Yodify Product Library
Instantly add the WP1P Pulse Repeater and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
WP1P Pulse Repeater
Brand: Yokogawa Electric CorporationThe WP1P is a compact, front terminal connection type pulse repeater that converts pulses from voltage free contacts, open collector contacts, voltage, and current into isolated transistor switch pulses.
Features- With built-in 12 V or 24 V power supply for transmitter inputs
- Internal filter can be set to eliminate chattering (in cases where the input frequency range is up to 100 Hz, the pulse width is 3 ms or more)
- 2,000 VAC withstand voltage specifications are available upon requests
Specifications
Consumption
- 6 VA at 100 Vac - Power Consumption
- 60 mA at 24 Vdc - Current Consumption
Electrical Rating
- 30 mA - Max.
Enclosure, Body Material
- ABS Resin
Frequency
- 0 to 10,000 Hz - Input & Output Frequency
Humidity
- 5 to 90 % Relative Humidity, Non-Condensing
Input Signal
- 2-Wire & 3-Wire Typical Current Pulse
- 2-Wire & 3-Wire Typical Voltage Pulse
Insulation Resistance
- 100 megaohms or more at 500 Vdc between Input & Output, Input & Power Supply, Input & Ground, Output & Power Supply, Output & Ground & Power Supply & Ground
Mounting
- DIN Rail Mounting
- M4 Screw x 4 - Mounting Screw
- Rack-Mounted
- Wall Mounted
Operating Temperature
- 0° to 50° C (32° to 122° F)
Output Format
- Open Collector (Transistor Contact)
Power Supply
- 12 Vdc ± 10 % - Transmitter Power Supply
- 24 Vdc ± 10 % - Transmitter Power Supply
- 30 mA or Less - Transmitter Power Supply
- 85-264 Vac, 47 to 63 Hz
Power Supply Effect
- ± 0.1 % of Span or Less
Pulse Range
- 3 milliseconds or more - Pulse Width
- 60 µs - ON/OFF for Min. Input Pulse Width
Resistance
- 1 Kiloohm (Selectable with Switch Inside) - Internal Load Resistance (For Current Pulse)
- 100 kiloohms or more - Open Contact Resistance
- 15 kiloohms or more (For Contact or Voltage Pulse) - Input Resistance
- 200 ohms (Selectable with Switch Inside) - Internal Load Resistance (For Current Pulse) & Close Contact
- 510 ohms (Selectable with Switch Inside) - Internal Load Resistance (For Current Pulse)
Supply Voltage
- -1 to 8 Vdc - Voltage EL (Low Level)
- 1,500 Vac/minute - AC & DC Drive Withstand Voltage
- 24 Vdc ± 10 %
- 3-24 Vdc - Voltage EH (High Level)
- 500 Vac/minute between Output & Power Supply - Withstand Voltage for DC Drive
Time Constant
- 10 milliseconds Switch Selectable for Set or Release - Filter