Brand: VEGAApplication Area: The double channel VEGATRENN 152 is used for galvanic separation of intrinsically safe applications as well as the signal transmission of Ex approved 4 to 20 mA sensors in hazardous areas.
The separator is ideal in conjunction with signal conditioning instruments without own Ex approval.
The VEGATRENN 152 is suitable for bidirectional transmission of HART signals. The HART signal can be tapped via the front-mounted HART communication sockets or the terminals. The total transmissibility of HART signals allows unrestricted access to the sensor settings.
Features- Reliable separation of intrinsically safe and non-intrinsically safe circuits
- Simple installation, because no additional power supply is required (loop-powered)
- Simple mounting through carrier rail as well as detachable, coded terminals
Specifications
Brand
Ambient Temperature Range
- -20° to 60° C (-4° to 140° F)
Approvals & Certifications
- ATEX
- IEC
- SIL 2
Communication
- HART
Electrical Connectors
- 0.25 mm² AWG 23
- DIN EN 50022-60715
- Screw Terminal
Environmental Protection
- IP20
Processing Circuit
- Current without Connected Sensor: < 500 µA
- Operating Voltage: 15-35 Vdc
- Quantity: 2 x 4-20 mA / HART
- Residual Ripple of the Output Current: < 40 µA RMS
- Typical of Output: Passive
Sensor Circuit
- Input Typical: Active (Sensor Power Supply by Vegatrenn 152)
- Number of Sensors: 2 x 4-20 mA / HART (5 x HART Multidrop Per Channel)
- Off-Load Voltage: < 17 V
- Residual Ripple: < 20 mV RMS
- Short-Circuit Current: ≤ 27 mA
- Terminal Voltage: 16-10 V at 4-20 mA
- Voltage Loss with 15 V Operating Voltage at 20 mA: < 5 V