Yodify Product Library
Instantly add the Ex i Power Supply Series 8510 and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
Ex i Power Supply Series 8510
Brand: R. STAHL AGSeries 8510 Ex i power supply components as an isolator system for process automation and for connecting sensors, actuators and transmitters.
At intrinsically safe outputs, they provide a stable output voltage for field devices such as 3- or 4-conductor transmitters, solenoid values or controllers. Outputs and auxiliary power are galvanically separated from one another.
Features- Intrinsically safe power supply for field devices
- Stable voltages at intrinsically safe outputs
- Galvanic separation between output and auxiliary power
1 - 4 of 4 Part Numbers
145799
Intrinsically safe power supply for field devices
Stable voltages at intrinsically safe outputs
Galvanic separation between output and auxiliary power
Ambient Conditions
- Ambient temperature - -20 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -20 °C
Electrical Data
- Frequency - 48 ... 62 Hz
- Max. nominal current I N - 180.00 mA
- Max. nominal voltage - 10.40 V
- Min. nominal voltage - 9.40 V
- Min. open-circuit voltage U a - 9.40 V
- Number of channels - 1
- Open-circuit voltage U a max. - 10.50 V
- Rated insulation voltage U m AC - 250.00 V
- Voltage range AC - 20 - 28 V
- Voltage range DC - 18 - 35 V
Explosion Protection
- Application range (zones) - 1, 2
- ATEX firedamp certificate - DMT 00 ATEX E 073 U
- ATEX gas certificate - DMT 00 ATEX E 073 U
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), IECEx (BVS), USA (FM)
- Firedamp protection ATEX - I M2 Ex de I
- Firedamp protection IECEx - Ex de I
- Gas explosion protection ATEX - II 2 G Ex de IIC
- Gas explosion protection IECEx - Ex de IIC
- IECEx firedamp certificate - IECEx BVS 07.0029U
- IECEX gas certificate - IECEx BVS 07.0029U
General
- Functional Description - Series 8510 Ex i power supply components as an isolator system for process automation and for connecting sensors, actuators and transmitters. At intrinsically safe outputs, they provide a stable output voltage for field devices such as 3- or 4-conductor transmitters, solenoid values or controllers. Outputs and auxiliary power are galvanically separated from one another.
- Highlights - Intrinsically safe power supply for field devices Stable voltages at intrinsically safe outputs Galvanic separation between output and auxiliary power
- Product Description - Ex i Power Supply module
- Product Type - 8510/122-20-001-00
- Title Product Variant Technical Data - 8510/122-20-001-00 Power supply modul
- WebCode - 8510T
Mechanical Data
- Built-in device - 9143/10-114-200-10
- Built-in device milled - No
- Connection terminals finely-stranded max. - 6.00 mm²
- Connection terminals min. - 1.50 mm²
- Connection terminals of auxiliary contact finely stranded max. - 1.50 mm²
- Connection terminals of auxiliary contact min. - 0.75 mm²
- Connection terminals of auxiliary contact solid max. - 2.50 mm²
- Connection terminals solid max. - 10.00 mm²
- Degree of protection (IP) - IP20
- Depth - 168.000 mm
- Enclosure material - Epoxy resin
- Height - 130.000 mm
- Type of connection cable - Finely stranded, solid
- Weight - 1.600 kg
- Width - 70.000 mm
Safety Data
- Max. Current I o - 200.0 mA
- Max. Power P o - 2.280 W
- Max. Voltage U o - 11.40 V
145805
Intrinsically safe power supply for field devices
Stable voltages at intrinsically safe outputs
Galvanic separation between output and auxiliary power
Ambient Conditions
- Ambient temperature - -20 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -20 °C
Electrical Data
- Frequency - 48 ... 62 Hz
- Max. nominal current I N - 180.00 mA
- Max. nominal voltage - 10.40 V
- Min. nominal voltage - 9.40 V
- Min. open-circuit voltage U a - 9.40 V
- Number of channels - 1
- Open-circuit voltage U a max. - 10.50 V
- Rated insulation voltage U m AC - 250.00 V
- Voltage range AC - 85 - 230 V
Explosion Protection
- Application range (zones) - 1, 2
- ATEX firedamp certificate - DMT 00 ATEX E 073 U
- ATEX gas certificate - DMT 00 ATEX E 073 U
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), IECEx (BVS), USA (FM)
- Firedamp protection ATEX - I M2 Ex de I
- Firedamp protection IECEx - Ex de I
- Gas explosion protection ATEX - II 2 G Ex de IIC
- Gas explosion protection IECEx - Ex de IIC
- IECEx firedamp certificate - IECEx BVS 07.0029U
- IECEX gas certificate - IECEx BVS 07.0029U
General
- Functional Description - Series 8510 Ex i power supply components as an isolator system for process automation and for connecting sensors, actuators and transmitters. At intrinsically safe outputs, they provide a stable output voltage for field devices such as 3- or 4-conductor transmitters, solenoid values or controllers. Outputs and auxiliary power are galvanically separated from one another.
