Yodify Product Library
Instantly add the ADMAG AXF Standard Clamp/Union/Butt Weld Magnetic and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
ADMAG AXF Standard Clamp/Union/Butt Weld Magnetic
Brand: Yokogawa Electric CorporationThe ADMAG AXF is the magnetic flow meter which has adopted the proven Dual Frequency Excitation. Moreover, the Enhanced Dual Frequency Excitation has been newly added to tackle more severe applications.
The AXF has user-friendly functions; such as an electrode adhesion level diagnosis function, infra-red switches which can be used for setting parameters without opening the case cover, ability to change the direction of electrical connection on the site.
Based on FOUNDATION™ Fieldbus specifications, AXF Fieldbus models offer more flexible instrumentation through a higher level communication capability and propose the cost reduction by multi-drop wirings with less cables. FOUNDATION™ Fieldbus is a registered trademark of Fieldbus FOUNDATION.
FeaturesUser-oriented Functionality
Fluid Adhesion Level Diagnosis
The amount of insulating material on the electrode is constantly monitored to determine when maintenance should be performed. An optional replaceable electrode is easy to remove and clean.
Flexible Electrical Connection Direction
The converter or the terminal box can be rotated in either direction to match the position of the electrical connections at the installation site.
Clear and Versatile Indications
The large, backlit full dot matrix LCD can display a variety of messages up to three lines in length. When an alarm condition occurs, a full description of the appropriate countermeasure is displayed.
Easy Setup
The most frequently used parameters are arranged in a group at the top of the display. Infrared switches enable the setting of parameters without opening the cover.
Operation Immediately after Installation
The AXF is shipped with the main parameters completely set and can go into operation as soon as installation and wiring are completed.
Expansion of Product Lineup
Improved Accuracy Specification
The standard accuracy is 0.35% of reading. Also available as an option is high accuracy calibration rated at 0.2% of reading.
Extra Small Size Flange Type
Flange types are now available in sizes as small as 2.5 mm.
Variety of Sanitary Connections
A wider variety of sanitary connections are now available, including Tri-Clamp, ISO, DIN and SMS.
Enhanced Performance
Enhanced Dual Frequency Excitation
The enhanced dual frequency excitation method is available as an option. This provides highly stable measurements involving high concentration slurries or low conductivity fluids.
Lower Minimum Conductivity
The newly designed AXF converter permits the measurement of fluids with conductivity as low as 1μS/cm depending on the nominal pipe size and fluid condition.
High-Speed Pulse Output
The maximum rate for high speed applications such as short-duration batch processes is now 10,000 pps (pulses per second).
Specifications
Accuracy
- 0.2 % of Reading - for High Accuracy Calibration
- 0.35 % of Reading - Standard Accuracy
Alarm
- Down-Scale: -10 %, 2.4 mA DC or Less
- Up-Scale: 110 %, 21.6 mA DC or more
Ambient Temperature Range
- -40° to 60° C (-40° to 140° F)
Approvals & Certifications
- Calibration
- Hydrostatic Pressure Test
- Liquid Penetration Test Certificate
- Material Certificate
- PMI
- Withstand Voltage Test Certificate
Approvals & Certifications
- ATEX Ex db E Ia IIC T6 to T4 Gb, EN 60079-0, EN 60079-1, EN 60079-7, EN 60079-11, EN 60079-31, DEKRA 15-ATEX-0029
- CE
- CSA - Certificate: 1481213, ANSI/ISA 12.27.01 (Process Sealing), (For CSA C22. 2 Series Explosion-proof for Class I, Div. 1, Groups A, B, C, D, Dust-Ignition-proof for Class II/III, Div. 1, Groups E, F, G, Intrinsically Safe (Electrodes) for Cla
- EMC - EN 61326-1 Class A, Table 2 (For use in Industrial Locations), EN 61326-2-3, EN 61326-2-5 (For FOUNDATION Fieldbus, PROFIBUS Only), EN 61000-3-2 Class A, EN 61000-3-3
- FM - 3600, 3610, 3615, 3810, ANSI/NEMA 250, Explosion-proof for Class I, Div. 1, Groups A, B, C, D, Dust-Ignition-proof for Class II/III, Division1, Groups E, F, G, Intrinsically Safe (Electrodes) for Class I, Div. 1, Groups A, B, C, D
- IEC Ex - 60079-0, 60079-1, 60079-7, 60079-11, 60079-31, Certificate: IEC Ex dEK 15.0022 X
- NAMUR NE43
- PED
- TIIS - Ex de[ia] IIC T4, Explosion-proof, Intrinsically Safety, Flameproof
Cable Length
- 330 feet (100 metres) - Max.
- 660 feet (201.2 metres) - Max.
