Digital Output Loop Powered Series 9176

Brand: R. STAHL AG

9176 series binary outputs issue binary signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices do not require a separate auxiliary power supply as they are powered by the control circuit. 

The intrinsically safe outputs are galvanically separated from the inputs. The two-channel variants are characterized by galvanically separated channels.
Features
  • Comprehensive portfolio to cater for all characteristics
  • Two-channel variants reduce the amount of space required
  • Can be used up to SIL 3 (IEC/EN 61508)

1 - 12 of 20 Part Numbers
222160
222160
R. STAHL Digital Output Loop Powered Ex I Field Circuit
Comprehensive portfolio to cater for all characteristics

two-channel variants reduce the amount of space required

can be used up to SIL 3 (IEC/EN 61508)

Ambient Conditions

  • Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
  • Ambient temperature max. - +70 °C
  • Ambient temperature max. note - Single device
  • Ambient temperature max. note 2 - Group assembly
  • Ambient temperature max.2 - +60 °C
  • Ambient temperature min. - -20 °C
  • Ambient temperature min. 2 - -20 °C
  • Ambient temperature min. note - Single device
  • Ambient temperature min. note 2 - Group assembly
  • Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Umgebungsbedingungen Hinweis - The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide".
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - without
  • Auxiliary power power input - 0,3 W+ (IA x 15 mW / mA)
  • Polarity reversal protection - yes
  • Undervoltage monitoring - No

Electrical Data

  • Number of channels - 1

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - BVS 04 ATEX E 075 X
  • ATEX gas certificate - BVS 04 ATEX E 075 X
  • Certificate EAC - TS RU S-DE.GB04.B.00353
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), Korea (KTL), SIL (exida), USA (FM)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection EAC - [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
  • Gas explosion protection EAC - 2 Ex nA [ia Ga] IIC T4 Gc X
  • Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx BVS 13.0012 X
  • IECEX gas certificate - IECEx BVS 13.0012 X
  • Installation in Division NEC 500 - (Class I, II, III) 2
  • Ship approval - CCS, DNVGL

Galvanic isolation

  • Galvanic isolation Ex i output to input - 1,5 kV AC
  • Galvanic isolation input to input - 350 V AC
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 50178

General

  • Functional Description - 9176 series binary outputs issue binary signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are galvanically separated from the inputs. The two-channel variants are characterised by galvanically separated channels.
  • Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
  • Product Description - Digital output loop powered Ex i field circuit
  • Product Type - 9176/10-12-00s
  • Title Product Variant Technical Data - 9176/10-12-00s Digital output l.p.
  • WebCode - 9176A

Input

  • Control Power P E - 0.3 W+ (I A x 15 mW / mA) (with I A = max. required output current)
  • Input - In accordance with EN 61131-2
  • Input voltage for OFF - 0 - 5 V
  • Input voltage for ON - 18.0 - 31.2 V

Mechanical Data

  • Connection cross-section - 0.2-2.5 mm² flexible 0.2-2.5 mm² rigid 0.25-2.5 mm² flexible core end sleeve
  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 17.60 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.170 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 0.2 mm²
  • Conduct cross-section flexible max. - 2.5 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Screw terminal
  • Mounting position - vertical horizontal
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Internal Resistance R i - 150.00 Ω
  • LFD relay - No
  • Max. output current I a max - 60.00 mA
  • Output internal resistiance R i - 150.00 Ω
  • Output open circuit voltage U a - 10,00 V
  • Output residual ripple - < 100 mV
  • Output switching frequency - <= 10 Hz
  • Switching delay ON/OFF - ≤ 25 ms
  • Switching delay ON/OFF - ≤ 12 ms
  • Switching state indication - Yellow LED "OUT"

Safety Data

  • Internal capacitance C i - 1.1 nF
  • Internal inductance L i - negligible
  • Max. current I o (Ex ia) - 75.00 mA
  • Max. permissible external capacitance C o for IIB - 12.100 μF
  • Max. permissible external capacitance C o for IIC - 1.790 μF
  • Max. permissible external inductance L o for IIB - 25.000 mH
  • Max. permissible external inductance L o for IIC - 6.300 mH
  • Max. Power P o - 210.000 mW
  • Max. Voltage U o - 11.30 V
  • Safety-related maximum voltage - 253 V
222171
222171
R. STAHL Digital Output Loop Powered Ex I Field Circuit
Comprehensive portfolio to cater for all characteristics

two-channel variants reduce the amount of space required

can be used up to SIL 3 (IEC/EN 61508)

Ambient Conditions

  • Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
  • Ambient temperature max. - +70 °C
  • Ambient temperature max. note - Single device
  • Ambient temperature max. note 2 - Group assembly
  • Ambient temperature max.2 - +60 °C
  • Ambient temperature min. - -20 °C
  • Ambient temperature min. 2 - -20 °C
  • Ambient temperature min. note - Single device
  • Ambient temperature min. note 2 - Group assembly
  • Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Umgebungsbedingungen Hinweis - The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide".
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - without
  • Auxiliary power power input - 0,3 W+ (IA x 15 mW / mA)
  • Polarity reversal protection - yes
  • Undervoltage monitoring - No

Electrical Data

  • Number of channels - 1

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - BVS 04 ATEX E 075 X
  • ATEX gas certificate - BVS 04 ATEX E 075 X
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), Korea (KTL), SIL (exida), USA (FM)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection EAC - [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
  • Gas explosion protection EAC - 2 Ex nA [ia Ga] IIC T4 Gc X
  • Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx BVS 13.0012 X
  • IECEX gas certificate - IECEx BVS 13.0012 X
  • Installation in Division NEC 500 - (Class I, II, III) 2
  • Ship approval - CCS, DNVGL

