Yodify Product Library
Add the SonoMeter 1100 Ultrasonic Compact Energy Meter to your store or catalog  
Book Your Demo and See How
or create your store

SonoMeter 1100 Ultrasonic Compact Energy Meter

Brand: Danfoss

The SONOMETER™ 1100 is an ultrasonic static compact energy meter especially designed for heating, cooling or combined heating/cooling application in local and district energy systems. 

The SONOMETER™ 1100 as a compact energy meter consists of the following components:
  • Ultrasonic flow sensor
  • Calculator with integral hardware and software for measuring flow rate, temperature and energy consumption
  • Pair of temperature sensors
Features
  • 1st. approval in Europe for ultrasonic energy meter with dynamic range of qi/qp 1:250 in class 2 (qp 1.5 / 2.5 / 6 / 10 / 15 / 25 / 40 / 60 m³/hr)
  • Complete dynamic range: ≥ 1:1500
  • Lithium battery, 230 V AC or 24 V AC mains unit
  • Battery lifetime 11 years (16 years optional)
  • Unique free-beam principle
  • Improved service-friendly energy meter design
  • Housings with thread and flange (PN 16 / 25)
  • Can be configured for heating, cooling or combined heating/cooling application
  • Temperature range: 5° to 130° / 150° C
  • Overload temperature up to 150° C (qp = 0.6-2.5 m³/hr)
  • Swirl-free flow around reflector
  • Lower pressure loss
  • Robust stainless steel reflector
  • Insensitive to dirt
  • Available in nominal sizes qp 0.6 / 1.5 / 2.5 / 3.5 / 6 / 10 / 15 / 25 / 40 / 60 m³/hr
  • Approved according to MID in class 2 and 3, and PTB K 7.2 for cooling 
  • No calming sections necessary in the inlet and/or outlet (standard installation)
  • Power save mode
  • NOWA test capability
  • Remote reading via M-Bus, L-Bus, RS 232, RS485, Radio or optical interface
  • Integrated Radio 868 MHz, Open Metering Standard (OMS)
  • Individual remote reading (Automatic Meter Reading) with add on modules Plug & Play
  • 2 communication ports (e.g. M-Bus + pulss input)
  • Improved radio performance
  • Individual tariff functions
  • History memory for 24 months
  • Extensive diagnostic displays
  • Dedicated district energy application telegram
  • Suitable for Danfoss ECL Comfort controller and ECL 310 internet portal connection
  • IZAR@SET parameterization software on Windows basis guarantees optimum adaptation to the user's specific needs

Specifications

Brand

Adjustment

  • Push-Buttons

Ambient Temperature Range

  • -25° to 60° C (-13° to 140° F)

Approvals & Certifications

  • EN 13757-3
  • CE
  • MID: DE-10-MI004-PTB003, Class 2 & 3

Battery Life

  • 11-Years - A-Cell Lithium Battery
  • 16 Years - D-Cell Lithium Battery

BSP Connection

  • G 1" B Male
  • G 1-1/4" Male B
  • G 2" Male B
  • G 3/4" Male B

Cable Length

  • 0 to 32.80 ft (0 to 10 metres)

Communication

  • L-Bus
  • M-Bus
  • Radio OMS 868 MHz
  • RS-232
  • RS-485

Configuration

  • ZAR @ SET Software

Diagnostics

  • EEPROM Error

Display

  • 8-Digit LCD

Electrical Protection

  • Reverse Polarity

Environmental Protection

  • Calculator & Flow Sensor: IP54 (Heating)
  • IP65 (Heat/Cooling, Cooling)

Flange Size - 1-1/2” (DN 40)

  • 1-1/2" (DN 40) - PN 25

Flange Size - 1-1/4” (DN 32)

  • 1-1/4" (DN 32) - PN 25

Flange Size - 1” (DN 25)

  • 1" (DN 25) - PN 16
  • 1" (DN 25) - PN 25

Flange Size - 1/2” (DN 15)

  • 1/2" (DN 15) - PN 16
  • 1/2" (DN 15) - PN 25

Flange Size - 2-1/2” (DN 65)

  • 2-1/2" (DN 65) - PN 25

Flange Size - 2” (DN 50)

  • 2" (DN 50) - PN 25

Flange Size - 3” (DN 80)

  • 3" (DN 80) - PN 25

Flange Size - 3/4” (DN 20)

  • 3/4" (DN 20) - PN 16
  • 3/4" (DN 20) - PN 25

Flange Size - 4” (DN 100)

  • 4" (DN 100) - PN 25

Flow Rate

  • Extended Min.: 6 to 1,200 L/hr
  • Maximum
  • Nominal: 0.6 to 60 m³/hour
  • Standard Min.: 6 to 600 L/hr
  • Starting: 1 to 120 L/hr

Humidity

  • Maximum

Input

  • Sensor Current: Pt500 Peak < 2 mA
  • Sensor Current: RMS < 0.012 mA

Input Signal

  • Pulse

Length

  • 4.33" to 14.17" (110 to 360 mm)

Media

  • Circulation Water, pH: 7 to 10

Mounting Position

  • Horizontal
  • Vertical

Nominal Pressure

  • psi: 232.1 (kPa: 1,600, bar: 16)
  • psi: 362.6 (kPa: 2,500, bar: 25)

Operating Pressure

  • psi: 232.1 (kPa: 1,600, bar: 16) - Max.
  • psi: 362.6 (kPa: 2,500, bar: 25) - Max.

Operating Temperature

  • Ambient: 5° to 55° C (41° to 131° F) (> [35° C (95° F)], Max.

Output

  • 4-20 mA

Resistance

  • 2.2 MΩ - Input Resistance

Sensor, Probe Material

  • Brass
  • Stainless Steel

Sensor, Probe Type

  • Pt500 Ø 5.2 mm with 2-Wire Leads

Storage Temperature

  • Ambient: -25° to 60° C (-13° to 140° F) (> [35° C (95° F)], Max.

Supply Voltage

  • 230 Vac
  • 24 Vac
  • 3.6 Vdc (Lithium-Battery)

Temperature Range

  • Absolute Temperature: 1° to 180° C (33.8° to 356° F)
  • Cooling: 5° to 90° C (41° to 194° F)
  • Heating/Cooling: 5° to 105° C (41° to 221° F)
  • Heating: 5° to 150° C (41° to 302° F)

Terminal Voltage

  • 3 Vdc
Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team
show more