Yodify Product Library
Instantly add the Temperature Controller & Limiter Series 8146/5041-B25A and 50,000+ more product series to your store or catalog  
Book Your Demo and See How
or create your store

Temperature Controller & Limiter Series 8146/5041-B25A

Brand: R. STAHL AG

R. STAHL temperature controllers and limiters perform various tasks: They disconnect the system after an adjustable limit value is exceeded, whereby limiters remain disconnected, while controllers switch back on again when the permissible temperature is reached. 

Both switch off in the event of leak in the system. 

The set value can be seen from the outside through the inspection window.
Features
  • Disconnection in the event that a user-defined temperature is exceeded or fallen below, switching capacity up to 25 A
  • Permanent disconnection in the event of leak in the liquid-filled measuring system
  • Standardized versions available in Series 8146 Ex e enclosure. Customized solutions available on request.

1 - 7 of 7 Part Numbers
135997
135997
R. STAHL Dual Temperature Controllers
Disconnection in the event that a user-defined temperature is exceeded or fallen below, switching capacity up to 25 A

Permanent disconnection in the event of leak in the liquid-filled measuring system

Standardised versions available in Series 8146 Ex e enclosure. Customised solutions available on request.

Ambient Conditions

  • Ambient temperature - -40 °C ... +40 °C
  • Ambient temperature max. - +40 °C
  • Ambient temperature min. - -40 °C

Electrical Data

  • Measuring range max. - +300 °C
  • Measuring range min. - -20 °C
  • Rated operational current - 16.000 A
  • Rated operational voltage AC - 400.00 V

Explosion Protection

  • Application range (zones) - 1, 2, 21, 22
  • ATEX dust certificate - PTB 01 ATEX 1024
  • ATEX gas certificate - PTB 01 ATEX 1024
  • Certificates - ATEX (PTB), Brazil (ULB), Canada (CSA), Canada (FM), Canada / USA (UL), China (NEPSI), EAC (LPE), IECEx (PTB), India (PESO), Korea (KGS), Taiwan (ITRI), USA (FM)
  • Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C
  • Dust explosion protection IECEx - Ex tb IIIC T80 °C
  • Gas explosion protection ATEX - II 2 G Ex db eb IIC T6
  • Gas explosion protection IECEx - Ex db eb IIC T6
  • IECEX dust certificate - IECEx PTB 06.0090
  • IECEX gas certificate - IECEx PTB 06.0090

General

  • Functional Description - R. STAHL temperature controllers and limiters perform various tasks: They disconnect the system after an adjustable limit value is exceeded, whereby limiters remain disconnected, while controllers switch back on again when the permissible temperature is reached. Both switch off in the event of leak in the system. The set value can be seen from the outside through the inspection window.
  • Highlights - Disconnection in the event that a user-defined temperature is exceeded or fallen below, switching capacity up to 25 A Permanent disconnection in the event of leak in the liquid-filled measuring system Standardised versions available in Series 8146 Ex e enclosure. Customised solutions available on request.
  • Product Description - Dual temperature controllers
  • Product Type - 8146/5041-.
  • Title Product Variant Technical Data - 8146/5041-. double-temperature controler
  • WebCode - 8146K

Mechanical Data

  • Contacts - 1 change-over contact
  • Degree of protection (IP) - IP66
  • Enclosure material - Polyester resin, Glass fibre reinforced
  • Weight - 1.100 kg
136011
136011
Disconnection in the event that a user-defined temperature is exceeded or fallen below, switching capacity up to 25 A

Permanent disconnection in the event of leak in the liquid-filled measuring system

Standardised versions available in Series 8146 Ex e enclosure. Customised solutions available on request.
136030
136030
R. STAHL Temperature Limiter
Disconnection in the event that a user-defined temperature is exceeded or fallen below, switching capacity up to 25 A

Permanent disconnection in the event of leak in the liquid-filled measuring system

Standardised versions available in Series 8146 Ex e enclosure. Customised solutions available on request.

