Yodify Product Library
Instantly add the Model NC230 Ao/CC-Link Converter and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
Model NC230 Ao/CC-Link Converter
Brand: Yokogawa Electric CorporationThe Model NC230 Ao/CC-Link converter receives input of digital values (0 to 10,000) from MELSEC (Mitsubishi Electric Corporation’s sequencer) via the CC-Link, and converts them to 16 (1-5 Vdc) Analog output signals.
The Analog output signals can be coupled with Yokogawa M&C’s signal converter - the JUXTA D Series – via a dedicated cable.
The NC230 is designed for either wall mounting or DIN-rail mounting.
Specifications
Accuracy
- ± 0.1 % of Full Scale
Ambient Temperature Range
- 0° to 50° C (32° to 122° F)
Channels
- 4 - Stations Occupied
Communication
- Baud Rate: 156 Kbps, 625 Kbps, 2.5 Mbps, 5 Mbps or 10 Mbps
Connection Pin-Out
- 14-Pin Plug-In Converter
Consumption
- Approximately 3.7 VA at (100 Vac)
- Approximately 5.8 VA at (240 Vac)
Distance
- 0 to 1,969 feet (0 to 600 metres): with Transmission Speed 625 Kbps
- 0 to 3,937 feet (0 to 1,200 metres): with Transmission Speed 156 Kbps
- 0 to 328.1 feet (0 to 100 metres): with Transmission Speed 10 Mbps
- 0 to 492.1 feet (0 to 150 metres): with Transmission Speed 5 Mbps
- 0 to 656.2 feet (0 to 200 metres): with Transmission Speed 2.5 Mbps
Enclosure, Body Material
- ABS Resin
Humidity
- 5 to 90 % Relative Humidity, Non-Condensing - Normal Operating Conditions
- 5 to 95 % Relative Humidity, Non-Condensing - Transport/Storage Conditions
Indication
- LED Indicator - RDY, RUN, ERR, SD & RD
Insulation Resistance
- 100 megaohms Min. at 500 Vdc between Any Two Terminals
Mounting
- DIN Rail Mounting
- Wall Mounted
Output
- Configration: 1-5 V Analog Output
Output Cycle
- Approximately 250 milliseconds / 16 Outputs
Power Supply
- 100-240 Vac (-15 %, 10 %), 50/60 Hz
Power Supply Effect
- ± 0.1 % of Full Scale, Max.
Storage Temperature
- -40° to 70° C (-40° to 158° F)
Supply Voltage
- 1,000 Vac/minute - Withstand Voltage between Output & CC-Link Output Terminals
- 100-120 Vac
- 2,000 Vac/minute - Withstand Voltage between Any Two Terminals, Among Terminals, Power Supply & Grounding Terminals
Switch Type
- Rotary Switches - 1 to 61 Remote Station Number Setting
Temperature Change
- 10° C (18° F)/hr, Max.
Temperature Effect
- ± 0.2 % of Full Scale, Max.