Galvanic isolation

  • Galvanic isolation Ex i output to input - 1,5 kV AC
  • Galvanic isolation input to input - 350 V AC
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 50178

General

  • Functional Description - 9176 series binary outputs issue binary signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are galvanically separated from the inputs. The two-channel variants are characterised by galvanically separated channels.
  • Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
  • Product Description - Digital output loop powered Ex i field circuit
  • Product Type - 9176/10-12-00k
  • Title Product Variant Technical Data - 9176/10-12-00k Digital output l.p.
  • WebCode - 9176A

Input

  • Control Power P E - 0.3 W+ (I A x 15 mW / mA) (with I A = max. required output current)
  • Input - In accordance with EN 61131-2
  • Input voltage for OFF - 0 - 5 V
  • Input voltage for ON - 18.0 - 31.2 V

Mechanical Data

  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 17.60 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.180 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 0.2 mm²
  • Conduct cross-section flexible max. - 2.5 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Spring clamp terminal
  • Mounting position - vertical horizontal
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Internal Resistance R i - 150.00 Ω
  • LFD relay - No
  • Max. output current I a max - 60.00 mA
  • Output internal resistiance R i - 150.00 Ω
  • Output open circuit voltage U a - 10,00 V
  • Output residual ripple - < 100 mV
  • Output switching frequency - <= 10 Hz
  • Switching delay ON/OFF - ≤ 12 ms
  • Switching delay ON/OFF - ≤ 25 ms
  • Switching state indication - Yellow LED "OUT"

Safety Data

  • Internal capacitance C i - 1.1 nF
  • Internal inductance L i - negligible
  • Max. current I o (Ex ia) - 75.00 mA
  • Max. permissible external capacitance C o for IIB - 12.100 μF
  • Max. permissible external capacitance C o for IIC - 1.790 μF
  • Max. permissible external inductance L o for IIB - 25.000 mH
  • Max. permissible external inductance L o for IIC - 6.300 mH
  • Max. Power P o - 210.000 mW
  • Max. Voltage U o - 11.30 V
  • Safety-related maximum voltage - 253 V
222172
222172
R. STAHL Digital Output Loop Powered Ex I Field Circuit
Comprehensive portfolio to cater for all characteristics

two-channel variants reduce the amount of space required

can be used up to SIL 3 (IEC/EN 61508)

Ambient Conditions

  • Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
  • Ambient temperature max. - +70 °C
  • Ambient temperature max. note - Single device
  • Ambient temperature max. note 2 - Group assembly
  • Ambient temperature max.2 - +60 °C
  • Ambient temperature min. - -20 °C
  • Ambient temperature min. 2 - -20 °C
  • Ambient temperature min. note - Single device
  • Ambient temperature min. note 2 - Group assembly
  • Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Umgebungsbedingungen Hinweis - The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide".
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - without
  • Auxiliary power power input - 0,3 W+ (IA x 15 mW / mA)
  • Polarity reversal protection - yes
  • Undervoltage monitoring - No

Electrical Data

  • Number of channels - 2

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - BVS 04 ATEX E 075 X
  • ATEX gas certificate - BVS 04 ATEX E 075 X
  • Certificate EAC - TS RU S-DE.GB04.B.00353
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), Korea (KTL), SIL (exida), USA (FM)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection EAC - [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
  • Gas explosion protection EAC - 2 Ex nA [ia Ga] IIC T4 Gc X
  • Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx BVS 13.0012 X
  • IECEX gas certificate - IECEx BVS 13.0012 X
  • Installation in Division NEC 500 - (Class I, II, III) 2
  • Ship approval - CCS, DNVGL

Galvanic isolation

  • Galvanic isolation Ex i output to input - 1,5 kV AC
  • Galvanic isolation Ex i to Ex i - 500 V AC
  • Galvanic isolation input to input - 350 V AC
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 50178

General

  • Functional Description - 9176 series binary outputs issue binary signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are galvanically separated from the inputs. The two-channel variants are characterised by galvanically separated channels.
  • Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
  • Product Description - Digital output loop powered Ex i field circuit
  • Product Type - 9176/20-12-00s
  • Title Product Variant Technical Data - 9176/20-12-00s Digital output l.p.
  • WebCode - 9176A

Input

  • Control Power P E - 0.3 W+ (I A x 15 mW / mA) (with I A = max. required output current)
  • Input - In accordance with EN 61131-2
  • Input voltage for OFF - 0 - 5 V
  • Input voltage for ON - 18.0 - 31.2 V

Mechanical Data

  • Connection cross-section - 0.2-2.5 mm² flexible 0.2-2.5 mm² rigid 0.25-2.5 mm² flexible core end sleeve
  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 17.60 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.185 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 2.5 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Screw terminal
  • Mounting position - vertical horizontal
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Internal Resistance R i - 150 Ω / 75 Ω*
  • Internal resistance R i note - 150 Ω / 75 Ω
  • LFD relay - No
  • Max. output current I a max - 60.00 mA / 120 mA*
  • Max. output current I a note - 60 mA / 120 mA
  • Output open circuit voltage U a - 10,00 V
  • Output residual ripple - < 100 mV
  • Output switching frequency - <= 10 Hz
  • Switching delay ON/OFF - ≤ 25 ms
  • Switching state indication - Yellow LED "OUT"

