509 Direct Winding Transformer Monitor
Brand: Qualitrol CompanyMeasures transformer temperatures (direct winding, calculated winding, main tank oil, load tap changer, ambient).
Consolidates temperature information with alarm contacts and other information using customizable relays.
Accepts most third party sensors for other parameters.
Features- All the features of the Qualitrol 509 ITM
- Real time comparison of calculated and direct (‘hot spot’) winding temperatures for verification of transformer operation to OEM specification
- Up to 8 modular inputs of various types and up to 16 additional fiber optic temperature inputs via digital port when combined with optical hot spot modules
- Cooling monitor model (509-200) for advanced control or load tap changer monitor (509-300) model for detailed performance monitoring
Specifications
Brand
AC Voltage
- 0 to 140 & 0 to 360 Vac Ranges
Accuracy
- ± 0.5 % of Full Scale Input Range
Approvals & Certifications
- CE
- IEC 61000-6-1, 61000-6-2, 61010-1
- IEEE C37.90.1
Communication
- Fiber Optic Port: ST Connector
- Protocols: DNP 3.0 Level 1 Slave, Modbus RTU, ASCII, IEC 61850, IEC 60870
- RS-232 Port
- RS-485 Port
- USB Port
Data Logging
- Log Rate: Selectable from One Minute to 24 Hours
- Memory Capacity: Memory Size Capable of Storing 8 Parameters at One Hour Log Rate for over 19 Months. Shared 32 Mb non-volatile Flash Memory
- Number of Points: Logs up to 20 Parameters
Dielectric Isolation
- 2,500 Vac, 60 seconds to Ground
Direct Winding
- Fiber Optic Extension Cable: Polyurethane Sheath, Kevlar Reinforcement & PVC Liner
- Fiber Optic Probes: Neoptix T2® Fiber Optic Temperature Probe
Dry Switch Contact
- Measures A Dry Switch Contact as Either Open or Closed
Event Recording
- 2 Record Typicals: Time & Date or Complete System Snapshot
- Memory Capacity: Memory Size Capable of Storing 62,500 Time & Date Events, Shared 32 Mb non-volatile Flash Memory
- Number of Points: Logs up to 8 Events
Humidity
- 5 to 90 % Non-Condensing
Number of Inputs
- Accepts up to 8 Input Modules of Various, Configurable Typicals
Number of Output Relays
- 8 Programmable, 1 System Status, 1 for Heater Control
Operating Temperature
- -40° to 72° C (-40° to 161.6° F)
Output Current Loop
- Number of Loops: 4 Magnetically-Isolated Current Loops
- Typical: Customer Configurable in Software to Choose between 0-1 mA - Max.
- Typical: Customer Configurable in Software to Choose between 4-20 mA - Max.
Output Relay Type
- Form C, 10 A at 120/240 Vac, 10 A at 30 Vdc
Potentiometer
- Accepts Potentiometers from 5K to 15K
Power Consumption
- < 35 W
Power Supply
- Typical: Universal, 90-264 W Vac, 47-63 Hz, 40-290 Vdc
Powered Switch Contact
- Optically Isolated, Detects AC or DC from 120-250 V
RTD
- 10 ohm Copper & 100 ohm Platinum -40° to 120° C (-40° to 248° F)
Shock
- 10 G's Half-Sine, in Three Orthogonal Planes
Storage Temperature
- -50° to 85° C (-58° to 185° F)
Tap Position
- Detects Resistor Bridges of 40 to 1 K, up to 32 Resistors
User Interface
- Control: 8 Pushdown Buttons Located on Front Panel
- Display: 2 x 16-Character Backlit LCD
Vibration
- 60/120 Hz at 0.004” Displacement, 10/150 Hz at 1 G