- Highlights - Intrinsically safe power supply for field devices Stable voltages at intrinsically safe outputs Galvanic separation between output and auxiliary power
- Product Description - Ex i Power Supply module
- Product Type - 8510/122-20-002-00
- Title Product Variant Technical Data - 8510/122-20-002-00 Ex i power supply
- WebCode - 8510T
Mechanical Data
- Built-in device - 9143/10-114-200-20
- Built-in device milled - No
- Connection terminals finely-stranded max. - 6.00 mm²
- Connection terminals min. - 1.50 mm²
- Connection terminals of auxiliary contact finely stranded max. - 1.50 mm²
- Connection terminals of auxiliary contact min. - 0.75 mm²
- Connection terminals of auxiliary contact solid max. - 2.50 mm²
- Connection terminals solid max. - 10.00 mm²
- Degree of protection (IP) - IP20
- Depth - 168.000 mm
- Enclosure material - Epoxy resin
- Height - 130.000 mm
- Type of connection cable - Finely stranded, solid
- Weight - 1.600 kg
- Width - 70.000 mm
Safety Data
- Max. Current I o - 200.0 mA
- Max. Power P o - 2.280 W
- Max. Voltage U o - 11.40 V
145811
Intrinsically safe power supply for field devices
Stable voltages at intrinsically safe outputs
Galvanic separation between output and auxiliary power
Ambient Conditions
- Ambient temperature - -20 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -20 °C
Electrical Data
- Frequency - 48 ... 62 Hz
- Max. nominal current I N - 35.00 mA
- Max. nominal voltage - 17.60 V
- Min. nominal voltage - 14.60 V
- Min. open-circuit voltage U a - 14.80 V
- Number of channels - 1
- Open-circuit voltage U a max. - 17.80 V
- Rated insulation voltage U m AC - 250.00 V
- Voltage range AC - 20 - 28 V
- Voltage range DC - 18 - 35 V
Explosion Protection
- Application range (zones) - 1, 2
- ATEX firedamp certificate - DMT 00 ATEX E 073 U
- ATEX gas certificate - DMT 00 ATEX E 073 U
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), IECEx (BVS), USA (FM)
- Firedamp protection ATEX - I M2 Ex de I
- Firedamp protection IECEx - Ex de I
- Gas explosion protection ATEX - II 2 G Ex de IIC
- Gas explosion protection IECEx - Ex de IIC
- IECEx firedamp certificate - IECEx BVS 07.0029U
- IECEX gas certificate - IECEx BVS 07.0029U
General
- Functional Description - Series 8510 Ex i power supply components as an isolator system for process automation and for connecting sensors, actuators and transmitters. At intrinsically safe outputs, they provide a stable output voltage for field devices such as 3- or 4-conductor transmitters, solenoid values or controllers. Outputs and auxiliary power are galvanically separated from one another.