Safety Data

  • Internal capacitance C i - 1.1 nF
  • Internal inductance L i - negligible
  • Max. current I o (Ex ia) - 75.00 mA
  • Max. permissible external capacitance C o for IIB - 12.100 μF
  • Max. permissible external capacitance C o for IIC - 1.790 μF
  • Max. permissible external inductance L o for IIB - 25.000 mH
  • Max. permissible external inductance L o for IIC - 6.300 mH
  • Max. Power P o - 210.000 mW
  • Max. Voltage U o - 11.30 V
  • Safety-related maximum voltage - 253 V
222173
222173
R. STAHL Digital Output Loop Powered Ex I Field Circuit
Comprehensive portfolio to cater for all characteristics

two-channel variants reduce the amount of space required

can be used up to SIL 3 (IEC/EN 61508)

Ambient Conditions

  • Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
  • Ambient temperature max. - +70 °C
  • Ambient temperature max. note - Single device
  • Ambient temperature max. note 2 - Group assembly
  • Ambient temperature max.2 - +60 °C
  • Ambient temperature min. - -20 °C
  • Ambient temperature min. 2 - -20 °C
  • Ambient temperature min. note - Single device
  • Ambient temperature min. note 2 - Group assembly
  • Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Umgebungsbedingungen Hinweis - The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide".
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - without
  • Auxiliary power power input - 0,3 W+ (IA x 15 mW / mA)
  • Polarity reversal protection - yes
  • Undervoltage monitoring - No

Electrical Data

  • Number of channels - 2

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - BVS 04 ATEX E 075 X
  • ATEX gas certificate - BVS 04 ATEX E 075 X
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), Korea (KTL), SIL (exida), USA (FM)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection EAC - [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
  • Gas explosion protection EAC - 2 Ex nA [ia Ga] IIC T4 Gc X
  • Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx BVS 13.0012 X
  • IECEX gas certificate - IECEx BVS 13.0012 X
  • Installation in Division NEC 500 - (Class I, II, III) 2
  • Ship approval - CCS, DNVGL

Galvanic isolation

  • Galvanic isolation Ex i output to input - 1,5 kV AC
  • Galvanic isolation Ex i to Ex i - 500 V AC
  • Galvanic isolation input to input - 350 V AC
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 50178

General

  • Functional Description - 9176 series binary outputs issue binary signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are galvanically separated from the inputs. The two-channel variants are characterised by galvanically separated channels.
  • Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
  • Product Description - Digital output loop powered Ex i field circuit
  • Product Type - 9176/20-12-00k
  • Title Product Variant Technical Data - 9176/20-12-00k Digital output l.p.
  • WebCode - 9176A

Input

  • Control Power P E - 0.3 W+ (I A x 15 mW / mA) (with I A = max. required output current)
  • Input - In accordance with EN 61131-2
  • Input voltage for OFF - 0 - 5 V
  • Input voltage for ON - 18.0 - 31.2 V

Mechanical Data

  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 17.60 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.180 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 2.5 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Spring clamp terminal
  • Mounting position - vertical horizontal
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Internal Resistance R i - 150 Ω / 75 Ω*
  • Internal resistance R i note - 150 Ω / 75 Ω
  • LFD relay - No
  • Max. output current I a note - 60 mA / 120 mA
  • Output open circuit voltage U a - 10,00 V
  • Output residual ripple - < 100 mV
  • Output switching frequency - <= 10 Hz
  • Switching delay ON/OFF - ≤ 25 ms
  • Switching state indication - Yellow LED "OUT"

Safety Data

  • Internal capacitance C i - 1.1 nF
  • Internal inductance L i - negligible
  • Max. current I o (Ex ia) - 75.00 mA
  • Max. permissible external capacitance C o for IIB - 12.100 μF
  • Max. permissible external capacitance C o for IIC - 1.790 μF
  • Max. permissible external inductance L o for IIB - 25.000 mH
  • Max. permissible external inductance L o for IIC - 6.300 mH
  • Max. Power P o - 210.000 mW
  • Max. Voltage U o - 11.30 V
  • Safety-related maximum voltage - 253 V
222174
222174
R. STAHL Digital Output Loop Powered Ex I Field Circuit
Comprehensive portfolio to cater for all characteristics

two-channel variants reduce the amount of space required

can be used up to SIL 3 (IEC/EN 61508)

Ambient Conditions

  • Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
  • Ambient temperature max. - +70 °C
  • Ambient temperature max. note - Single device
  • Ambient temperature max. note 2 - Group assembly
  • Ambient temperature max.2 - +60 °C
  • Ambient temperature min. - -20 °C
  • Ambient temperature min. 2 - -20 °C
  • Ambient temperature min. note - Single device
  • Ambient temperature min. note 2 - Group assembly
  • Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Umgebungsbedingungen Hinweis - The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide".
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - without
  • Auxiliary power power input - 0,38 W+ (IA x 26 mW / mA)
  • Polarity reversal protection - yes
  • Undervoltage monitoring - No

Electrical Data

  • Number of channels - 1

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - BVS 04 ATEX E 075 X
  • ATEX gas certificate - BVS 04 ATEX E 075 X
  • Certificate EAC - TS RU S-DE.GB04.B.00353
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection EAC - [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
  • Gas explosion protection EAC - 2 Ex nA [ia Ga] IIC T4 Gc X
  • Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx BVS 13.0012 X
  • IECEX gas certificate - IECEx BVS 13.0012 X
  • Installation in Division NEC 500 - (Class I, II, III) 2
  • Ship approval - CCS, DNVGL

Galvanic isolation

  • Galvanic isolation Ex i output to input - 1,5 kV AC
  • Galvanic isolation input to input - 350 V AC
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 50178