Ambient Conditions

  • Ambient temperature - -40 °C ... +40 °C
  • Ambient temperature max. - +40 °C
  • Ambient temperature min. - -40 °C

Components

  • Drilled holes - 1 x M20
  • Material of screw connections - Polyamide, black
  • Screw connections - 1 x M20 Ø 4 – 13 mm

Electrical Data

  • - temperature limiter
  • Measuring range max. - +300 °C
  • Measuring range min. - +50 °C
  • Rated operational current - 16.000 A
  • Rated operational voltage AC - 400.00 V

Explosion Protection

  • Application range (zones) - 1, 2, 21, 22
  • ATEX dust certificate - PTB 01 ATEX 1024
  • ATEX gas certificate - PTB 01 ATEX 1024
  • Certificate EAC - TS RU S-DE.AA71.B.00139
  • Certificates - ATEX (PTB), Brazil (ULB), Canada (CSA), Canada (FM), Canada / USA (UL), China (NEPSI), EAC (LPE), IECEx (PTB), India (PESO), Korea (KGS), Taiwan (ITRI), USA (FM)
  • Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
  • Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
  • Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
  • Gas explosion protection IECEx - Ex db eb IIC T6 Gb
  • IECEX dust certificate - IECEx PTB 06.0090
  • IECEX gas certificate - IECEx PTB 06.0090

General

  • Functional Description - R. STAHL temperature controllers and limiters perform various tasks: They disconnect the system after an adjustable limit value is exceeded, whereby limiters remain disconnected, while controllers switch back on again when the permissible temperature is reached. Both switch off in the event of leak in the system. The set value can be seen from the outside through the inspection window.
  • Highlights - Disconnection in the event that a user-defined temperature is exceeded or fallen below, switching capacity up to 25 A Permanent disconnection in the event of leak in the liquid-filled measuring system Standardised versions available in Series 8146 Ex e enclosure. Customised solutions available on request.
  • Product Description - Temperature limiter
  • Product Type - 8146/5041-STB25A/+50- +300°C
  • Title Product Variant Technical Data - 8146/5041-STB25A/+50- +300°C temp.lim.
  • WebCode - 8146K

Mechanical Data

  • Contacts - 1 change-over contact
  • Degree of protection (IP) - IP66
  • Enclosure material - Polyester resin, Glass fibre reinforced
  • Weight - 1.100 kg

Output

  • Output max. load AC - 1-2 400 V AC1 / 16 A, 1-4 400 V AC1 / 6.3 A
136043
136043
R. STAHL Temperature Controller
Disconnection in the event that a user-defined temperature is exceeded or fallen below, switching capacity up to 25 A

Permanent disconnection in the event of leak in the liquid-filled measuring system

Standardised versions available in Series 8146 Ex e enclosure. Customised solutions available on request.

Ambient Conditions

  • Ambient temperature - -45 °C ... +40 °C
  • Ambient temperature max. - +40 °C
  • Ambient temperature min. - -45 °C

Components

  • Drilled holes - 1 x M20
  • Material of screw connections - Polyamide, black
  • Screw connections - 1 x M20 Ø 4 – 13 mm

Electrical Data

  • - temperature controller
  • Measuring range max. - +50 °C
  • Measuring range min. - -20 °C
  • Rated operational current - 25.000 A
  • Rated operational voltage AC - 230.00 V

Explosion Protection

  • Application range (zones) - 1, 2, 21, 22
  • ATEX dust certificate - PTB 01 ATEX 1024
  • ATEX gas certificate - PTB 01 ATEX 1024
  • Certificate EAC - TS RU S-DE.AA71.B.00139
  • Certificates - ATEX (PTB), Brazil (ULB), Canada (CSA), Canada (FM), Canada / USA (UL), China (NEPSI), EAC (LPE), IECEx (PTB), India (PESO), Korea (KGS), Taiwan (ITRI), USA (FM)
  • Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
  • Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
  • Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
  • Gas explosion protection IECEx - Ex db eb IIC T6 Gb
  • IECEX dust certificate - IECEx PTB 06.0090
  • IECEX gas certificate - IECEx PTB 06.0090

General

  • Functional Description - R. STAHL temperature controllers and limiters perform various tasks: They disconnect the system after an adjustable limit value is exceeded, whereby limiters remain disconnected, while controllers switch back on again when the permissible temperature is reached. Both switch off in the event of leak in the system. The set value can be seen from the outside through the inspection window.
  • Highlights - Disconnection in the event that a user-defined temperature is exceeded or fallen below, switching capacity up to 25 A Permanent disconnection in the event of leak in the liquid-filled measuring system Standardised versions available in Series 8146 Ex e enclosure. Customised solutions available on request.
  • Product Description - Temperature controller
  • Product Type - 8146/5041-STW25A/-20- +50°C
  • Title Product Variant Technical Data - 8146/5041-STW25A/-20- +50°C temp.detec.
  • WebCode - 8146K

