Yodify Product Library
Instantly add the MICRO-DCI 53SL5100B Single-Loop Controller and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
MICRO-DCI 53SL5100B Single-Loop Controller
Brand: MicroMod Automation & ControlsThe 53SL5100 features a library of four user-selectable control strategies for advanced single loop control. The high visibility dot matrix display shows process information in a clear and concise manner.
The 53SL5100 capabilities include: PID control, Ratio PID control, Auto/Manual Station, Analog Backup Station.
The instrument accepts two Analog inputs and provides one control output.
The 53SL5100 includes an RS-232 front configuration port and standard RS-458 DataLink serial communications at the rear terminations for connection to a PC and/or other Micro-DCI instruments on a network. The 53SL5 RetroPAK is also supported by the G3 Operator Panel DataLink interface.
53SL5100B is a direct replacement for the 53SL5100A. The standard displays, alarm reporting and alarm acknowledgement are identical, making the transition seamless for operators, and it can be mounted in the same panel cutout.
FeaturesSpecifications
Accuracy
- ± 0.1 % of Span
- ± 0.2 % of Span
Adjustment
- Push-Buttons
Ambient Temperature Range
- 4° to 52° C (40° to 125° F)
Approvals & Certifications
- FM
Approvals & Certifications
- ISA S71.01 1985
Bezel Material
- ULTEM 1000 (Polyetherimide Resin)
Communication
- Baud Rate: 300 & 9,600 Plus 14,400 & 28,800
- RS-422
- RS-485
Consumption
- AC Operation: 15 W, Max.
Display
- Bargraph Display, 48 x 96 Pixels
Electrical Contacts
- Normally Closed
- Normally Open
Enclosure Finish
- Baked Enamel
- Light Gray
- Painted with RAL 9002
Environmental Protection
- IP10
- IP20
- NEMA 1
Humidity
- 10 to 90 % Relative Humidity, Max.
Indication
- Alarm Status
Input
- 0-20 mA
- 2 mA at 4 Vdc - Contact Inputs
- Contact Recognition Level (Closed): 1 Vdc, Max.
- Contact Recognition Level (Open): 10 mA - Max.
- Contact Recognition Level (Open): 4-15 Vdc, Max.
- Signal Range: 0-5 Vdc or 1-5 Vdc - Analog Input
Input Impedance
- 1 Megaohm, Min.
Interval Time
- Integral: 0.02 to 200 minutes / Repeat or Manual Reset from 0 to 100 %
Materials of Construction
- Circuit Boards: Glass Epoxy
Output
- 30 Vdc, Max.
- 50 mA DC, Max.
- Available Power for Transmitters: 24-26 Vdc, 80 mA, Short Circuit Protected
- Ripple: 200 mV Peak-to-Peak, Max.
- Signal Range: 0-21.84 mA
- Slew Rate: 40 mA/second
Output Impedence
- Load Resistance: 0 to 750 ohms
Power Requirement
- 110-120 Vac, 50/60 Hz
- 120 Vac ± 10 %, 50/60 Hz
- 21-28 Vdc
- 220-240 Vac ± 10 %, 50/60 Hz
- 24 Vdc
Range
- Proportional Band: 2 to 100 % - Control Ranges
Resistance
- Permissible Contact: 100 ohms, Max.
Response Time
- Derivative: 0.01 to 8 minutes & OFF
- Open/Close Contact Duration: 0.05 second Min.
Sample Rate
- Analog / Contact: 50 milliseconds for All Inputs
Scan Time
- Program: 100 milliseconds
Temperature Effect
- ± 0.28 % Per 28° C (50° F) from Reference Temperature of 25° C (77° F)
Update Time
- 100 milliseconds