General

  • Functional Description - 9176 series binary outputs issue binary signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are galvanically separated from the inputs. The two-channel variants are characterised by galvanically separated channels.
  • Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
  • Product Description - Digital output loop powered Ex i field circuit
  • Product Type - 9176/10-14-00s
  • WebCode - 9176A

Input

  • Control Power P E - 0.3 W+ (I A x 15 mW / mA) (with I A = max. required output current)
  • Input - In accordance with EN 61131-2
  • Input voltage for OFF - 0 - 5 V
  • Input voltage for ON - 18.0 - 31.2 V

Mechanical Data

  • Connection cross-section - 0.2-2.5 mm² flexible 0.25-2.5 mm² flexible core end sleeve 0.2-2.5 mm² rigid
  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 17.60 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.170 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 2.5 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Screw terminal
  • Mounting position - horizontal vertical
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Internal Resistance R i - 130.00 Ω
  • LFD relay - No
  • Max. output current I a max - 45.00 mA
  • Output internal resistiance R i - 130.00 Ω
  • Output open circuit voltage U a - 17,50 V
  • Output residual ripple - < 100 mV
  • Output switching frequency - <= 10 Hz
  • Switching delay ON/OFF - ≤ 40 ms
  • Switching state indication - Yellow LED "OUT"

Safety Data

  • Internal capacitance C i - 1.1 nF
  • Internal inductance L i - negligible
  • Max. current I o (Ex ia) - 150.00 mA
  • Max. current I o (Ex ib) - 60.0 mA
  • Max. permissible external capacitance C o for IIB - 1.470 μF
  • Max. permissible external capacitance C o for IIC - 0.235 μF
  • Max. permissible external inductance L o for IIB - 6.000 mH
  • Max. permissible external inductance L o for IIC - 1.500 mH
  • Max. Power P o - 732.000 mW
  • Max. Voltage U o - 19.60 V
  • Safety-related maximum voltage - 253 V
222175
222175
R. STAHL Digital Output Loop Powered Ex I Field Circuit
Comprehensive portfolio to cater for all characteristics

two-channel variants reduce the amount of space required

can be used up to SIL 3 (IEC/EN 61508)

Ambient Conditions

  • Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
  • Ambient temperature max. - +70 °C
  • Ambient temperature max. note - Single device
  • Ambient temperature max. note 2 - Group assembly
  • Ambient temperature max.2 - +60 °C
  • Ambient temperature min. - -20 °C
  • Ambient temperature min. 2 - -20 °C
  • Ambient temperature min. note - Single device
  • Ambient temperature min. note 2 - Group assembly
  • Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Umgebungsbedingungen Hinweis - The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide".
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - without
  • Auxiliary power power input - 0,38 W+ (IA x 26 mW / mA)
  • Polarity reversal protection - yes
  • Undervoltage monitoring - No

Electrical Data

  • Number of channels - 1

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - BVS 04 ATEX E 075 X
  • ATEX gas certificate - BVS 04 ATEX E 075 X
  • Certificate EAC - TS RU S-DE.GB04.B.00353
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection EAC - [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
  • Gas explosion protection EAC - 2 Ex nA [ia Ga] IIC T4 Gc X
  • Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx BVS 13.0012 X
  • IECEX gas certificate - IECEx BVS 13.0012 X
  • Installation in Division NEC 500 - (Class I, II, III) 2
  • Ship approval - CCS, DNVGL

Galvanic isolation

  • Galvanic isolation Ex i output to input - 1,5 kV AC
  • Galvanic isolation input to input - 350 V AC
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 50178

General

  • Functional Description - 9176 series binary outputs issue binary signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are galvanically separated from the inputs. The two-channel variants are characterised by galvanically separated channels.
  • Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
  • Product Description - Digital output loop powered Ex i field circuit
  • Product Type - 9176/10-14-00k
  • Title Product Variant Technical Data - 9176/10-14-00k Digital output l.p.
  • WebCode - 9176A

Input

  • Control Power P E - 0.3 W+ (I A x 15 mW / mA) (with I A = max. required output current)
  • Input - In accordance with EN 61131-2
  • Input voltage for OFF - 0 - 5 V
  • Input voltage for ON - 18.0 - 31.2 V

Mechanical Data

  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 17.60 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.180 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 2.5 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Spring clamp terminal
  • Mounting position - vertical horizontal
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Internal Resistance R i - 130.00 Ω
  • LFD relay - No
  • Max. output current I a max - 45.00 mA
  • Output internal resistiance R i - 130.00 Ω
  • Output open circuit voltage U a - 17,50 V
  • Output residual ripple - < 100 mV
  • Output switching frequency - <= 10 Hz
  • Switching delay ON/OFF - ≤ 20 ms
  • Switching state indication - Yellow LED "OUT"

Safety Data

  • Internal capacitance C i - 1.1 nF
  • Internal inductance L i - negligible
  • Max. current I o (Ex ia) - 150.00 mA
  • Max. current I o (Ex ib) - 60.0 mA
  • Max. permissible external capacitance C o for IIB - 1.470 μF
  • Max. permissible external capacitance C o for IIC - 0.235 μF
  • Max. permissible external inductance L o for IIB - 6.000 mH
  • Max. permissible external inductance L o for IIC - 1.500 mH
  • Max. Power P o - 732.000 mW
  • Max. Voltage U o - 19.60 V
  • Safety-related maximum voltage - 253 V
222176
222176
R. STAHL Digital Output Loop Powered Ex I Field Circuit
Comprehensive portfolio to cater for all characteristics

two-channel variants reduce the amount of space required

can be used up to SIL 3 (IEC/EN 61508)