Communication
- BRAIN
- FOUNDATION Fieldbus
- HART
- PROFIBUS PA
Conduit Connection
- G 3/4” Female
Consumption
- 12 W - for Integral Flowmeter & Remote Flowtube combined with AXFA14
- 20 W - for Remote Flowtube combined with AXFA11
Cover Material
- Aluminum Alloy - Converter Material & Terminal Box
Diagnostics
- Process, System, Setting Alarm & Warnings
Diameter
- 0.59” to 11.60” (15 to 294.7 mm) - Inner Diameter of Grounding Ring
- 1.50” to 13.70” (38 to 348 mm) - Outer Diameter for Effective Sealing
Display
- Full Dot Matrix LCD (32 x 132 Pixels)
Distance
- 6” (15 cm) or more - Distance from Power Line
- Up to 1.5 Kilometers, when Polyethylene Insulated PVC-sheathed Cables (CEV Cables) are used - Communication Distance
Duty Cycle
- 50 % - Pulse Width
Electrical Connectors
- ANSI 1/2” NPT Female
- ISO M20 x 1.5 Female
- JIS G 1/2” Female
- M4 Screw Terminal - Terminal Connection
Electrical Protection
- Lightning Protection
Electrical Rating
- 200 mA (ON) at 30 Vdc (OFF) - Contact Capacity for One Pulse, One Alarm & Two Status Output Signals
Enclosure Finish
- Coated in Black (Munsell N1.5 or its Equivalent)
- Coated in Jade Green (Munsell 7.5 BG 4/1.5 or its Equivalent)
- Coated in Metallic Silver
- Corrosion-Resistant Coating - Case & Cover
- Epoxy Resin Coating
- High Anti-Corrosion Coating
- Mint Green Paint (Munsell 5.6 BG 3.3/2.9 or its Equivalent) - Coating Color
Enclosure, Body Material
- Aluminum Alloy - Converter Material (Case)
- JIS SUS304 (AISI 304 Stainless Steel / EN 1.4301 Equivalent) - for 1” to 5” (25 to 125 mm)
- Stainless Steel, JIS SCS11 Equivalent - for 0.1” to 0.5” (2.5 to 15 mm)
Environmental Protection
- IP66 - for General-purpose Use / Sanitary Typical / TIIS Flameproof Typical
- IP67 - for General-purpose Use / Sanitary Typical / TIIS Flameproof Typical
- IP68 - for Submersible Typical (Only for Remote Flowtube)
- NEMA 4X
Excitation Voltage
- 140 V, Max.
- 170 V, Max.
Flange Material
- JIS SCS13 (EN 1.4308 Equivalent) - Mini-Flange & Pipe Material
- JIS SUS304 or SUSF304 (304 Stainless Steel) - Mini-Flange, Pipe Material & Tag Plate
Fluid
- 1 µS/cm or Larger, for Size 0.5” to 5” (15 to 125 mm) - Fluid Conductivity
- 3 µS/cm or Larger, for Size 6” to 16” (150 to 400 mm) - Fluid Conductivity
- 5 µS/cm or Larger, for Size 0.1” to 0.4” (2.5 to 10 mm) - Fluid Conductivity
- Gas
- Liquid
Gasket Material
- Silicone Rubber - Special Gaskets
- Viton (Acid-Resistant & Alkali-Resistant) - Special Gaskets
Humidity
- 0 to 100 % - Ambient Humidity
Input Impedance
- 10 kiloohms or more at 2.4 kHz - Input Impedance of Communicating Device
Input Signal
- Dry Contact
Insulation Resistance
- 100 megaohms at 500 Vdc - between Power Supply Terminals & Ground Terminal, between Power Supply Terminals & Input/Output Terminals (Integral Flowmeter), between Excitation Current Terminal & Signal / Common Terminals, between Signal Terminals, between S
- 20 megaohms at 100 Vdc - between Ground Terminal & Input/Output Terminals, between Input/Output Terminals (Integral Flowmeter)
Load
- 0.22 µF or Less - Load Capacitance
- 3.3 MH or Less - Load Inductance
Mounting Position
- Vertical
O-Ring Material
- Fluororubber, for Replaceable Electrode Typical
Operating Voltages
- 20.4-28.8 Vac - Integral Flowmeter
- 20.4-28.8 Vdc - Integral Flowmeter
- 80-264 Vac - Integral Flowmeter
- 90-130 Vdc - Integral Flowmeter
Output
- 1.6 Vdc, 200 mA - Max.
- 30 Vdc, Max.
