Yodify Product Library
Instantly add the IDM T1+ Multi-Function Power System Monitor and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
IDM T1+ Multi-Function Power System Monitor
Brand: Qualitrol CompanyDigital Fault Recorder upgrade from IDM T1 to the new IDM T1+ / IDM+ architecture utilizing existing wiring.
Features- Improved measurement accuracy and reliability
- Utilize existing field wiring
- Phasor Measurement compliant to IEEE C37.118-2005
- Measure and analyze IEC 61000-4-30 Class A Power Quality
- Enable future expansion with advanced architecture and protocols
Specifications
Brand
Accuracy
- < 500 Nanoseconds when Locked to Internal GPS Module
- 0.2 % of Full Scale, Typical (Analog Channels)
Alarm Relays
- Quantity: 4 Relays
Analog Channels
- Quantity: 18 - Voltage or Current as Required
Clock
- Internal RTC Sync Via GPS, IRIG-B, IRIG-J
Communication
- Ethernet Port: 1 Rear (RJ45 or Fiber)
- Serial Port: 4 Ports (3 x RS-232 / 1 x RS-485)
Current
- 20/100 A AC (Analog Channels)
- 4-20 mA DC (Analog Channels)
Data Storage
- 8/16/32 GB CompactFlash
Digital Channels
- Quantity: 32 - Wide Input Range (48-250 Vdc)(Optional 24 Vdc) - Selectable De-Bounce
Front Panel
- LED Indicator: 9, Including Health, Communications, Clock Sync, Alarm & 3 Status, Battery Not Used
- MMI: LCD Display with 7 Button Keypad
Immunity
- IEEE , EN & IEC
Operating Temperature
- -5° to 50° C (23° to 122° F)
Power
- Maximum
Resolution
- 16-bits on Voltage & DC Analog Channels
- 20-bits on Current Analog Channels
Sample Rate
- 50 Hz Selectable - 25.6 / 12.8 / 6.4 / 3.2 / 1.6 kHz
- 60 Hz Selectable - 30.7 / 15.3 / 7.6 / 3.8 / 1.9 kHz
Storage Temperature
- -30° to 70° C (-22° to 158° F)
Supply Voltage
- 85-264 Vac, 47-440 Hz
- 90-370 Vdc
Voltage
- 12/120/240/480 Vdc (Analog Channels)
- 80 / 130 / 260 Vac (Analog Channels)