Ambient Conditions

  • Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
  • Ambient temperature max. - +70 °C
  • Ambient temperature max. note - Single device
  • Ambient temperature max. note 2 - Group assembly
  • Ambient temperature max.2 - +60 °C
  • Ambient temperature min. - -20 °C
  • Ambient temperature min. 2 - -20 °C
  • Ambient temperature min. note - Single device
  • Ambient temperature min. note 2 - Group assembly
  • Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Umgebungsbedingungen Hinweis - The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide".
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - without
  • Auxiliary power power input - 0,38 W+ (IA x 26 mW / mA)
  • Polarity reversal protection - yes
  • Undervoltage monitoring - No

Electrical Data

  • Number of channels - 2

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - BVS 04 ATEX E 075 X
  • ATEX gas certificate - BVS 04 ATEX E 075 X
  • Certificate EAC - TS RU S-DE.GB04.B.00353
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection EAC - [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
  • Gas explosion protection EAC - 2 Ex nA [ia Ga] IIC T4 Gc X
  • Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx BVS 13.0012 X
  • IECEX gas certificate - IECEx BVS 13.0012 X
  • Installation in Division NEC 500 - (Class I, II, III) 2
  • Ship approval - CCS, DNVGL

Galvanic isolation

  • Galvanic isolation Ex i output to input - 1,5 kV AC
  • Galvanic isolation Ex i to Ex i - 500 V AC
  • Galvanic isolation input to input - 350 V AC
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 50178

General

  • Functional Description - 9176 series binary outputs issue binary signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are galvanically separated from the inputs. The two-channel variants are characterised by galvanically separated channels.
  • Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
  • Product Description - Digital output loop powered Ex i field circuit
  • Product Type - 9176/20-14-00s
  • Title Product Variant Technical Data - 9176/20-14-00s
  • WebCode - 9176A

Input

  • Control Power P E - 0.3 W+ (I A x 15 mW / mA) (with I A = max. required output current)
  • Input - In accordance with EN 61131-2
  • Input voltage for OFF - 0 - 5 V
  • Input voltage for ON - 18.0 - 31.2 V

Mechanical Data

  • Connection cross-section - 0.2-2.5 mm² flexible 0.25-2.5 mm² flexible core end sleeve 0.2-2.5 mm² rigid
  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 17.60 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.185 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 2.5 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Screw terminal
  • Mounting position - vertical horizontal
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Internal Resistance R i - 130 Ω / 65 Ω*
  • Internal resistance R i note - 130 Ω / 65 Ω
  • LFD relay - No
  • Max. output current I a max - 45.00 mA / 90 mA*
  • Max. output current I a note - 45 mA / 90 mA
  • Output open circuit voltage U a - 17,50 V
  • Output residual ripple - < 100 mV
  • Output switching frequency - <= 10 Hz
  • Switching delay ON/OFF - ≤ 40 ms
  • Switching state indication - Yellow LED "OUT"

Safety Data

  • Internal capacitance C i - 1.1 nF
  • Internal inductance L i - negligible
  • Max. current I o (Ex ia) - 150.00 mA
  • Max. current I o (Ex ib) - 60.0 mA
  • Max. permissible external capacitance C o for IIB - 1.470 μF
  • Max. permissible external capacitance C o for IIC - 0.235 μF
  • Max. permissible external inductance L o for IIB - 6.000 mH
  • Max. permissible external inductance L o for IIC - 1.500 mH
  • Max. Power P o - 732.000 mW
  • Max. Voltage U o - 19.60 V
  • Safety-related maximum voltage - 253 V
222177
222177
R. STAHL Digital Output Loop Powered Ex I Field Circuit
Comprehensive portfolio to cater for all characteristics

two-channel variants reduce the amount of space required

can be used up to SIL 3 (IEC/EN 61508)

Ambient Conditions

  • Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
  • Ambient temperature max. - +70 °C
  • Ambient temperature max. note - Single device
  • Ambient temperature max. note 2 - Group assembly
  • Ambient temperature max.2 - +60 °C
  • Ambient temperature min. - -20 °C
  • Ambient temperature min. 2 - -20 °C
  • Ambient temperature min. note - Single device
  • Ambient temperature min. note 2 - Group assembly
  • Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Umgebungsbedingungen Hinweis - The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide".
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - without
  • Auxiliary power power input - 0,38 W+ (IA x 26 mW / mA)
  • Polarity reversal protection - yes
  • Undervoltage monitoring - No

Electrical Data

  • Number of channels - 2

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - BVS 04 ATEX E 075 X
  • ATEX gas certificate - BVS 04 ATEX E 075 X
  • Certificate EAC - TS RU S-DE.GB04.B.00353
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection EAC - [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
  • Gas explosion protection EAC - 2 Ex nA [ia Ga] IIC T4 Gc X
  • Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx BVS 13.0012 X
  • IECEX gas certificate - IECEx BVS 13.0012 X
  • Installation in Division NEC 500 - (Class I, II, III) 2
  • Ship approval - CCS, DNVGL

Galvanic isolation

  • Galvanic isolation Ex i output to input - 1,5 kV AC
  • Galvanic isolation Ex i to Ex i - 500 V AC
  • Galvanic isolation input to input - 350 V AC
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 50178

General

  • Functional Description - 9176 series binary outputs issue binary signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are galvanically separated from the inputs. The two-channel variants are characterised by galvanically separated channels.
  • Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
  • Product Description - Digital output loop powered Ex i field circuit
  • Product Type - 9176/20-14-00k
  • Title Product Variant Technical Data - 9176/20-14-00k Digital output l.p.
  • WebCode - 9176A

