AM Series Boilers
Brand: AERCOThe AM Series of commercial condensing boilers are essentially pre-packaged boiler plants giving you the reliability and redundancy of a multi-unit system in a single unit.
Each unit consists of between two and four individual modules, each with its own combustion chamber, burner, gas valve, and combustion controls and safeguards, all tied together to common water connections and assembled in a single enclosure.
This provides all the advantages of a larger boiler plant, including high turndown and multiple-unit redundancy, while still keeping installation costs down and operation simple.
Full front access means near-zero side clearance with no loss of serviceability when more than one million BTUs are necessary. Installations take up minimal space and remain simple to service.
Standard Modbus controls easily connect to Energy Management or Building Automation System.
The high efficiency of the AM series condensing boilers means less wasted heat and lower operating costs. In a condensing unit, lower fire rates return higher operating efficiencies.
By running multiple modules at low fire rather than one large unit at higher fire, the AM series ensures the installation is always running at its most efficient.
High efficiencies also mean lower flue temperatures and thus a range of venting options. All units can be vented in polypropylene, PVC, cPVC, or AL-294C vent materials. Available in 399, 500, 750 and 1000 MBH.
Features- Superior uptime reliability and increased life expectancy with well-designed, durable heat exchanger
- Efficiencies up to 98%
- Low installation and maintenance costs
- Built-in redundancy with multiple heating modules
- Small footprint
- Natural gas or propane
- Low NOx and CO emissions
- Turndown up to 20:1
- Easy access and maintenance
- Whisper quiet operation, even at full fire
- Direct or conventional vent with PVC, CPVC, Polypropylene or AL29-4C Materials
- Daisy-chain multiple units for applications over 1000 MBH
Specifications
Brand
Boiler Category
- IV
Gas Connections (NPT)
- AM 399: 1”
- AM 500: 1”
- AM 750: 1 1/4”
- AM 1000: 1 1/4”
Maximum Gas Pressure
- 13”
Minimum Gas Pressure
- 3”
Maximum Allowed Working Pressure
- 160 psi
Appliance Electrical Req: 120 V
- AM 399: 1.8 FLA
- AM 500: 2.5 FLA
- AM 750: 3.6 FLA
- AM 1000: 4.9 FLA
Water Connections (NPT)
- AM 399: 2”
- AM 500: 2”
- AM 750: 2 1/2”
- AM 1000: 2 1/2”
Minimum Water Flow (GPM) at Maximum Fire
- AM 399: 22
- AM 500: 24
- AM 750: 36
- AM 1000: 48
Maximum Water Flow (GPM)
- AM 399: 40
- AM 500: 40
- AM 750: 60
- AM 1000: 80
Water Pressure Drop at 30° F Rise (psi)
- AM 399: 5.6
- AM 500: 10.8
- AM 750: 10.0
- AM 1000: 11.7
Unit Water Volume: Gallons
- AM 399: 4
- AM 500: 4
- AM 750: 7
- AM 1000: 9
Thermal Modules
- AM 399: 2
- AM 500: 2
- AM 750: 3
- AM 1000: 4
Turndown or Operating Range
- AM 399: 8:1
- AM 500: 10:1
- AM 750: 15:1
- AM 1000: 20:1
Vent Size (Combustion Air & Vent)
- AM 399: 4”
- AM 500: 4”
- AM 750: 6”
- AM 1000: 6”
Vent Materials (as per Local Code)
- Can support PVC, CPVC , Polypropylene, or AL29-4C venting materials
Type of Gas
- Natural Gas or Propane
Temperature Control Range
- Boilers deliver 68°-180° F*, Water Heaters deliver 68°-180° F
Maximum Noise Level
- < 50 dBA
Condensate Production (gal/hr)
- AM 399: 3.84
- AM 500: 4.62
- AM 750: 9.96
- AM 1000: 9.24
Standard Listings and Approvals
- ASME , CSA, CSD-1, Mass. Approval, SCAQMD, NSF 372, AHRI