Yodify Product Library
Instantly add the L8124A1007/U Triple Aquastat Relay for Oil Applications, Vertical Case, 1.5" Insulation Depth and 50,000+ more product series to your store or catalog  
Book Your Demo and See How
or create your store

L8124A1007/U Triple Aquastat Relay for Oil Applications, Vertical Case, 1.5" Insulation Depth

Brand: Resideo Technologies Inc

Immersion-type controllers that combine high limit protection with low limit and circulator control in forced hydronic heating systems, including domestic hot water service.
Features
  • Immersion-type Controllers that Combine High Limit Protection with Low Limit and Circulator Control in Forced Hydronic Heating Systems.
  • Provide Multizone Control by Using a Separate Circulator and R845 Relay for Each Zone.
  • Include Diaphragm Powerhead and Micro Switch™ Assembly that Respond to Temperature Changes in Boiler Water.
  • Mount Directly to Boiler.
  • Select Models Include Large Transformers and Extra Terminals for Supplying Power to Low Voltage Zone Valves.
  • Require 24 Vac Thermostat with Heat Anticipator Set At 0.2 A - Plus Current Draw of Gas Valve on L8124E.
  • Tradeline Models Include Tube of Heat Conductive Compound and Range Stops.

1 - 1 of 1 Part Numbers
L8124A1007/U
L8124A1007/U
Triple Aquastat Relay for Oil Applications, Vertical Case, 1.5" Insulation Depth
1 - 1 of 1 Part Numbers

Specifications

Dimensions

  • 6-1/8 in. high x 4-3/8 in. wide x 3-1/16 in. deep
  • 156 mm high x 111 mm wide x 78 mm deep

Maximum Safe Operating Pressure

  • 200 psi on outside of immersion well, 100 psi on capsule if inserted directly.
  • 1378 kPa on outside of immersion well, 690 kPa on capsule if inserted directly.

Temperature Range

  • Maximum: 150 °F at switches; 265 °F at sensing element
  • Maximum: 66 °C at switches; 129 °C at sensing element

Includes

  • No Well

Mounting

  • Vertical Mount

Approvals, Underwriters Laboratories Inc.

  • UL Listed (models with well): File No. MP466, Guide No. MBPR; UL Component Recognized (models without well): File No. MP466, Guide No. MBPR2

Approvals, Canadian Standards Association

  • Certified: File No. LR1620, Guide No. 400-E-O

Operating Humidity Range

  • 0 to 95% RH, non-condensing

Voltage

  • 120 Vac

Operating Temperature Range

  • High Limit: 130 °F to 240 °F adjustable; Low Limit: 110 °F to 220 °F adjustable
  • High Limit: 54 °C to 116 °C adjustable; Low Limit: 43 °C to 104 °C adjustable

Differential Temperature

  • High limit: 10 °F fixed; low limit: 10 to 25 °F adj.

Insulation Depth

  • 1-1/2 in.
  • 38 mm

Electrical Ratings, Burner

  • At Full Load - 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; At Locked Rotor - 44.4 A @ 120 Vac: 22.2 A @ 240 Vac

Electrical Ratings, Circulator

  • At Full Load - 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; At Locked Rotor - 44.4 A @ 120 Vac: 22.2 A @ 240 Vac

  • High Limit Protection, Low Limit and Circulation Control