be taken quicker to eliminate the problem from becoming widespread
- Zero and span controls provides easy calibration checks and shorter installation time to get device running and monitoring
1 - 12 of 20 Part Numbers
616W-10B-LCD
616W-2-LCD-NIST
- Pressure Range - Inches WC: 0 to 6
- Certificates - NIST Traceable Calibration Certificate
616W-20B-LCD-NIST
- Pressure Range - Inches WC: 0 to ± 10
- Certificates - NIST Traceable Calibration Certificate
616W-2M-LCD
616W-3-LCD-NIST
- Pressure Range - Inches WC: 0 to 10
- Certificates - NIST Traceable Calibration Certificate
616W-3M-LCD-NIST
- Pressure Range - kPa: 0 to 2.5
- Certificates - NIST Traceable Calibration Certificate
616W-4-LCD-NIST
- Pressure Range - Inches WC: 0 to 20
- Certificates - NIST Traceable Calibration Certificate
1 - 12 of 20 Part Numbers
Specifications
Brand
Accuracy
- ± 0.25 % of Full Scale at 25° C (77° F), Display Accuracy ± 0.5 %
Approvals & Certifications
- CE
Consumption
- 40 mA
Electrical Connectors
- 3-Wire Removable European Style Terminal Block or 16 to 26 AWG
Environmental Protection
- IP66
- NEMA 4X
Loop Resistance
- Current Output: 0-1250 ohms, Max.
- Voltage Output: Load Resistance 1 Kiloohm (Min.)
Media
- Air
- Non-Combustible, Compatible Gases
Mounting Position
- Any Orientation
NACE & NIST
- NIST Traceable Calibration Certificate
Output
- 0-10 Vdc, 3-Wire
- 0-5 Vdc
- 4-20 mA, 2-Wire
Power Requirement
- 10-35 Vdc (2-Wire)
- 17-36 Vdc
- Isolated 21.6-33 Vac (3-Wire)
Pressure Range
- Inches WC: 0 to 200
- kPa: 0 to 2.5
Process Connection Material
- Rubber
- Vinyl Tubing
Span & Zero Adjustments
- Push Button
Stability
- ± 1 % of Full Scale Per Year
Temperature Range
- -10° to 85° C (14° to 185° F)
Tube Connection
- 3/16” Tube
- Dual Size to Fit 1/8” & 3/16” I.D. Rubber or Vinyl Tubing
- Dust collection
- Outdoor HVAC
- Roof-top equipment