Yodify Product Library
Instantly add the SCH-PSB Differential Pressure Switch and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
SCH-PSB Differential Pressure Switch
Brand: KOBOLD Instruments, IncAdjustable differential pressure switch for monitoring overpressure, vacuum and differential pressure of air or other non-combustible, non-aggressive gases.
With this pressure switch the switching pressure can be adjusted without a pressure gauge using a scaled adjustment knob. The switching differential can also be adjusted with a screwdriver.
Switching pressure specifications apply to vertical installation which is also the recommended position with pressure-pipe connections pointing downwards. If the switches are installed horizontally with AMP connection terminals uppermost, the switching values are approximately 20 Pa higher.
Specifications
Brand
Adjustment Type
- Scaled Adjustment Knob
Ambient Temperature Range
- 20° to 70° C (-4° to 158° F) (Limited from 85° to 70° C Due to PVC-Hose)
Cable Entry
- M16 x 1.5
Connectors
- Hose Ports
Cover Material
- Polystyrene
Diaphragm Material
- Silicone, Tempered at 200° C (392° F) Getempert
Electrical Connectors
- AMP Flat Plug 6.3 x 0.8 mm According to DIN 46244
- Cable Conduit with Cable Strain Relief
- Push-On Screw Terminal
Electrical Rating
- 1 A (0.4 A) at 250 Vac
Enclosure / Body Material
- Polyamide (PA)
Environmental Protection
- IP54
Maximum System Pressure
- psi: 1.45 (kPa: 10, bar: 0.1)
Media
- Air
- Non-Aggressive Gases
Mounting Position
- Fastening Lugs
Process Temperature
- -20° to 70° C (-4° to 158° F)
Set Point - Decreasing
- Inches WC: 0.08 to 4.015
- mbar: 0.2 to 10
- mmHg: 1.5 to 7.5
Set Point - Increasing
- Inches WC: 0.08 to 4.015
- mbar: 0.2 to 10
- mmHg: 1.5 to 7.5
Storage Temperature
- -40° to 70° C (-40° to 158° F) (Limited from 85° to 70° C Due to PVC-Hose)
Switch Type
- 1 or 2 Normally Closed or Normally Open
System Pressure
- bar: 0 to 0.1
- kPa: 0 to 10
- psi: 0 to 1.45
Temperature Range
- 70° C (158° F) - Max.
- Monitoring air filters and ventilators
- Monitoring industrial cooling-air circuits
- Overheating protection for fan heaters
- Monitoring flows in ventilation ducts
- Controlling air and fire-protection flaps
- Frost protection for heat exchangers