Yodify Product Library
Instantly add the Safety Switches Series 8146/5-V37 and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
Safety Switches Series 8146/5-V37
Brand: R. STAHL AGR. STAHL's 8146/5-V37 series safety switches safely disconnect the power supply to machinery and system components for cleaning and repair as prescribed.
They can be used at frequencies from 5 to 400 Hz.
All of the installed load disconnect switches have an AC-3 switching capacity.
The switches can be locked in the 0-position using padlocks.
Features- Can be used with conventional drives and drives controlled by frequency converters
- Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter
- Version complies with IEC/EN 62626-1, Class 1
- The rotary actuator can be locked with 3 padlocks in the 0-position
1 - 12 of 56 Part Numbers
147855
Can be used with conventional drives and drives controlled by frequency converters
Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter
Version complies with IEC/EN 62626-1, Class 1
The rotary actuator can be locked with 3 padlocks in the 0-position
147856
Can be used with conventional drives and drives controlled by frequency converters
Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter
Version complies with IEC/EN 62626-1, Class 1
The rotary actuator can be locked with 3 padlocks in the 0-position
Ambient Conditions
- Ambient temperature - -40 °C ... +51 °C -40 °C ... +51 °C
- Ambient temperature max. - +51 °C
- Ambient temperature max.2 - +51 °C
- Ambient temperature min. - -40 °C
- Ambient temperature min. 2 - -40 °C
- Extended ambient temperature - -40 - 69 °C
- Extended ambient temperature max. - +69 °C
- Extended ambient temperature min. - -40 °C
Components
- Entry type - Brass plate with 8161
Electrical Data
- Auxiliary contact NC - without
- Auxiliary contact NO - 1 NO / delayed
- Frequency range - 50 - 60 Hz
- Rated operational current - 0.000 - 12.000 A
- Rated operational current 2 - 0.000 - 16.000 A
- Rated operational voltage AC - 0.00 - 690.00 V
- Rated operational voltage AC 2 - 0.00 - 690.00 V
- Switching capacity AC-3 230 V - 3.00 - 4.00 kW
- Switching capacity AC-3 400 V - 5.50 - 7.50 kW
- Switching capacity AC-3 440 V - 5.50 - 7.50 kW
- Switching capacity AC-3 500 V - 7.50 - 7.50 kW
- Switching capacity AC-3 690 V - 7.50 - 11.00 kW
Explosion Protection
- Ambient temperature °C - -40 - 51 °C
- Ambient temperature °C 2 - -40 - 51 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 09 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), China (NEPSI), EAC (LPE), IECEx (PTB), Korea (KGS)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection EAC - 1 Ex e * IIA ... IIC T6 ... T3 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL's 8146/5-V37 series safety switches safely disconnect the power supply to machinery and system components for cleaning and repair as prescribed. They can be used at frequencies from 5 to 400 Hz. All of the installed load disconnect switches have an AC-3 switching capacity. The switches can be locked in the 0-position using padlocks.
- Highlights - Can be used with conventional drives and drives controlled by frequency converters Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter Version complies with IEC/EN 62626-1, Class 1 The rotary actuator can be locked with 3 padlocks in the 0-position
- Product Description - Safety switch
- Product Type - 8146/5-V37-301-50-1050
- Title Product Variant Technical Data - 8146/5-V37-301-50-1050 Safety sw. 3p
- WebCode - 8146L
Mechanical Data
- Additional terminal - Standard (without)
- Cable gland - 2 x M25 Ø 7 ... 17 mm 1 x M20 Ø 4 ... 13 mm
- Colour of handle - yellow collar, red handle
- Conductor cross-section max. - 4.00 mm²
- Conductor cross-section min. - 2.50 mm²
- Conductor cross-section min. 2 - 2.50 mm²
- Connection terminals of auxiliary contact finely stranded max. - 2.50 mm²
- Connection terminals of auxiliary contact min. - 1.50 mm²
- Connection terminals of auxiliary contact solid max. - 4.00 mm²
- Construction type - Standard
- Degree of protection (IP) - IP66
- Detailed number of poles - 3-pole
- Dimension A - 112.5 mm
- Dimension B - 112.5 mm
- Dimension C - 131.0 mm
- Enclosure material - Polyester resin, Glass fibre reinforced
- Lockable in - 3x in 0
- Seal - Silicone, foamed
- Seal Notes - Seal optional: EPDM
- Type of connection cable - Finely stranded, solid
- Weight - 0.958 kg
147857
Can be used with conventional drives and drives controlled by frequency converters
Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter
Version complies with IEC/EN 62626-1, Class 1
The rotary actuator can be locked with 3 padlocks in the 0-position
Ambient Conditions
- Ambient temperature - -40 °C ... +51 °C -40 °C ... +51 °C
- Ambient temperature max. - +51 °C
- Ambient temperature max.2 - +51 °C
- Ambient temperature min. - -40 °C
