Yodify Product Library
Add the HART Termination Board Series 9196 to your store or catalog  
Book Your Demo and See How
or create your store

HART Termination Board Series 9196

Brand: R. STAHL AG

Used in combination with the HART multiplexer (9192), the 9196 series HART termination board enables the transmission of data using the HART protocol between field devices and an asset management system. 

The boards are very easy to install on DIN rails and can process 4 to 20 mA signals with HART FSK. If Ex i separation is necessary, this will require separate Ex i isolators.
Features
  • Cost- and space-saving system for HART communication
  • Different variants available with or without signal conversion
  • Easy to install on DIN rails

1 - 2 of 2 Part Numbers
160891
160891
R. STAHL HART Termination Board ISpac
Cost- and space-saving system for HART communication

different variants available with or without signal conversion

easy to install on DIN rails

Ambient Conditions

  • Ambient temperature - -20 °C ... +70 °C
  • Ambient temperature max. - +70 °C
  • Ambient temperature min. - -20 °C
  • Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Umgebungsbedingungen Hinweis - "The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide"."
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - 24 V DC
  • Nominal voltage - 24 V DC
  • Polarity reversal protection - yes
  • Voltage range residual ripple - ≤ 3,6 VSS

Components

  • Signal to the control system - 4 … 20 mA
  • Terminal - One terminal for field and control system side, detachable

Electrical Data

  • Connection HART-multiplexer - Yes
  • Connection isolators / Non-Ex field devices - via pluggable terminal; connected to the field device in parallel / automation system; in or output
  • I/O type - Any
  • Number of channels - 16
  • Type of signal - AI AO

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX gas certificate - BVS 03 ATEX E 213 X
  • Certificate EAC - TS RU S-DE.GB04.B.00353
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), SIL (exida), USA (FM)
  • Further information - see respective certificate and operating instructions
  • Gas explosion protection ATEX - II 3 G Ex nA IIC T4 Gc
  • Gas explosion protection EAC - 2 Ex nA IIC T4 Gc X
  • Gas explosion protection IECEx - Ex nA IIC T4 Gc
  • IECEX gas certificate - IECEx BVS 10.0042 X
  • Installation - in Zone 2, Division 2 and in the safe area
  • Installation in Division NEC 500 - (Class I, II, III) 2
  • Ship approval - CCS, DNVGL

General

  • Application - 2-, 3- or 4-conductor, Transmitter, positioner
  • Functional Description - Used in combination with the HART multiplexer (9192), the 9196 series HART termination board enables the transmission of data using the HART protocol between field devices and an asset management system. The boards are very easy to install on DIN rails and can process 4 to 20 mA signals with HART FSK. If Ex i separation is necessary, this will require separate Ex i isolators.
  • Highlights - Cost- and space-saving system for HART communication different variants available with or without signal conversion easy to install on DIN rails
  • Product Description - HART Termination Board ISpac
  • Product Type - 9196/16H-XX0-03c
  • Title Product Variant Technical Data - 9196/16H-XX0-03c HART-connection- board
  • WebCode - 9196A

Mechanical Data

  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.150 kg

Mounting / Installation

  • Mounting orientation - horizontal or vertical
  • Mounting type - DIN rail (NS35/15, NS35/7.5)

Output

  • Application - 2-, 3- or 4-conductor
249297
249297
R. STAHL HART Termination Board ISpac
Cost- and space-saving system for HART communication

different variants available with or without signal conversion

easy to install on DIN rails

Ambient Conditions

  • Ambient temperature - -20 °C ... +70 °C
  • Ambient temperature max. - +70 °C
  • Ambient temperature min. - -20 °C
  • Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Umgebungsbedingungen Hinweis - "The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide"."
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - 24 V DC
  • Nominal voltage - 24 V DC
  • Polarity reversal protection - yes
  • Voltage range residual ripple - ≤ 3,6 VSS

Components

  • Signal to the control system - 4 … 20 mA
  • Terminal - One terminal for field side, one terminal for control system side, detachable

Electrical Data

  • Connection automation system - via integrated screw terminal
  • Connection HART-multiplexer - Yes
  • Connection isolators / Non-Ex field devices - via pluggable terminal; connected to the field device in parallel / automation system; in or output
  • I/O type - Any
  • Number of channels - 16
  • Type of signal - AO AI

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX gas certificate - BVS 03 ATEX E 213 X
  • Certificate EAC - TS RU S-DE.GB04.B.00353
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), SIL (exida), USA (FM)
  • Further information - see respective certificate and operating instructions
  • Gas explosion protection ATEX - II 3 G Ex nA IIC T4 Gc
  • Gas explosion protection EAC - 2 Ex nA IIC T4 Gc X
  • Gas explosion protection IECEx - Ex nA IIC T4 Gc
  • IECEX gas certificate - IECEx BVS 10.0042 X
  • Installation - in Zone 2, Division 2 and in the safe area
  • Installation in Division NEC 500 - (Class I, II, III) 2
  • Ship approval - CCS, DNVGL

General

  • Application - 2-, 3- or 4-conductor, Transmitter, positioner
  • Functional Description - Used in combination with the HART multiplexer (9192), the 9196 series HART termination board enables the transmission of data using the HART protocol between field devices and an asset management system. The boards are very easy to install on DIN rails and can process 4 to 20 mA signals with HART FSK. If Ex i separation is necessary, this will require separate Ex i isolators.
  • Highlights - Cost- and space-saving system for HART communication different variants available with or without signal conversion easy to install on DIN rails
  • Product Description - HART Termination Board ISpac
  • Product Type - 9196/16H-XX0-05c
  • Title Product Variant Technical Data - 9196/16H-XX0-05c HART-connection board
  • WebCode - 9196A

Mechanical Data

  • Degree of protection (IP) - IP00
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.520 kg

Mounting / Installation

  • Mounting orientation - horizontal or vertical
  • Mounting type - DIN rail (NS35/15, NS35/7.5)

Output

  • Application - 2-, 3- or 4-conductor
1 - 2 of 2 Part Numbers