- Highlights - Intrinsically safe power supply for field devices Stable voltages at intrinsically safe outputs Galvanic separation between output and auxiliary power
- Product Description - Ex i Power Supply module
- Product Type - 8510/122-20-003-00
- Title Product Variant Technical Data - 8510/122-20-003-00 Power supply module
- WebCode - 8510T
Mechanical Data
- Built-in device - 9143/10-187-050-10
- Built-in device milled - No
- Connection terminals finely-stranded max. - 6.00 mm²
- Connection terminals min. - 1.50 mm²
- Connection terminals of auxiliary contact finely stranded max. - 1.50 mm²
- Connection terminals of auxiliary contact min. - 0.75 mm²
- Connection terminals of auxiliary contact solid max. - 2.50 mm²
- Connection terminals solid max. - 10.00 mm²
- Degree of protection (IP) - IP20
- Depth - 168.000 mm
- Enclosure material - Epoxy resin
- Height - 130.000 mm
- Type of connection cable - Finely stranded, solid
- Weight - 1.470 kg
- Width - 70.000 mm
Safety Data
- Max. Current I o - 50.0 mA
- Max. Power P o - 0.935 W
- Max. Voltage U o - 18.70 V
201707
Intrinsically safe power supply for field devices
Stable voltages at intrinsically safe outputs
Galvanic separation between output and auxiliary power
Ambient Conditions
- Ambient temperature - -20 °C ... +40 °C
- Ambient temperature max. - +40 °C
- Ambient temperature min. - -20 °C
Electrical Data
- Frequency - 48 ... 62 Hz
- Max. nominal current I N - 140.00 mA
- Max. nominal voltage - 14.70 V
- Min. nominal voltage - 12.50 V
- Min. open-circuit voltage U a - 12.60 V
- Number of channels - 1
- Open-circuit voltage U a max. - 14.80 V
- Rated insulation voltage U m AC - 250.00 V
- Voltage range AC - 85 - 230 V
Explosion Protection
- Application range (zones) - 1, 2
- ATEX firedamp certificate - DMT 00 ATEX E 073 U
- ATEX gas certificate - DMT 00 ATEX E 073 U
- Certificates - Brazil (ULB), Canada (FM), IECEx (BVS), USA (FM)
- Firedamp protection ATEX - I M2 Ex de I
- Firedamp protection IECEx - Ex de I
- Gas explosion protection ATEX - II 2 G Ex de IIC
- Gas explosion protection IECEx - Ex de IIC
- IECEx firedamp certificate - IECEx BVS 07.0029U
- IECEX gas certificate - IECEx BVS 07.0029U
General
- Functional Description - Series 8510 Ex i power supply components as an isolator system for process automation and for connecting sensors, actuators and transmitters. At intrinsically safe outputs, they provide a stable output voltage for field devices such as 3- or 4-conductor transmitters, solenoid values or controllers. Outputs and auxiliary power are galvanically separated from one another.
- Highlights - Intrinsically safe power supply for field devices Stable voltages at intrinsically safe outputs Galvanic separation between output and auxiliary power
- Product Description - Ex i Power Supply module
- Product Type - 8510/122-20-014-00
- Title Product Variant Technical Data - 8510/122-20-014-00 Exi pwr. supp. mod.
- WebCode - 8510T
Mechanical Data
- Built-in device - 9143/10-156-160-20
- Built-in device milled - No
- Connection terminals finely-stranded max. - 6.00 mm²
- Connection terminals min. - 1.50 mm²
- Connection terminals of auxiliary contact finely stranded max. - 1.50 mm²
- Connection terminals of auxiliary contact min. - 0.75 mm²
- Connection terminals of auxiliary contact solid max. - 2.50 mm²
- Connection terminals solid max. - 10.00 mm²
- Degree of protection (IP) - IP20
- Depth - 168.000 mm
- Enclosure material - Epoxy resin
- Height - 130.000 mm
- Type of connection cable - Finely stranded, solid
- Weight - 1.600 kg
- Width - 70.000 mm
Safety Data
- Max. Current I o - 160.0 mA
- Max. Power P o - 2.496 W
- Max. Voltage U o - 15.60 V
1 - 4 of 4 Part Numbers