- Ambient temperature min. 2 - -40 °C
- Extended ambient temperature - -40 - 69 °C
- Extended ambient temperature max. - +69 °C
- Extended ambient temperature min. - -40 °C
Components
- Entry type - Brass plate with 8161
Electrical Data
- Auxiliary contact NC - without
- Auxiliary contact NO - 1 NO / delayed
- Frequency range - 50 - 60 Hz
- Rated operational current - 12.00 A / 16.00 A
- Rated operational current 2 - 0.000 - 16.000 A
- Rated operational voltage AC - 690.00 V
- Rated operational voltage AC 2 - 0.00 - 690.00 V
- Switching capacity AC-3 230 V - 3.00 - 4.00 kW
- Switching capacity AC-3 400 V - 5.50 - 7.50 kW
- Switching capacity AC-3 440 V - 5.50 - 7.50 kW
- Switching capacity AC-3 500 V - 7.50 - 7.50 kW
- Switching capacity AC-3 690 V - 7.50 - 11.00 kW
Explosion Protection
- Ambient temperature °C - -40 - 51 °C
- Ambient temperature °C 2 - -40 - 51 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 09 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), China (NEPSI), EAC (LPE), IECEx (PTB), Korea (KGS)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection EAC - 1 Ex e * IIA ... IIC T6 ... T3 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL's 8146/5-V37 series safety switches safely disconnect the power supply to machinery and system components for cleaning and repair as prescribed. They can be used at frequencies from 5 to 400 Hz. All of the installed load disconnect switches have an AC-3 switching capacity. The switches can be locked in the 0-position using padlocks.
- Highlights - Can be used with conventional drives and drives controlled by frequency converters Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter Version complies with IEC/EN 62626-1, Class 1 The rotary actuator can be locked with 3 padlocks in the 0-position
- Product Description - Safety switch
- Product Type - 8146/5-V37-301-50-0150
- Title Product Variant Technical Data - 8146/5-V37-301-50-0150 Safety sw. 3p
- WebCode - 8146L
Mechanical Data
- Additional terminal - with N-terminal
- Cable gland - 2 x M25 Ø 7 ... 17 mm 1 x M20 Ø 4 ... 13 mm
- Colour of handle - Black shroud and handle
- Conductor cross-section max. - 4.00 mm²
- Conductor cross-section min. - 2.50 mm²
- Conductor cross-section min. 2 - 2.50 mm²
- Connection terminals of auxiliary contact finely stranded max. - 2.50 mm²
- Connection terminals of auxiliary contact min. - 1.50 mm²
- Connection terminals of auxiliary contact solid max. - 4.00 mm²
- Construction type - Standard
- Degree of protection (IP) - IP66
- Detailed number of poles - 3-pole
- Dimension A - 112.5 mm
- Dimension B - 112.5 mm
- Dimension C - 131 mm
- Enclosure material - Polyester resin, Glass fibre reinforced
- Lockable in - 3x in 0
- Seal - Silicone, foamed
- Seal Notes - Seal optional: EPDM
- Type of connection cable - Finely stranded, solid
- Weight - 0.982 kg
147858
Can be used with conventional drives and drives controlled by frequency converters
Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter
Version complies with IEC/EN 62626-1, Class 1
The rotary actuator can be locked with 3 padlocks in the 0-position
Ambient Conditions
- Ambient temperature - -40 °C ... +51 °C -40 °C ... +51 °C
- Ambient temperature max. - +51 °C
- Ambient temperature max.2 - +51 °C
- Ambient temperature min. - -40 °C
- Ambient temperature min. 2 - -40 °C
- Extended ambient temperature - -40 - 69 °C
- Extended ambient temperature max. - +69 °C
- Extended ambient temperature min. - -40 °C
Components
- Entry type - Brass plate with 8161
Electrical Data
- Auxiliary contact NC - without
- Auxiliary contact NO - 1 NO / delayed
- Frequency range - 50 - 60 Hz
- Rated operational current - 12.000 A
- Rated operational current 2 - 0.000 - 16.000 A
- Rated operational voltage AC - 0.00 - 690.00 V
- Rated operational voltage AC 2 - 0.00 - 690.00 V
- Switching capacity AC-3 230 V - 3.00 - 4.00 kW
- Switching capacity AC-3 400 V - 5.50 - 7.50 kW
- Switching capacity AC-3 440 V - 5.50 - 7.50 kW
- Switching capacity AC-3 500 V - 7.50 - 7.50 kW
- Switching capacity AC-3 690 V - 7.50 - 11.00 kW
Explosion Protection
- Ambient temperature °C - -40 - 51 °C
- Ambient temperature °C 2 - -40 - 51 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 09 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), China (NEPSI), EAC (LPE), IECEx (PTB), Korea (KGS)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection EAC - 1 Ex e * IIA ... IIC T6 ... T3 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL's 8146/5-V37 series safety switches safely disconnect the power supply to machinery and system components for cleaning and repair as prescribed. They can be used at frequencies from 5 to 400 Hz. All of the installed load disconnect switches have an AC-3 switching capacity. The switches can be locked in the 0-position using padlocks.