- 4-20 mA DC
Output Format
- Alarm Output
- Current Output
- Pulse Output
Power Supply
- 100-120 Vdc - Integral Flowmeter
- 100-240 Vac, 47 to 63 Hz - Integral Flowmeter
- 24 Vac, 50/60 Hz - Integral Flowmeter
- 24 Vdc - Integral Flowmeter
- Maximum
Pressure Range
- psi: -14.5 to 580 (MPa: -0.1 to 4, bar: -1 to 40) - Fluid Pressure
Process Temperature
- -40° to 110° C (-40° to 230° F)
Pulse Range
- 0.0001 to 10,000 Pulse/second - Pulse Output Rate
- 0.05 to 100 milliseconds - Pulse Width
Repeatability
- ± 0.05 % of Rate ± 0.5 mm/sec (V< 1 m/sec (3.3 feet/sec))
- ± 0.1 % of Rate (V≥ 1 m/sec (3.3 feet/sec))
Resistance
- 10 ohms or Less - Grounding Resistance for JIS Class C & JIS Class A
- 100 kiloohms or more (OFF) - Load Resistance
- 100 ohms or Less - Grounding Resistance
- 200 ohms or Less (ON) - Load Resistance
- 250 to 450 ohms (Including Cable Resistance) - Load Resistance for BRAIN Communication
- 250 to 600 ohms (Including Cable Resistance) - Load Resistance for HART Communication
- 750 ohms, Max.
Rotation
- 180° Rotated Converter (or Terminal Box) to Change the Direction of Electrical Connection
- 90° Rotated Converter (or Terminal Box) to Change the Direction of Electrical Connection
- -90° Rotated Converter (or Terminal Box) to Change the Direction of Electrical Connection
Temperature Range
- 120° C (248° F) - Max.
Time Constant
- 0.1 to 200 seconds (63 % Response) - Damping Time Constant
Tri-Clamp Connection
- 1” Tri-Clamp
- 1/2” Tri-Clamp
- 1-1/2” Tri-Clamp
- 1-1/4” Tri-Clamp
- 2” Tri-Clamp
- 2-1/2” Tri-Clamp
- 3” Tri-Clamp
- 4” Tri-Clamp
- 5” Tri-Clamp
Welded Connection
- 1” Butt Weld End
- 1/2” Butt Weld End
- 1-1/2” Butt Weld End
- 1-1/4” Butt Weld End
- 2” Butt Weld End
- 2-1/2” Butt Weld End
- 3” Butt Weld End
- 4” Butt Weld End
- 5” Butt Weld End
Wetted Materials
- Fluorocarbon PFA - Lining
- JIS SUS316L (316L Stainless Steel) - Electrode Material
Documentation
Product Manuals
- ADMAG AXF Series Foundation Fieldbus Communication Type Magnetic Flowmeter pdf 791 KB
- AXF Magnetic Flowmeter Installation Manual ATEX and IECEx Explosion Proof Type pdf 643 KB
- AXF Magnetic Flowmeter Integral Flowmeter/ Remote Flowtube [Hardware Edition] pdf 480 KB
- AXF Magnetic Flowmeter Integral Flowmeter/ Remote Flowtube [Hardware Edition] pdf 3.3 MB
- AXF PROFIBUS PA Communication Type Magnetic Flowmeter pdf 5.3 MB
- AXF Series Magnetic Flowmeter Installation Manual pdf 547 KB
- AXF Series Magnetic Flowmeter Installation Manual pdf 6.9 MB
- AXF Series Magnetic Flowmeter Installation Manual ATEX and IECEx Explosion Proof Type pdf 2.4 MB
- AXF Series Magnetic Flowmeter Installation Manual FOUNDATION Fieldbus Communication Type and PROFIBUS PA Communication Type pdf 876 KB
- AXF Verification Tool pdf 10.7 MB
- AXFA11G Magnetic Flowmeter Remote Converter pdf 1.4 MB
- AXFA14G/C Magnetic Flowmeter Remote Converter [Hardware Edition/Software Edition] pdf 59 KB
- AXFA14G/C Magnetic Flowmeter Remote Converter [Hardware Edition/Software Edition] pdf 1.8 MB
Brochure
Product Drawing
- AXF Integral Flowmeter/Remote Flowtube AXF Standard (Sanitary Type for Butt Weld) pdf 480 KB
- AXF Integral Flowmeter/Remote Flowtube AXF Standard (Sanitary Type for Clamp Connection) pdf 484 KB
- AXF Integral Flowmeter/Remote Flowtube AXF Standard (Sanitary Type for Union Connection) pdf 490 KB
- AXF Integral Flowmeter/Remote Flowtube Replacement Model for Earlier ADMAG or ADMAG AE (ANSI Flange) pdf 94 KB