Input

  • Control Power P E - 0.3 W+ (I A x 15 mW / mA) (with I A = max. required output current)
  • Input - In accordance with EN 61131-2
  • Input voltage for OFF - 0 - 5 V
  • Input voltage for ON - 18.0 - 31.2 V

Mechanical Data

  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 17.60 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.180 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 0.2 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Spring clamp terminal
  • Mounting position - horizontal vertical
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Internal Resistance R i - 130 Ω / 65 Ω*
  • Internal resistance R i note - 130 Ω / 65 Ω
  • LFD relay - No
  • Max. output current I a note - 45 mA / 90 mA
  • Output open circuit voltage U a - 17,50 V
  • Output residual ripple - < 100 mV
  • Output switching frequency - <= 10 Hz
  • Switching delay ON/OFF - ≤ 40 ms
  • Switching state indication - Yellow LED "OUT"

Safety Data

  • Internal capacitance C i - 1.1 nF
  • Internal inductance L i - negligible
  • Max. current I o (Ex ia) - 150.00 mA
  • Max. current I o (Ex ib) - 60.0 mA
  • Max. permissible external capacitance C o for IIB - 1.470 μF
  • Max. permissible external capacitance C o for IIC - 0.235 μF
  • Max. permissible external inductance L o for IIB - 6.000 mH
  • Max. permissible external inductance L o for IIC - 1.500 mH
  • Max. Power P o - 732.000 mW
  • Max. Voltage U o - 19.60 V
  • Safety-related maximum voltage - 253 V
222178
222178
R. STAHL Digital Output Loop Powered Ex I Field Circuit
Comprehensive portfolio to cater for all characteristics

two-channel variants reduce the amount of space required

can be used up to SIL 3 (IEC/EN 61508)

Ambient Conditions

  • Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
  • Ambient temperature max. - +70 °C
  • Ambient temperature max. note - Single device
  • Ambient temperature max. note 2 - Group assembly
  • Ambient temperature max.2 - +60 °C
  • Ambient temperature min. - -20 °C
  • Ambient temperature min. 2 - -20 °C
  • Ambient temperature min. note - Single device
  • Ambient temperature min. note 2 - Group assembly
  • Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Umgebungsbedingungen Hinweis - The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide".
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - without
  • Auxiliary power power input - 0,5 W+ (IA x 37 mW / mA)
  • Polarity reversal protection - yes
  • Undervoltage monitoring - No

Electrical Data

  • Number of channels - 1

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - BVS 04 ATEX E 075 X
  • ATEX gas certificate - BVS 04 ATEX E 075 X
  • Certificate EAC - TS RU S-DE.GB04.B.00353
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection EAC - [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
  • Gas explosion protection EAC - 2 Ex nA [ia Ga] IIC T4 Gc X
  • Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx BVS 13.0012 X
  • IECEX gas certificate - IECEx BVS 13.0012 X
  • Installation in Division NEC 500 - (Class I, II, III) 2
  • Ship approval - CCS, DNVGL

Galvanic isolation

  • Galvanic isolation Ex i output to input - 1,5 kV AC
  • Galvanic isolation input to input - 350 V AC
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 50178

General

  • Functional Description - 9176 series binary outputs issue binary signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are galvanically separated from the inputs. The two-channel variants are characterised by galvanically separated channels.
  • Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
  • Product Description - Digital output loop powered Ex i field circuit
  • Product Type - 9176/10-15-00s
  • Title Product Variant Technical Data - 9176/10-15-00s
  • WebCode - 9176A

Input

  • Control Power P E - 0.3 W+ (I A x 15 mW / mA) (with I A = max. required output current)
  • Input - In accordance with EN 61131-2
  • Input voltage for OFF - 0 - 5 V
  • Input voltage for ON - 18.0 - 31.2 V

Mechanical Data

  • Connection cross-section - 0.2-2.5 mm² flexible 0.25-2.5 mm² flexible core end sleeve 0.2-2.5 mm² rigid
  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 17.60 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.170 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 2.5 mm²
  • Conduct cross-section flexible max. - 0.2 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Screw terminal
  • Mounting position - horizontal vertical
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Internal Resistance R i - 320.00 Ω
  • LFD relay - No
  • Max. output current I a max - 29.00 mA
  • Output internal resistiance R i - 320.00 Ω
  • Output open circuit voltage U a - 25,00 V
  • Output residual ripple - < 100 mV
  • Output switching frequency - <= 10 Hz
  • Switching delay ON/OFF - ≤ 50 ms
  • Switching delay ON/OFF - ≤ 18 ms
  • Switching state indication - Yellow LED "OUT"

Safety Data

  • Internal capacitance C i - 1.1 nF
  • Internal inductance L i - negligible
  • Max. current I o (Ex ia) - 86.50 mA
  • Max. current I o (Ex ib) - 44.0 mA
  • Max. permissible external capacitance C o for IIB - 0.667 μF
  • Max. permissible external capacitance C o for IIC - 0.085 μF
  • Max. permissible external inductance L o for IIB - 17.000 mH
  • Max. permissible external inductance L o for IIC - 1.800 mH
  • Max. Power P o - 596.000 mW
  • Max. Voltage U o - 27.60 V
  • Safety-related maximum voltage - 253 V
222179
222179
R. STAHL Digital Output Loop Powered Ex I Field Circuit
Comprehensive portfolio to cater for all characteristics

two-channel variants reduce the amount of space required

can be used up to SIL 3 (IEC/EN 61508)