- Highlights - Can be used with conventional drives and drives controlled by frequency converters Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter Version complies with IEC/EN 62626-1, Class 1 The rotary actuator can be locked with 3 padlocks in the 0-position
- Product Description - Safety switch
- Product Type - 8146/5-V37-301-50-1150
- Title Product Variant Technical Data - 8146/5-V37-301-50-1150 Safety sw. 3p
- WebCode - 8146L
Mechanical Data
- Additional terminal - with N-terminal
- Cable gland - 2 x M25 Ø 7 ... 17 mm 1 x M20 Ø 4 ... 13 mm
- Colour of handle - yellow collar, red handle
- Conductor cross-section max. - 4.00 mm²
- Conductor cross-section min. - 2.50 mm²
- Conductor cross-section min. 2 - 2.50 mm²
- Connection terminals of auxiliary contact finely stranded max. - 2.50 mm²
- Connection terminals of auxiliary contact min. - 1.50 mm²
- Connection terminals of auxiliary contact solid max. - 4.00 mm²
- Construction type - Standard
- Degree of protection (IP) - IP66
- Detailed number of poles - 3-pole
- Dimension A - 112.5 mm
- Dimension B - 112.5 mm
- Dimension C - 131 mm
- Enclosure material - Polyester resin, Glass fibre reinforced
- Lockable in - 3x in 0
- Seal - Silicone, foamed
- Seal Notes - Seal optional: EPDM
- Type of connection cable - Finely stranded, solid
- Weight - 0.978 kg
200206
Can be used with conventional drives and drives controlled by frequency converters
Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter
Version complies with IEC/EN 62626-1, Class 1
The rotary actuator can be locked with 3 padlocks in the 0-position
Ambient Conditions
- Ambient temperature - -40 °C ... +48 °C
- Ambient temperature max. - +48 °C
- Ambient temperature min. - -40 °C
- Extended ambient temperature - -40 - 66 °C
- Extended ambient temperature max. - +66 °C
- Extended ambient temperature min. - -40 °C
Components
- Entry type - Standard 8161, moulded material
Electrical Data
- Auxiliary contact NC - 1 NC
- Auxiliary contact NO - 1 NO / delayed
- Frequency range - 50 - 60 Hz
- Rated operational current - 40.00 A
- Rated operational current - 40.000 A
- Rated operational current - 0.000 - 40.000 A
- Rated operational voltage AC - 0.00 - 690.00 V
- Rated operational voltage AC - 690.00 V
- Switching capacity AC-3 230 V - 11.00 kW
- Switching capacity AC-3 400 V - 22.00 kW
- Switching capacity AC-3 440 V - 22.00 kW
- Switching capacity AC-3 500 V - 22.00 kW
- Switching capacity AC-3 690 V - 37.00 kW
Explosion Protection
- Ambient temperature °C - -40 - 48 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 09 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), China (NEPSI), EAC (LPE), IECEx (PTB), Korea (KGS)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection EAC - 1 Ex e * IIA ... IIC T6 ... T3 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL's 8146/5-V37 series safety switches safely disconnect the power supply to machinery and system components for cleaning and repair as prescribed. They can be used at frequencies from 5 to 400 Hz. All of the installed load disconnect switches have an AC-3 switching capacity. The switches can be locked in the 0-position using padlocks.