Mechanical Data

  • Contacts - 1 change-over contact
  • Degree of protection (IP) - IP66
  • Enclosure material - Polyester resin, Glass fibre reinforced
  • Weight - 1.000 kg

Output

  • Output max. load AC - 1-2 230 V AC1 / 25 A, 1-4 230 V AC1 / 2 A
136081
136081
R. STAHL Temperature Controller
Disconnection in the event that a user-defined temperature is exceeded or fallen below, switching capacity up to 25 A

Permanent disconnection in the event of leak in the liquid-filled measuring system

Standardised versions available in Series 8146 Ex e enclosure. Customised solutions available on request.

Ambient Conditions

  • Ambient temperature - -45 °C ... +40 °C
  • Ambient temperature max. - +40 °C
  • Ambient temperature min. - -45 °C

Components

  • Drilled holes - 1 x M20
  • Material of screw connections - Polyamide, black
  • Screw connections - 1 x M20 Ø 4 – 13 mm

Electrical Data

  • - temperature controller
  • Measuring range max. - +190 °C
  • Measuring range min. - 0 °C
  • Rated operational current - 25.000 A
  • Rated operational voltage AC - 230.00 V

Explosion Protection

  • Application range (zones) - 1, 2, 21, 22
  • ATEX dust certificate - PTB 01 ATEX 1024
  • ATEX gas certificate - PTB 01 ATEX 1024
  • Certificate EAC - TS RU S-DE.AA71.B.00139
  • Certificates - ATEX (PTB), Brazil (ULB), Canada (CSA), Canada (FM), Canada / USA (UL), China (NEPSI), EAC (LPE), IECEx (PTB), India (PESO), Korea (KGS), Taiwan (ITRI), USA (FM)
  • Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
  • Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
  • Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
  • Gas explosion protection IECEx - Ex db eb IIC T6 Gb
  • IECEX dust certificate - IECEx PTB 06.0090
  • IECEX gas certificate - IECEx PTB 06.0090

General

  • Functional Description - R. STAHL temperature controllers and limiters perform various tasks: They disconnect the system after an adjustable limit value is exceeded, whereby limiters remain disconnected, while controllers switch back on again when the permissible temperature is reached. Both switch off in the event of leak in the system. The set value can be seen from the outside through the inspection window.
  • Highlights - Disconnection in the event that a user-defined temperature is exceeded or fallen below, switching capacity up to 25 A Permanent disconnection in the event of leak in the liquid-filled measuring system Standardised versions available in Series 8146 Ex e enclosure. Customised solutions available on request.
  • Product Description - Temperature controller
  • Product Type - 8146/5041-STW25A/0- +190°C
  • Title Product Variant Technical Data - 8146/5041-STW25A/0- +200°C temp.detec.
  • WebCode - 8146K

Mechanical Data

  • Contacts - 1 change-over contact
  • Degree of protection (IP) - IP66
  • Enclosure material - Polyester resin, Glass fibre reinforced
  • Weight - 1.000 kg

Output

  • Output max. load AC - 1-2 230 V AC1 / 25 A, 1-4 230 V AC1 / 2 A
136119
136119
R. STAHL Temperature Controller
Disconnection in the event that a user-defined temperature is exceeded or fallen below, switching capacity up to 25 A

Permanent disconnection in the event of leak in the liquid-filled measuring system

Standardised versions available in Series 8146 Ex e enclosure. Customised solutions available on request.

Ambient Conditions

  • Ambient temperature - -40 °C ... +40 °C
  • Ambient temperature max. - +40 °C
  • Ambient temperature min. - -40 °C

Components

  • Drilled holes - 1 x M20
  • Material of screw connections - Polyamide, black
  • Screw connections - 1 x M20 Ø 4 – 13 mm

Electrical Data

  • - temperature controller
  • Measuring range max. - +300 °C
  • Measuring range min. - +50 °C
  • Rated operational current - 16.000 A
  • Rated operational voltage AC - 400.00 V

Explosion Protection

  • Application range (zones) - 1, 2, 21, 22
  • ATEX dust certificate - PTB 01 ATEX 1024
  • ATEX gas certificate - PTB 01 ATEX 1024
  • Certificate EAC - TS RU S-DE.AA71.B.00139
  • Certificates - ATEX (PTB), Brazil (ULB), Canada (CSA), Canada (FM), Canada / USA (UL), China (NEPSI), EAC (LPE), IECEx (PTB), India (PESO), Korea (KGS), Taiwan (ITRI), USA (FM)
  • Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
  • Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
  • Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
  • Gas explosion protection IECEx - Ex db eb IIC T6 Gb
  • IECEX dust certificate - IECEx PTB 06.0090
  • IECEX gas certificate - IECEx PTB 06.0090

