The IP800-Series are impeller (or “paddlewheel”) insertion meters designed for use with a wide variety of clean liquids in pipe sizes 1/2” to 8”. Sensors are available in brass, 316 stainless steel, PVC, and polypropylene. Bodies are machined from a solid rod for maximum precision. Highquality jewel bearings and nickel-bound tungsten carbide shafts are used for extreme low friction and long life. 

The rotation of the rotor is detected by a non-drag Hall-effect sensor. Output is a current-sinking pulse, which can be sent long distances (up to 2,000 feet) without a transmitter. This signal can be connected directly to PLC’s, counters, and computer cards, as well as a variety of Seametrics controls and displays. For rate and total display, a modular system of electronics can be installed directly on the flow sensor or mounted remotely. 

The FT430 (externally powered with pulse), FT440 (loop powered), and FT450 (battery powered) all provide digital rate and total displays, as well as a programmable pulse; the FT440 also provides a 4-20 mA analog output. Electronic modules can be wall- or meter- mounted. If no display is required, a simple divider may be needed, such as the PD10 to provide adjustable pump pacing. 

The IP800-Series require special fittings that ensure correct depth placement in the pipe. Fittings come in a variety of materials for compatibility with specific applications. Tee fittings are individually wetcalibrated at the factory and marked with the K-factor (pulses per gallon). Saddle fittings must be field-installed on the pipe and do not come wet calibrated. K-factors for saddles are based on factory-testing.
Features
  • High-quality ruby bearings for excellent low-flow performance and long life
  • One easily-replaced moving part
  • Pickup exerts no magnetic drag on the rotor
  • Square-wave frequency output can connect directly to PLC's or counter controls
  • Indicator or transmitter can be mounted on the flowmeter or remote
  • Fittings are available in a wide variety of materials and sizes

Specifications

Pipe Size

  • 1/2” to 8”

Power

  • Low Power: 6-36 Vdc/< 2 mA
  • Micropowered (-04 Option): 3.1-16 Vdc/60 μA @ 3.6 Vdc

Sensor

  • Low Power: Digital Magnetoresistive
  • Micropowered (-04 Option): Giant Magnetoresistance (GMR)

Materials Optional Housing

  • Powder-coated cast aluminum

Sensor Body

  • Brass, 316 Stainless Steel, PVC, or Polypropylene

O-ring

  • EPDM (Viton optional)

Rotor

  • PVDF (Kynar®)

Shaft

  • Kynar® /Tungsten Carbide (Kynar® /Ceramic or Kynar®/Silicon Carbide optional)

Bearings

  • Ruby jewel

Pressure

  • 200 psi (14 bar)
  • 175 psi (12 bar) @ 75° F (24° C)

High Pressure

  • 400 psi (28 bar)

Temperature

  • 200° F (93° C)
  • 130° F (55° C)

Flow Velocity

  • 0.3 to 30 ft/sec (0.09 to 9.14 m/sec)

Accuracy

  • ± 1.5 % of full scale

Output Transistor Maximum Current Sinking

  • 150 mA (low power version only)

Cable

  • #22 AWG 3-con, 18’ (6 m); 2,000’ (610 m) maximum cable run Note: 50’ (15 m) maximum for battery powered or micropowered versions.

Regulatory

  • CE Mark

Documentation