- Highlights - Can be used with conventional drives and drives controlled by frequency converters Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter Version complies with IEC/EN 62626-1, Class 1 The rotary actuator can be locked with 3 padlocks in the 0-position
- Product Description - Safety switch
- Product Type - 8146/5-V37-305-51-0010-K
- Title Product Variant Technical Data - 8146/5-V37-305-51-0010-K Safety sw. 3p
- WebCode - 8146L
Mechanical Data
- Additional terminal - Standard (without)
- Cable gland - 2 x M40 Ø 12 ... 28 mm 1 x M20 Ø 4 ... 13 mm
- Colour of handle - Black shroud and handle
- Conductor cross-section max. - 25.00 mm²
- Conductor cross-section min. - 10.00 mm²
- Connection terminals of auxiliary contact finely stranded max. - 2.50 mm²
- Connection terminals of auxiliary contact min. - 0.75 mm²
- Construction type - Compact design
- Degree of protection (IP) - IP66
- Detailed number of poles - 3-pole
- Dimension A - 340.5 mm
- Dimension B - 170 mm
- Dimension B - 170.0 mm
- Dimension C - 176.5 mm
- Enclosure material - Polyester resin, Glass fibre reinforced
- Lockable in - 3x in 0
- Seal - Silicone, foamed
- Seal Notes - Seal optional: EPDM
- Type of connection cable - Finely stranded, solid
- Weight - 5.560 kg
200207
Can be used with conventional drives and drives controlled by frequency converters
Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter
Version complies with IEC/EN 62626-1, Class 1
The rotary actuator can be locked with 3 padlocks in the 0-position
Ambient Conditions
- Ambient temperature - -40 °C ... +48 °C
- Ambient temperature max. - +48 °C
- Ambient temperature min. - -40 °C
- Extended ambient temperature - -40 - 66 °C
- Extended ambient temperature max. - +66 °C
- Extended ambient temperature min. - -40 °C
Components
- Entry type - Standard 8161, moulded material
Electrical Data
- Auxiliary contact NC - 1 NC
- Auxiliary contact NO - 1 NO / delayed
- Frequency range - 50 - 60 Hz
- Rated operational current - 0.000 - 40.000 A
- Rated operational voltage AC - 690.00 V
- Switching capacity AC-3 230 V - 11.00 kW
- Switching capacity AC-3 400 V - 22.00 kW
- Switching capacity AC-3 440 V - 22.00 kW
- Switching capacity AC-3 500 V - 22.00 kW
- Switching capacity AC-3 690 V - 37.00 kW
Explosion Protection
- Ambient temperature °C - -40 - 48 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 09 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), China (NEPSI), EAC (LPE), IECEx (PTB), Korea (KGS)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection EAC - 1 Ex e * IIA ... IIC T6 ... T3 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL's 8146/5-V37 series safety switches safely disconnect the power supply to machinery and system components for cleaning and repair as prescribed. They can be used at frequencies from 5 to 400 Hz. All of the installed load disconnect switches have an AC-3 switching capacity. The switches can be locked in the 0-position using padlocks.
- Highlights - Can be used with conventional drives and drives controlled by frequency converters Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter Version complies with IEC/EN 62626-1, Class 1 The rotary actuator can be locked with 3 padlocks in the 0-position
- Product Description - Safety switch
- Product Type - 8146/5-V37-305-51-1010-K
- Title Product Variant Technical Data - 8146/5-V37-305-51-1010-K Safety sw. 3p
- WebCode - 8146L
Mechanical Data
- Additional terminal - Standard (without)
- Cable gland - 2 x M40 Ø 12 ... 28 mm 1 x M20 Ø 4 ... 13 mm
- Colour of handle - yellow collar, red handle
- Conductor cross-section max. - 25.00 mm²
- Conductor cross-section min. - 10.00 mm²
- Connection terminals of auxiliary contact finely stranded max. - 2.50 mm²
- Connection terminals of auxiliary contact min. - 0.75 mm²
- Construction type - Compact design
- Degree of protection (IP) - IP66
- Detailed number of poles - 3-pole
- Dimension A - 340.5 mm
- Dimension B - 170.0 mm
- Dimension C - 176.5 mm
- Enclosure material - Polyester resin, Glass fibre reinforced
- Lockable in - 3x in 0
- Seal - Silicone, foamed
- Seal Notes - Seal optional: EPDM
- Type of connection cable - Finely stranded, solid
- Weight - 5.520 kg
200208
Can be used with conventional drives and drives controlled by frequency converters
Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter
Version complies with IEC/EN 62626-1, Class 1
The rotary actuator can be locked with 3 padlocks in the 0-position
Ambient Conditions
- Ambient temperature - -40 °C ... +48 °C
- Ambient temperature max. - +48 °C
- Ambient temperature min. - -40 °C
- Extended ambient temperature - -40 - 66 °C
- Extended ambient temperature max. - +66 °C
- Extended ambient temperature min. - -40 °C
Components
- Entry type - Standard 8161, moulded material
Electrical Data
- Auxiliary contact NC - 1 NC
- Auxiliary contact NO - 1 NO / delayed
- Frequency range - 50 - 60 Hz
- Rated operational current - 40.00 A
- Rated operational voltage AC - 690.00 V
- Switching capacity AC-3 230 V - 11.00 kW
- Switching capacity AC-3 400 V - 22.00 kW
- Switching capacity AC-3 440 V - 22.00 kW
- Switching capacity AC-3 500 V - 22.00 kW
- Switching capacity AC-3 690 V - 37.00 kW
Explosion Protection
- Ambient temperature °C - -40 - 48 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 09 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), China (NEPSI), EAC (LPE), IECEx (PTB), Korea (KGS)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection EAC - 1 Ex e * IIA ... IIC T6 ... T3 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL's 8146/5-V37 series safety switches safely disconnect the power supply to machinery and system components for cleaning and repair as prescribed. They can be used at frequencies from 5 to 400 Hz. All of the installed load disconnect switches have an AC-3 switching capacity. The switches can be locked in the 0-position using padlocks.
