SERᴺᴱᵀ Sequence of Events Recorder

Brand: RIS - Scientific Columbus

Each SERᴺᴱᵀ product can work as a stand-alone system monitoring up to 48 digital inputs or multiple SERᴺᴱᵀ units can be networked together to form a larger system with all events consolidated in one chronological list as they occur.

A single WEB browser screen can display alarms from several SERᴺᴱᵀ units, making it easy to see the interaction between different equipment types or processes.

This flexibility makes it easy to analyze alarms across an entire site or even across multiple sites for a larger system view - much better than piecing together a list of alarms from multiple devices.
Features
  • Capture alarms to 1 msec precision across entire system
  • IEC-61850 compliant
  • 40,000 event storage per unit
  • WEB browser configuration and display of alarms
  • Network multiple units together for "big picture" view
  • Time sync via IRIG-B and NTP
  • Modbus, DNP, ASCII, BACnet protocols
  • LED indicator per alarm
  • Email notification
  • Meets new NERC SER requirements
  • 19" rack and surface mounting

Specifications

System Capacity

  • 16, 32, 48 Inputs per Unit

Field Contacts

  • Normally Open(N.O.) or Normally Closed (N.C.)
  • Wetted (Voltage Supplied) or Dry (Voltage Free) Contacts

Field Contact Voltage Range

  • 20-150 Vdc (Auto-Select)

Input Isolation

  • Each Input is Optically Isolated

Input Response

  • 1 millisecond to 60 seconds: Responds to Alarms as Quick as 1 msec or Alarms Lasting Up to 60 seconds

Contact De-Bounce

  • 0-60 seconds: Can Ignore Multiple Alarms Occurring Within 0-60 seconds from Initial Alarm

Delete From Scan

  • Automatic Mode: Adjustable from 0-255 Events per Minute. Automatically Resets itself
  • Manual Mode: Disable Any Input Manually

Alarm Legends

  • 32 Character Alarm Legend
  • 32 Character Normal Legend

LED Indicators

  • Alarm Status: Red LED per Input, Flash upon Alarm, Steady ON after Acknowledged via WEB Browser
  • Power, Status, Time Sync: Green LED for ”Normal” | Red LED for ”Abnormal

Outputs - Alarm Relay

  • 2 Form C (SPDT) Relays, Configurable via WEB Browser for: Common Alarm (Closes on any Alarm), Reflash Alarm (Pulses upon New Alarm), Horn Output, System Watchdog
  • Energized or De-Energized Operation

Outputs - Relay Ratings

  • 24 Vdc @ 2.0 amps
  • 110 Vdc @ 0.2 amps
  • 120 Vac @ 2.0 amps

Time Stamped Alarms

  • 1 msec Time Stamp Resolution
  • 40,000 Event Storage (per Unit)

Time Synchronization

  • IRIG-B Time Sync Input (Modulated or De-Modulated) Accurate to ± 1 msec Real Time
  • NTP Time Sync (via Ethernet) (Can Sync 1-3 IP Addressed Sources) Accuracy Based on Location of NTP Time Servers
  • Internal Crystal
  • Master Unit can Synchronize up to 24” Slave” Units via RS-485 (max 4,000 feet)

Communications

  • Serial Port: RS-232/485 Selectable | Modbus RTU, DNP3.0, Serial ASCII
  • Ethernet Port 10/100: DHCP or Fixed IP | Modbus TCP/IP, DNP3.0, BACNET, SNMP

WEB Server

  • Multi-user Support
  • Used for Configuration of Unit
  • Graphical and Text Display of Alarms
  • Can Combine Up to 25 Units on a Single WEB Browser (1,200 Alarms)
  • Acknowledgement of Alarms
  • Separate Screens for Active Alarms and Archived Event Log
  • Email Notification
  • Export to CSV
  • Printing of Alarms (Auto/Manual)
  • Multiple Levels of Security
  • HTTPS Encrypted Username/Password

Connections

  • Input / Output Terminals: Removable Barrier Terminal Block, Max. 12 GA (2.5 mm)

Mechanical

  • Surface Mounting: Din Rail/Panel: 17.8” (452 mm) x 6.8” (172 mm) x 2.3”(58 mm)
  • 19” Rack Mounting: 1U, 6.8” (172 mm) Depth
  • ISM Retrofits: Input Card Rack, Panel and Shelf

Power Requirements

  • Built-in Power Supplies: 24 Vdc Power Supply, AC/DC Power Supply
  • Can Use 1 Supply above or 2 for Redundancy/Dual Power Applications
  • Hot Swappable
  • Internal 24 Vdc Field Contact Voltage Supply
  • Maximum 24 watts
  • External Power Supply: System Power Supply, 125 Vdc Field Contact Voltage Supply

24 VDC Power Supply

  • 24 Vdc (19-29 Vdc)
  • Maximum 24 watts

AC/DC Power Supply

  • 85-300 Vac, 50/60 Hz
  • 100-300 Vdc

System Power Supply

  • Input: 48 Vdc (36-72 Vdc)
  • Output: 24 Vdc (Requires Internal 24 Vdc Power Supply Above)

125 VDC Field Contact Voltage Supply

  • Input: 90-265 Vac or 110-350 Vdc
  • Output: 125 Vdc

Environmental

  • Operating Temperature Range:-4° F to 140° F (-20° C to 60° C)
  • Humidity: 20-95 % RH
  • Surge Withstand: ANSIC37.90.1:2002
  • Fast Transient: IEC 61000-4-4
  • Surge Immunity: IEC 61000-4-5
  • EMI/RFI/ESD: IEC 61000-4-2,4-3,4-6,4-8, Emissions: CISPR11, Class A
  • Isolation: 2000 Vdc Power to Earth, 3150 Vdc Power to Inputs
  • Power Quality: IEC 61000-3-2 Harmonic Current | IEC 61000-3-3 Flicker Low Voltage | EN 61000-4-11 Voltage Variation