Ambient Conditions

  • Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
  • Ambient temperature max. - +70 °C
  • Ambient temperature max. note - Single device
  • Ambient temperature max. note 2 - Group assembly
  • Ambient temperature max.2 - +60 °C
  • Ambient temperature min. - -20 °C
  • Ambient temperature min. 2 - -20 °C
  • Ambient temperature min. note - Single device
  • Ambient temperature min. note 2 - Group assembly
  • Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Umgebungsbedingungen Hinweis - The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide".
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - without
  • Auxiliary power power input - 0,5 W+ (IA x 37 mW / mA)
  • Polarity reversal protection - yes
  • Undervoltage monitoring - No

Electrical Data

  • Number of channels - 1

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - BVS 04 ATEX E 075 X
  • ATEX gas certificate - BVS 04 ATEX E 075 X
  • Certificate EAC - TS RU S-DE.GB04.B.00353
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection EAC - [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
  • Gas explosion protection EAC - 2 Ex nA [ia Ga] IIC T4 Gc X
  • Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx BVS 13.0012 X
  • IECEX gas certificate - IECEx BVS 13.0012 X
  • Installation in Division NEC 500 - (Class I, II, III) 2
  • Ship approval - CCS, DNVGL

Galvanic isolation

  • Galvanic isolation Ex i output to input - 1,5 kV AC
  • Galvanic isolation input to input - 350 V AC
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 50178

General

  • Functional Description - 9176 series binary outputs issue binary signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are galvanically separated from the inputs. The two-channel variants are characterised by galvanically separated channels.
  • Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
  • Product Description - Digital output loop powered Ex i field circuit
  • Product Type - 9176/10-15-00k
  • Title Product Variant Technical Data - 9176/10-15-00k Digital output l.p.
  • WebCode - 9176A

Input

  • Control Power P E - 0.3 W+ (I A x 15 mW / mA) (with I A = max. required output current)
  • Input - In accordance with EN 61131-2
  • Input voltage for OFF - 0 - 5 V
  • Input voltage for ON - 18.0 - 31.2 V

Mechanical Data

  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 17.60 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.180 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 0.2 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Spring clamp terminal
  • Mounting position - vertical horizontal
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Internal Resistance R i - 320.00 Ω
  • LFD relay - No
  • Max. output current I a max - 29.00 mA
  • Output internal resistiance R i - 320.00 Ω
  • Output open circuit voltage U a - 25,00 V
  • Output residual ripple - < 100 mV
  • Output switching frequency - <= 10 Hz
  • Switching delay ON/OFF - ≤ 50 ms
  • Switching state indication - Yellow LED "OUT"

Safety Data

  • Internal capacitance C i - 1.1 nF
  • Internal inductance L i - negligible
  • Max. current I o (Ex ia) - 86.50 mA
  • Max. current I o (Ex ib) - 44.0 mA
  • Max. permissible external capacitance C o for IIB - 0.667 μF
  • Max. permissible external capacitance C o for IIC - 0.085 μF
  • Max. permissible external inductance L o for IIB - 17.000 mH
  • Max. permissible external inductance L o for IIC - 1.800 mH
  • Max. Power P o - 596.000 mW
  • Max. Voltage U o - 27.60 V
  • Safety-related maximum voltage - 253 V
222180
222180
R. STAHL Digital Output Loop Powered Ex I Field Circuit
Comprehensive portfolio to cater for all characteristics

two-channel variants reduce the amount of space required

can be used up to SIL 3 (IEC/EN 61508)

Ambient Conditions

  • Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
  • Ambient temperature max. - +70 °C
  • Ambient temperature max. note - Single device
  • Ambient temperature max. note 2 - Group assembly
  • Ambient temperature max.2 - +60 °C
  • Ambient temperature min. - -20 °C
  • Ambient temperature min. 2 - -20 °C
  • Ambient temperature min. note - Single device
  • Ambient temperature min. note 2 - Group assembly
  • Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Umgebungsbedingungen Hinweis - The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide".
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - without
  • Auxiliary power power input - 0,5 W+ (IA x 37 mW / mA)
  • Polarity reversal protection - yes
  • Undervoltage monitoring - No

Electrical Data

  • Number of channels - 2

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - BVS 04 ATEX E 075 X
  • ATEX gas certificate - BVS 04 ATEX E 075 X
  • Certificate EAC - TS RU S-DE.GB04.B.00353
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection EAC - [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
  • Gas explosion protection EAC - 2 Ex nA [ia Ga] IIC T4 Gc X
  • Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx BVS 13.0012 X
  • IECEX gas certificate - IECEx BVS 13.0012 X
  • Installation in Division NEC 500 - (Class I, II, III) 2
  • Ship approval - CCS, DNVGL

Galvanic isolation

  • Galvanic isolation Ex i output to input - 1,5 kV AC
  • Galvanic isolation Ex i to Ex i - 500 V AC
  • Galvanic isolation input to input - 350 V AC
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 50178

General

  • Functional Description - 9176 series binary outputs issue binary signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are galvanically separated from the inputs. The two-channel variants are characterised by galvanically separated channels.
  • Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
  • Product Description - Digital output loop powered Ex i field circuit
  • Product Type - 9176/20-15-00s
  • Title Product Variant Technical Data - 9176/20-15-00s Digital output l.p.
  • WebCode - 9176A

Input

  • Control Power P E - 0.3 W+ (I A x 15 mW / mA) (with I A = max. required output current)
  • Input - In accordance with EN 61131-2
  • Input voltage for OFF - 0 - 5 V
  • Input voltage for ON - 18.0 - 31.2 V