- Highlights - Can be used with conventional drives and drives controlled by frequency converters Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter Version complies with IEC/EN 62626-1, Class 1 The rotary actuator can be locked with 3 padlocks in the 0-position
- Product Description - Safety switch
- Product Type - 8146/5-V37-305-51-1110-K
- Title Product Variant Technical Data - 8146/5-V37-305-51-1110-K Safety sw. 3p
- WebCode - 8146L
Mechanical Data
- Additional terminal - with N-terminal
- Cable gland - 2 x M40 Ø 12 ... 28 mm 1 x M20 Ø 4 ... 13 mm
- Colour of handle - yellow collar, red handle
- Conductor cross-section max. - 25.00 mm²
- Conductor cross-section min. - 10.00 mm²
- Connection terminals of auxiliary contact finely stranded max. - 2.50 mm²
- Connection terminals of auxiliary contact min. - 0.75 mm²
- Construction type - Compact design
- Degree of protection (IP) - IP66
- Detailed number of poles - 3-pole
- Dimension A - 340.5 mm
- Dimension B - 170.0 mm
- Dimension C - 176.5 mm
- Enclosure material - Polyester resin, Glass fibre reinforced
- Lockable in - 3x in 0
- Seal - Silicone, foamed
- Seal Notes - Seal optional: EPDM
- Type of connection cable - Finely stranded, solid
- Weight - 5.900 kg
200290
Can be used with conventional drives and drives controlled by frequency converters
Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter
Version complies with IEC/EN 62626-1, Class 1
The rotary actuator can be locked with 3 padlocks in the 0-position
Ambient Conditions
- Ambient temperature - -40 °C ... +47 °C
- Ambient temperature max. - +47 °C
- Ambient temperature min. - -40 °C
- Extended ambient temperature - -40 - 62 °C
- Extended ambient temperature max. - +62 °C
- Extended ambient temperature min. - -40 °C
Components
- Entry type - Standard 8161, moulded material
Electrical Data
- Auxiliary contact NC - 1 NC
- Auxiliary contact NO - 1 NO / delayed
- Frequency range - 50 - 60 Hz
- Rated operational current - 40.000 A
- Rated operational voltage AC - 0.00 - 690.00 V
- Switching capacity AC-3 230 V - 11.00 kW
- Switching capacity AC-3 400 V - 22.00 kW
- Switching capacity AC-3 440 V - 22.00 kW
- Switching capacity AC-3 500 V - 22.00 kW
- Switching capacity AC-3 690 V - 37.00 kW
Explosion Protection
- Ambient temperature °C - -40 - 47 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 09 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), China (NEPSI), EAC (LPE), IECEx (PTB), Korea (KGS)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection EAC - 1 Ex e * IIA ... IIC T6 ... T3 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL's 8146/5-V37 series safety switches safely disconnect the power supply to machinery and system components for cleaning and repair as prescribed. They can be used at frequencies from 5 to 400 Hz. All of the installed load disconnect switches have an AC-3 switching capacity. The switches can be locked in the 0-position using padlocks.
- Highlights - Can be used with conventional drives and drives controlled by frequency converters Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter Version complies with IEC/EN 62626-1, Class 1 The rotary actuator can be locked with 3 padlocks in the 0-position
- Product Description - Safety switch
- Product Type - 8146/5-V37-605-51-0010-K
- Title Product Variant Technical Data - 8146/5-V37-605-51-0010-K Safety sw. 6p
- WebCode - 8146L
Mechanical Data
- Additional terminal - Standard (without)
- Cable gland - 2 x M40 Ø 12 ... 28 mm 1 x M20 Ø 4 ... 13 mm
- Colour of handle - Black shroud and handle
- Conductor cross-section max. - 25.00 mm²
- Conductor cross-section min. - 10.00 mm²
- Connection terminals of auxiliary contact finely stranded max. - 2.50 mm²
- Connection terminals of auxiliary contact min. - 0.75 mm²
- Construction type - Compact design
- Degree of protection (IP) - IP66
- Detailed number of poles - 6-pole
- Dimension A - 340.5 mm
- Dimension B - 340.5 mm
- Dimension C - 205.0 mm
- Enclosure material - Polyester resin, Glass fibre reinforced
- Lockable in - 3x in 0
- Seal - Silicone, foamed
- Seal Notes - Seal optional: EPDM
- Type of connection cable - Finely stranded, solid
- Weight - 10.960 kg
200311
Can be used with conventional drives and drives controlled by frequency converters
Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter
Version complies with IEC/EN 62626-1, Class 1
The rotary actuator can be locked with 3 padlocks in the 0-position
Ambient Conditions
- Ambient temperature - -40 °C ... +47 °C
- Ambient temperature max. - +47 °C