- AXF Integral Flowmeter/Remote Flowtube Replacement Model for Earlier ADMAG or ADMAG AE (DIN Flange) pdf 95 KB
- AXF Integral Flowmeter/Remote Flowtube Replacement Model for Earlier ADMAG or ADMAG AE (JIS Flange) pdf 120 KB
- AXF Integral Flowmeter/Remote Flowtube Replacement Model for Earlier ADMAG or ADMAG AE (Wafer) pdf 91 KB
- AXF Integral Flowmeter/Remote Flowtube Replacement Model for Earlier ADMAG or ADMAG AE (Wafer) pdf 92 KB
- AXF Integral Flowmeter/Remote Flowtube Replacement Model for Earlier ADMAG or ADMAG AE (Wafer) pdf 94 KB
- AXF Magnetic Flowmeter Remote Converter (AM11 Replacement Bracket) pdf 48 KB
- AXF002, AXF005, AXF010 AXF Integral Flowmeter/Remote Flowtube AXF Standard (JIS/DIN Flange 10mm Diameter) pdf 96 KB
- AXF002, AXF005, AXF010 AXF Integral Flowmeter/Remote Flowtube AXF Standard (Union Joint) pdf 97 KB
- AXF002, AXF005, AXF010, AXF015 AXF Integral Flowmeter/Remote Flowtube pdf 95 KB
- AXF002, AXF005, AXF010, AXF015 AXF Integral Flowmeter/Remote Flowtube AXF Standard (ANSI/DIN/JPI Flange) pdf 97 KB
- AXF002, AXF005, AXF010, AXF015 AXF Integral Flowmeter/Remote Flowtube AXF Standard (JIS Flange) pdf 96 KB
- AXF015 AXF Integral Flowmeter/Remote Flowtube AXF Standard (Wafer) pdf 94 KB
- AXF025, AXF032, AXF040, AXF050 AXF Integral Flowmeter/Remote Flowtube AXF Standard (ANSI/JPI Flange) pdf 97 KB
- AXF025, AXF032, AXF040, AXF050 AXF Integral Flowmeter/Remote Flowtube AXF Standard (DIN/AS Flange) pdf 95 KB
- AXF025, AXF032, AXF040, AXF050 AXF Integral Flowmeter/Remote Flowtube AXF Standard (JIS Flange) pdf 96 KB
- AXF025, AXF032, AXF040, AXF050, AXF065, AXF080, AXF100, AXF125 AXF Integral Flowmeter/Remote Flowtube AXF Standard (Wafer) pdf 92 KB
- AXF025, AXF040, AXF050, AXF080, AXF100 AXF Integral Flowmeter/Remote Flowtube AXF Standard (Wafer) pdf 90 KB
- AXF065, AXF080, AXF100, AXF125 AXF Integral Flowmeter/Remote Flowtube AXF Standard (ANSI/JPI Flange) pdf 95 KB
- AXF065, AXF080, AXF100, AXF125 AXF Integral Flowmeter/Remote Flowtube AXF Standard (DIN/AS Flange) pdf 93 KB
- AXF065, AXF080, AXF100, AXF125 AXF Integral Flowmeter/Remote Flowtube AXF Standard (JIS Flange) pdf 95 KB
- AXF150, AXF200 AXF Integral Flowmeter/Remote Flowtube AXF Standard (ANSI/JPI Flange) pdf 110 KB
- AXF150, AXF200 AXF Integral Flowmeter/Remote Flowtube AXF Standard (DIN/AS Flange) pdf 111 KB
- AXF150, AXF200 AXF Integral Flowmeter/Remote Flowtube AXF Standard (JIS Flange) pdf 110 KB
- AXF150, AXF200 AXF Integral Flowmeter/Remote Flowtube AXF Standard (Wafer) pdf 89 KB
- AXF150, AXF200, AXF250, AXF300 AXF Integral Flowmeter/Remote Flowtube AXF Standard (Wafer) pdf 93 KB
- AXF250, AXF300, AXF350, AXF400 AXF Integral Flowmeter/Remote Flowtube AXF Standard (ANSI/JPI Flange) pdf 93 KB
- AXF250, AXF300, AXF350, AXF400 AXF Integral Flowmeter/Remote Flowtube AXF Standard (DIN/AS Flange) pdf 93 KB
- AXF250, AXF300, AXF350, AXF400 AXF Integral Flowmeter/Remote Flowtube AXF Standard (JIS Flange) pdf 93 KB
- AXFA11G - AXF Magnetic Flowmeter Remote Converter pdf 58 KB
- AXFA14G/C - AXF Magnetic Flowmeter Remote Converter pdf 63 KB
- Magnetic Flowmeter Dedicated Signal Cable For the ADMAG AXF Series pdf 28 KB
Specification
- ADMAG AXF Series General Specifications pdf 108 KB
- ADMAG Series Magnetic Flowmeter List of RoHS (2011/65/EU) Directive Compliant Products pdf 276 KB
- AXF PROFIBUS PA Communication Type Magnetic Flowmeter pdf 113 KB
- AXFA11G Magnetic Flowmeter Remote Converter pdf 303 KB
- AXFA14G/C Magnetic Flowmeter Remote Converter pdf 238 KB