Mechanical Data

  • Connection cross-section - 0.2-2.5 mm² flexible 0.25-2.5 mm² flexible core end sleeve 0.2-2.5 mm² rigid
  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 17.60 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.185 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 2.5 mm²
  • Conduct cross-section flexible max. - 0.2 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Screw terminal
  • Mounting position - vertical horizontal
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Internal Resistance R i - 320 Ω / 160 Ω*
  • Internal resistance R i note - 320 Ω / 160 Ω
  • LFD relay - No
  • Max. output current I a max - 29.00 mA / 58 mA*
  • Max. output current I a note - 29 mA / 58 mA
  • Output open circuit voltage U a - 25,00 V
  • Output residual ripple - < 100 mV
  • Output switching frequency - <= 10 Hz
  • Switching delay ON/OFF - ≤ 18 ms
  • Switching delay ON/OFF - ≤ 50 ms
  • Switching state indication - Yellow LED "OUT"

Safety Data

  • Internal capacitance C i - 1.1 nF
  • Internal inductance L i - negligible
  • Max. current I o (Ex ia) - 86.50 mA
  • Max. current I o (Ex ib) - 44.0 mA
  • Max. permissible external capacitance C o for IIB - 0.667 μF
  • Max. permissible external capacitance C o for IIC - 0.085 μF
  • Max. permissible external inductance L o for IIB - 17.000 mH
  • Max. permissible external inductance L o for IIC - 1.800 mH
  • Max. Power P o - 596.000 mW
  • Max. Voltage U o - 27.60 V
  • Safety-related maximum voltage - 253 V
222181
222181
R. STAHL Digital Output Loop Powered Ex I Field Circuit
Comprehensive portfolio to cater for all characteristics

two-channel variants reduce the amount of space required

can be used up to SIL 3 (IEC/EN 61508)

Ambient Conditions

  • Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
  • Ambient temperature max. - +70 °C
  • Ambient temperature max. note - Single device
  • Ambient temperature max. note 2 - Group assembly
  • Ambient temperature max.2 - +60 °C
  • Ambient temperature min. - -20 °C
  • Ambient temperature min. 2 - -20 °C
  • Ambient temperature min. note - Single device
  • Ambient temperature min. note 2 - Group assembly
  • Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Umgebungsbedingungen Hinweis - The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide".
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - without
  • Auxiliary power power input - 0,5 W+ (IA x 37 mW / mA)
  • Polarity reversal protection - yes
  • Undervoltage monitoring - No

Electrical Data

  • Number of channels - 2

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - BVS 04 ATEX E 075 X
  • ATEX gas certificate - BVS 04 ATEX E 075 X
  • Certificate EAC - TS RU S-DE.GB04.B.00353
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), SIL (exida), USA (FM)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection EAC - [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
  • Gas explosion protection EAC - 2 Ex nA [ia Ga] IIC T4 Gc X
  • Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx BVS 13.0012 X
  • IECEX gas certificate - IECEx BVS 13.0012 X
  • Installation in Division NEC 500 - (Class I, II, III) 2
  • Ship approval - CCS, DNVGL

Galvanic isolation

  • Galvanic isolation Ex i output to input - 1,5 kV AC
  • Galvanic isolation Ex i to Ex i - 500 V AC
  • Galvanic isolation input to input - 350 V AC
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 50178

General

  • Functional Description - 9176 series binary outputs issue binary signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are galvanically separated from the inputs. The two-channel variants are characterised by galvanically separated channels.
  • Highlights - Comprehensive portfolio to cater for all characteristics two-channel variants reduce the amount of space required can be used up to SIL 3 (IEC/EN 61508)
  • Product Description - Digital output loop powered Ex i field circuit
  • Product Type - 9176/20-15-00k
  • Title Product Variant Technical Data - 9176/20-15-00k Digital output l.p.
  • WebCode - 9176A

Input

  • Control Power P E - 0.3 W+ (I A x 15 mW / mA) (with I A = max. required output current)
  • Input - In accordance with EN 61131-2
  • Input voltage for OFF - 0 - 5 V
  • Input voltage for ON - 18.0 - 31.2 V

Mechanical Data

  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 17.60 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.180 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 2.5 mm²
  • Conduct cross-section flexible max. - 0.2 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Spring clamp terminal
  • Mounting position - horizontal vertical
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Internal Resistance R i - 320 Ω / 160 Ω*
  • Internal resistance R i note - 320 Ω / 160 Ω
  • LFD relay - No
  • Max. output current I a note - 29 mA / 58 mA
  • Output open circuit voltage U a - 25,00 V
  • Output residual ripple - < 100 mV
  • Output switching frequency - <= 10 Hz
  • Switching delay ON/OFF - ≤ 18 ms
  • Switching delay ON/OFF - ≤ 50 ms
  • Switching state indication - Yellow LED "OUT"

Safety Data

  • Internal capacitance C i - 1.1 nF
  • Internal inductance L i - negligible
  • Max. current I o (Ex ia) - 86.50 mA
  • Max. current I o (Ex ib) - 44.0 mA
  • Max. permissible external capacitance C o for IIB - 0.667 μF
  • Max. permissible external capacitance C o for IIC - 0.085 μF
  • Max. permissible external inductance L o for IIB - 17.000 mH
  • Max. permissible external inductance L o for IIC - 1.800 mH
  • Max. Power P o - 596.000 mW
  • Max. Voltage U o - 27.60 V
  • Safety-related maximum voltage - 253 V
1 - 12 of 20 Part Numbers