- Ambient temperature min. - -40 °C
- Extended ambient temperature - -40 - 62 °C
- Extended ambient temperature max. - +62 °C
- Extended ambient temperature min. - -40 °C
Components
- Entry type - Standard 8161, moulded material
Electrical Data
- Auxiliary contact NC - without
- Auxiliary contact NO - without
- Frequency range - 50 - 60 Hz
- Rated operational current - 40.00 A
- Rated operational voltage AC - 690.00 V
- Switching capacity AC-3 230 V - 11.00 kW
- Switching capacity AC-3 400 V - 22.00 kW
- Switching capacity AC-3 440 V - 22.00 kW
- Switching capacity AC-3 500 V - 22.00 kW
- Switching capacity AC-3 690 V - 37.00 kW
Explosion Protection
- Ambient temperature °C - -40 - 47 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 09 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), China (NEPSI), EAC (LPE), IECEx (PTB), Korea (KGS)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection EAC - 1 Ex e * IIA ... IIC T6 ... T3 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL's 8146/5-V37 series safety switches safely disconnect the power supply to machinery and system components for cleaning and repair as prescribed. They can be used at frequencies from 5 to 400 Hz. All of the installed load disconnect switches have an AC-3 switching capacity. The switches can be locked in the 0-position using padlocks.
- Highlights - Can be used with conventional drives and drives controlled by frequency converters Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter Version complies with IEC/EN 62626-1, Class 1 The rotary actuator can be locked with 3 padlocks in the 0-position
- Product Description - Safety switch
- Product Type - 8146/5-V37-605-00-0010-K
- Title Product Variant Technical Data - 8146/5-V37-605-00-0010-K Safety sw. 6p
- WebCode - 8146L
Mechanical Data
- Additional terminal - Standard (without)
- Cable gland - 2 x M40 Ø 12 ... 28 mm 1 x M20 Ø 4 ... 13 mm
- Colour of handle - Black shroud and handle
- Conductor cross-section max. - 25.00 mm²
- Conductor cross-section min. - 10.00 mm²
- Connection terminals of auxiliary contact finely stranded max. - 2.50 mm²
- Connection terminals of auxiliary contact min. - 0.75 mm²
- Construction type - Compact design
- Degree of protection (IP) - IP66
- Detailed number of poles - 6-pole
- Dimension A - 340.5 mm
- Dimension B - 340.5 mm
- Dimension C - 205 mm
- Enclosure material - Polyester resin, Glass fibre reinforced
- Lockable in - 3x in 0
- Seal - Silicone, foamed
- Seal Notes - Seal optional: EPDM
- Type of connection cable - Finely stranded, solid
- Weight - 10.960 kg
200558
Can be used with conventional drives and drives controlled by frequency converters
Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter
Version complies with IEC/EN 62626-1, Class 1
The rotary actuator can be locked with 3 padlocks in the 0-position
Ambient Conditions
- Ambient temperature - -40 °C ... +42 °C -40 °C ... +40 °C
- Ambient temperature max. - +42 °C
- Ambient temperature max.2 - +40 °C
- Ambient temperature min. - -40 °C
- Ambient temperature min. 2 - -40 °C
- Extended ambient temperature - -40 - 57 °C
- Extended ambient temperature max. - +57 °C
- Extended ambient temperature min. - -40 °C
Components
- Entry type - Standard 8161, moulded material
Electrical Data
- Auxiliary contact NC - 1 NC
- Auxiliary contact NO - 1 NO / delayed
- Frequency range - 50 - 60 Hz
- Rated operational current - 63.000 A
- Rated operational current 2 - 0.000 - 80.000 A
- Rated operational voltage AC - 690.00 V
- Rated operational voltage AC 2 - 0.00 - 500.00 V
- Switching capacity AC-3 230 V - 18.50 - 22.00 kW
- Switching capacity AC-3 400 V - 30.00 - 45.00 kW
- Switching capacity AC-3 440 V - 37.00 - 45.00 kW
- Switching capacity AC-3 500 V - 37.00 - 55.00 kW
- Switching capacity AC-3 690 V - 55.00 - -- kW
Explosion Protection
- Ambient temperature °C - -40 - 42 °C
- Ambient temperature °C 2 - -40 - 40 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 09 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), China (NEPSI), EAC (LPE), IECEx (PTB), Korea (KGS)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection EAC - 1 Ex e * IIA ... IIC T6 ... T3 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL's 8146/5-V37 series safety switches safely disconnect the power supply to machinery and system components for cleaning and repair as prescribed. They can be used at frequencies from 5 to 400 Hz. All of the installed load disconnect switches have an AC-3 switching capacity. The switches can be locked in the 0-position using padlocks.