General

  • Functional Description - R. STAHL temperature controllers and limiters perform various tasks: They disconnect the system after an adjustable limit value is exceeded, whereby limiters remain disconnected, while controllers switch back on again when the permissible temperature is reached. Both switch off in the event of leak in the system. The set value can be seen from the outside through the inspection window.
  • Highlights - Disconnection in the event that a user-defined temperature is exceeded or fallen below, switching capacity up to 25 A Permanent disconnection in the event of leak in the liquid-filled measuring system Standardised versions available in Series 8146 Ex e enclosure. Customised solutions available on request.
  • Product Description - Temperature controller
  • Product Type - 8146/5041-STW25A/+50- +300°C
  • Title Product Variant Technical Data - 8146/5041-STW25A/+50- +300°C temp.detec.
  • WebCode - 8146K

Mechanical Data

  • Contacts - 1 change-over contact
  • Degree of protection (IP) - IP66
  • Enclosure material - Polyester resin, Glass fibre reinforced
  • Weight - 1.000 kg

Output

  • Output max. load AC - 1-2 400 V AC1 / 16 A, 1-4 400 V AC1 / 6.3 A
269562
269562
R. STAHL Temperature Controller and a Temperature Limiter
Disconnection in the event that a user-defined temperature is exceeded or fallen below, switching capacity up to 25 A

Permanent disconnection in the event of leak in the liquid-filled measuring system

Standardised versions available in Series 8146 Ex e enclosure. Customised solutions available on request.

Ambient Conditions

  • Ambient temperature - -45 °C ... +40 °C
  • Ambient temperature max. - +40 °C
  • Ambient temperature min. - -45 °C

Components

  • Drilled holes - 2 x M20
  • Material of screw connections - Polyamide, black
  • Screw connections - 2 x M20 x 1.5

Electrical Data

  • - temperature controller
  • - temperature limiter
  • Max. measuring range 2 - +120 °C
  • Measuring range max. - +190 °C
  • Measuring range min. - 0 °C
  • Min. measuring range 2 - 0 °C
  • Rated operational current - 25.000 A
  • Rated operational voltage AC - 230.00 V

Explosion Protection

  • Application range (zones) - 1, 2, 21, 22
  • ATEX dust certificate - PTB 01 ATEX 1024
  • ATEX gas certificate - PTB 01 ATEX 1024
  • Certificate EAC - TS RU S-DE.AA71.B.00139
  • Certificates - ATEX (PTB), Brazil (ULB), Canada (CSA), Canada (FM), Canada / USA (UL), China (NEPSI), EAC (LPE), IECEx (PTB), India (PESO), Korea (KGS), Taiwan (ITRI), USA (FM)
  • Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C
  • Dust explosion protection IECEx - Ex tb IIIC T80 °C
  • Gas explosion protection ATEX - II 2 G Ex db eb IIC T6
  • Gas explosion protection IECEx - Ex db eb IIC T6
  • IECEX dust certificate - IECEx PTB 06.0090
  • IECEX gas certificate - IECEx PTB 06.0090

General

  • Functional Description - R. STAHL temperature controllers and limiters perform various tasks: They disconnect the system after an adjustable limit value is exceeded, whereby limiters remain disconnected, while controllers switch back on again when the permissible temperature is reached. Both switch off in the event of leak in the system. The set value can be seen from the outside through the inspection window.
  • Highlights - Disconnection in the event that a user-defined temperature is exceeded or fallen below, switching capacity up to 25 A Permanent disconnection in the event of leak in the liquid-filled measuring system Standardised versions available in Series 8146 Ex e enclosure. Customised solutions available on request.
  • Product Description - Temperature controller And a temperature limiter
  • Product Type - 8146/5051-STW25A+STB25A
  • WebCode - 8146K

Mechanical Data

  • Contacts - 1 change-over contact
  • Degree of protection (IP) - IP66
  • Enclosure material - Polyester resin, Glass fibre reinforced

Output

  • Output max. load AC - 1-2 230 V AC1 / 25 A, 1-4 230 V AC1 / 2 A
1 - 7 of 7 Part Numbers