Yodify Product Library
Instantly add the i2P-100 Electro-Pneumatic Transducer and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
i2P-100 Electro-Pneumatic Transducer
Brand: FisherThe Fisher i2P-100 transducer is designed to meet environmental concerns, but optimized to provide maximum uptime.
Featuring dual compartments with an explosive-fluid seal to prevent natural gas from migrating to the electrical conduit. Additional advantages include corrosion resistance, tolerance to dirty supply, and vibration resistance.
The transducer receives a 4‐20 mA DC input signal and transmits a proportional user field‐configurable pneumatic output pressure to a final control element.
The pneumatic output range are typically 0.2 to 1.0 bar (3 to 15 psig), 0.4 to 2.0 bar (6 to 30 psig), and 0.14 to 2.3 bar (2 to 33 psi).
A typical application is in electronic control loops where the final control element is a control valve assembly that is pneumatically operated. The input signal and output pressure range of the transducer is indicated on the nameplate, attached to the housing.
Specifications
Brand
Accuracy
- ± 1.0 % of Full Scale Output Span
Adjustment Type
- Field Adjustable
Ambient Temperature Range
- -40° to 85° C (-40° to 185° F)
Approvals & Certifications
- ATEX
- CSA
- FM
- IEC Ex
- INMETRO
- NEPSI
Diaphragm Material
- Nitrile
Electrical Connectors
- 1/2” NPT
Enclosure Finish
- Polyurethane Paint
Enclosure, Body Material
- Low-Copper Aluminum
Environmental Protection
- IP54
- IP64
- IP66
- NEMA 3
- NEMA 4X
Frequency
- 3 dB at 3 Hz
Hysteresis
- 0.4 % of Full Scale Output Span
Input
- 4-20 mA
Mounting
- Pipestand
- Surface
- Yoke
NPT Connection
- 1/4” NPT Female
O-Ring Material
- Nitrile
Operating Temperature
- -40° to 85° C (-40° to 185° F)
Pressure Range
- bar: 0.14 to 2.3
- kPa: 13.79 to 227.5
- psig: 2 to 33
Supply Pressure Effect
- 0.2 % of Full Scale Output Span Per psi Supply Pressure Change
Temperature Effect
- ± 0.14 % Per °C (± 0.075 % Per °F) of Span
Vibration Effect
- < 1 % of Full Scale Output Span when Tested to ISA S75.13