- Highlights - Can be used with conventional drives and drives controlled by frequency converters Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter Version complies with IEC/EN 62626-1, Class 1 The rotary actuator can be locked with 3 padlocks in the 0-position
- Product Description - Safety switch
- Product Type - 8146/5-V37-306-51-0010-K
- Title Product Variant Technical Data - 8146/5-V37-306-51-0010-K Safety sw. 3p
- WebCode - 8146L
Mechanical Data
- Additional terminal - Standard (without)
- Cable gland - 2 x M50 Ø 16 ... 35 mm 1 x M20 Ø 4 ... 13 mm
- Colour of handle - Black shroud and handle
- Conductor cross-section max. - 25.00 mm²
- Conductor cross-section min. - 16.00 mm²
- Conductor cross-section min. 2 - 25.00 mm²
- Connection terminals of auxiliary contact finely stranded max. - 2.50 mm²
- Connection terminals of auxiliary contact min. - 0.75 mm²
- Construction type - Compact design
- Degree of protection (IP) - IP66
- Detailed number of poles - 3-pole
- Dimension A - 340.5 mm
- Dimension B - 170 mm
- Dimension C - 195.0 mm
- Enclosure material - Polyester resin, Glass fibre reinforced
- Lockable in - 3x in 0
- Seal - Silicone, foamed
- Seal Notes - Seal optional: EPDM
- Type of connection cable - Finely stranded, solid
- Weight - 5.680 kg
200559
Can be used with conventional drives and drives controlled by frequency converters
Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter
Version complies with IEC/EN 62626-1, Class 1
The rotary actuator can be locked with 3 padlocks in the 0-position
Ambient Conditions
- Ambient temperature - -40 °C ... +42 °C -40 °C ... +40 °C
- Ambient temperature max. - +42 °C
- Ambient temperature max.2 - +40 °C
- Ambient temperature min. - -40 °C
- Ambient temperature min. 2 - -40 °C
- Extended ambient temperature - -40 - 57 °C
- Extended ambient temperature max. - +57 °C
- Extended ambient temperature min. - -40 °C
Components
- Entry type - Standard 8161, moulded material
Electrical Data
- Auxiliary contact NC - 1 NC
- Auxiliary contact NO - 1 NO / delayed
- Frequency range - 50 - 60 Hz
- Rated operational current - 63.000 A
- Rated operational current 2 - 0.000 - 80.000 A
- Rated operational voltage AC - 0.00 - 690.00 V
- Rated operational voltage AC 2 - 0.00 - 500.00 V
- Switching capacity AC-3 230 V - 18.50 - 22.00 kW
- Switching capacity AC-3 400 V - 30.00 - 45.00 kW
- Switching capacity AC-3 440 V - 37.00 - 45.00 kW
- Switching capacity AC-3 500 V - 37.00 - 55.00 kW
- Switching capacity AC-3 690 V - 55.00 - -- kW
Explosion Protection
- Ambient temperature °C - -40 - 42 °C
- Ambient temperature °C 2 - -40 - 40 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 09 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), China (NEPSI), EAC (LPE), IECEx (PTB), Korea (KGS)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection EAC - 1 Ex e * IIA ... IIC T6 ... T3 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL's 8146/5-V37 series safety switches safely disconnect the power supply to machinery and system components for cleaning and repair as prescribed. They can be used at frequencies from 5 to 400 Hz. All of the installed load disconnect switches have an AC-3 switching capacity. The switches can be locked in the 0-position using padlocks.
- Highlights - Can be used with conventional drives and drives controlled by frequency converters Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter Version complies with IEC/EN 62626-1, Class 1 The rotary actuator can be locked with 3 padlocks in the 0-position
- Product Description - Safety switch
- Product Type - 8146/5-V37-306-51-1010-K
- Title Product Variant Technical Data - 8146/5-V37-306-51-1010-K Safety sw. 3p
- WebCode - 8146L
Mechanical Data
- Additional terminal - Standard (without)
- Cable gland - 2 x M50 Ø 16 ... 35 mm 1 x M20 Ø 4 ... 13 mm
- Colour of handle - yellow collar, red handle
- Conductor cross-section max. - 25.00 mm²
- Conductor cross-section min. - 16.00 mm²
- Conductor cross-section min. 2 - 25.00 mm²
- Connection terminals of auxiliary contact finely stranded max. - 2.50 mm²
- Connection terminals of auxiliary contact min. - 0.75 mm²
- Construction type - Compact design
- Degree of protection (IP) - IP66
- Detailed number of poles - 3-pole
- Dimension A - 340.5 mm
- Dimension B - 170 mm
- Dimension C - 195.0 mm
- Enclosure material - Polyester resin, Glass fibre reinforced
- Lockable in - 3x in 0
- Seal - Silicone, foamed
- Seal Notes - Seal optional: EPDM
- Type of connection cable - Finely stranded, solid
- Weight - 5.680 kg
200560
Can be used with conventional drives and drives controlled by frequency converters
Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter
Version complies with IEC/EN 62626-1, Class 1
The rotary actuator can be locked with 3 padlocks in the 0-position
Ambient Conditions
- Ambient temperature - -40 °C ... +42 °C -40 °C ... +40 °C
- Ambient temperature max. - +42 °C
- Ambient temperature max.2 - +40 °C
- Ambient temperature min. - -40 °C
- Ambient temperature min. 2 - -40 °C
- Extended ambient temperature - -40 - 57 °C
- Extended ambient temperature max. - +57 °C
- Extended ambient temperature min. - -40 °C
Components
- Entry type - Standard 8161, moulded material
Electrical Data
- Auxiliary contact NC - 1 NC
- Auxiliary contact NO - 1 NO / delayed
- Frequency range - 50 - 60 Hz
- Rated operational current - 63.000 A
- Rated operational current 2 - 0.000 - 80.000 A
- Rated operational voltage AC - 690.00 V
- Rated operational voltage AC 2 - 0.00 - 500.00 V
- Switching capacity AC-3 230 V - 18.50 - 22.00 kW
- Switching capacity AC-3 400 V - 30.00 - 45.00 kW
- Switching capacity AC-3 440 V - 37.00 - 45.00 kW
- Switching capacity AC-3 500 V - 37.00 - 55.00 kW
- Switching capacity AC-3 690 V - 55.00 - -- kW
Explosion Protection
- Ambient temperature °C - -40 - 42 °C
- Ambient temperature °C 2 - -40 - 40 °C
- Application range (zones) - 1, 2, 21, 22
- ATEX dust certificate - PTB 09 ATEX 1024
- ATEX gas certificate - PTB 01 ATEX 1024
- Certificate EAC - TS RU S-DE.AA71.B.00139
- Certificates - ATEX (PTB), China (NEPSI), EAC (LPE), IECEx (PTB), Korea (KGS)
- Dust explosion protection ATEX - II 2 D Ex tb IIIC T80 °C Db
- Dust explosion protection EAC - Ex tb IIIC T80 °C ... T130 °C Db X
- Dust explosion protection IECEx - Ex tb IIIC T80 °C Db
- Gas explosion protection ATEX - II 2 G Ex db eb IIC T6 Gb
- Gas explosion protection EAC - 1 Ex e * IIA ... IIC T6 ... T3 Gb X
- Gas explosion protection IECEx - Ex db eb IIC T6 Gb
- IECEX dust certificate - IECEx PTB 06.0090
- IECEX gas certificate - IECEx PTB 06.0090
General
- Functional Description - R. STAHL's 8146/5-V37 series safety switches safely disconnect the power supply to machinery and system components for cleaning and repair as prescribed. They can be used at frequencies from 5 to 400 Hz. All of the installed load disconnect switches have an AC-3 switching capacity. The switches can be locked in the 0-position using padlocks.
- Highlights - Can be used with conventional drives and drives controlled by frequency converters Intelligent design: A single rotary actuator for actuating both main and auxiliary contacts, ≥ 20 ms leading auxiliary contact for safely disconnecting the frequency converter Version complies with IEC/EN 62626-1, Class 1 The rotary actuator can be locked with 3 padlocks in the 0-position
- Product Description - Safety switch
- Product Type - 8146/5-V37-306-51-1110-K
- Title Product Variant Technical Data - 8146/5-V37-306-51-1110-K Safety sw. 3p
- WebCode - 8146L
Mechanical Data
- Additional terminal - with N-terminal
- Cable gland - 2 x M50 Ø 16 ... 35 mm 1 x M20 Ø 4 ... 13 mm
- Colour of handle - yellow collar, red handle
- Conductor cross-section max. - 25.00 mm²
- Conductor cross-section min. - 16.00 mm²
- Conductor cross-section min. 2 - 25.00 mm²
- Connection terminals of auxiliary contact finely stranded max. - 2.50 mm²
- Connection terminals of auxiliary contact min. - 0.75 mm²
- Construction type - Compact design
- Degree of protection (IP) - IP66
- Detailed number of poles - 3-pole
- Dimension A - 340.5 mm
- Dimension B - 170 mm
- Dimension C - 195 mm
- Enclosure material - Polyester resin, Glass fibre reinforced
- Lockable in - 3x in 0
- Seal - Silicone, foamed
- Seal Notes - Seal optional: EPDM
- Type of connection cable - Finely stranded, solid
- Weight - 5.680 kg
1 - 12 of 56 Part Numbers